APC APBX700UI Manual
Læs nedenfor 📖 manual på dansk for APC APBX700UI (1 sider) i kategorien Server. Denne guide var nyttig for 26 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere
Side 1/1
Back-UPS
BX700U Series
Safety and General Information
Inspect the package contents upon receipt. Notify the
carrier and dealer if there is any damage.
Read the following reminders before installing the UPS.
User Guide
4
12
5
Status Indicators
• This UPS is intended for indoor use only.
• Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
• When grounding cannot be verified, disconnect the equipment from the AC power outlet before
installing or connecting to other equipment. Reconnect the power cord after all connections are made.
• Servicing of batteries should be performed by Schneider Electric IT (SEIT) Customer Support only.
• When replacing battery the UPS must be OFF, and its AC inlet unplugged.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin
and eyes.
• To avoid harmful injury due to energy hazard, remove wrist watches and jewelry such as rings
when replacing the batteries. Use tools with insulated handles.
• Replace batteries with the same number and type of batteries as origin
ally installed in the
equipment.
LED Audible Alarm Condition
On Off On-line
- The Back-UPS is su
pplying AC power to
the connected equipment
Constant Tone On Line Overload - The power being used by the
connected equipment has exceeded the capacity of the
unit. Disconnect some equipment
Constant beeping Over-temperature Warning - The unit is
overheating and will shut down if the temperature is
not lowered. Disconnect some of the connected
equipment.
On
(Off during 4 beeps)
4 beeps repeated every 30
seconds
On-Battery - The Back-UPS is supplying battery
power
Flashing Rapid Beeping
(every 1/2 second)
Low Battery Warning - The Back-UPS has 2
minutes of runtime remaining
Constant tone Bad Battery Detected - The battery needs to be
charged, or is at end of life.
Chirp every 2 seconds Charger Warning - The Back-UPS has experienced
an internal problem, but is still providing power to the
connected equipment. Contact Schneider Electric IT
(SEIT) Technical Support
Off Short beep every
4 seconds
Low Battery Shutdown - During On Battery
operation the battery power was almost completely
exhausted, and the Back-UPS is waiting for AC
power to return to normal
Constant Tone On Battery Overload - The connected equipment
requires more power than provided by the Back-UPS
battery. Unplug devices one at a time to remove
overload. If the problem is not corrected, contact
SEIT Technical Support
Constant Tone Charger Fault
- Back-UPS has an
internal problem.
The AC input is present but is no powering the load.
Contact SEIT Technical Support
Long beep every
4 seconds
Over-temperature Protected - The Back-UPS has
overheated and has shut down. Unplug connected
devices one at a time or wait a few hours for system to
cool down.
Connect the Battery
™
3
1 Connect the battery by pulling the battery connector handle
down, and then pushing it into the unit.
2 Connect the Back-UPS BX700U- FR/GR/AZ models power
cable directly to a wall outlet. Do not use surge protectors or
extension cords.
For BX700UI and BX700U-MS, replace PC’s input cord
with the jumper cable and use PC’s input cord to connect UPS
Note:
BX700LI-MS comes with an extra powe
r cord for connection to a wall outlet.
3 Press the ON/OFF button to turn on the unit.
The green “Power On” indicator confirms that the Back-UPS is on and ready to provide
protection.
The Back-UPS should charge for at least 10 hours to ensure su
fficient runtime. The unit is being
charged whenever it is connected to AC power, whether the unit is turned ON or OFF.
Features
Operational Features
Automatic Voltage Regulation
Automatic Voltage Regulation boosts/trims the AC voltage when it drops/exceeds safe levels. This allows the
equipment plugged into the unit to operate during low/high voltage conditions, conserving the battery power in
the event of a power cut.
The Back-UPS will switch to battery power if the input voltage level becomes too low/high for the Automatic
Voltage Regulation to compensate, or if the AC power
is distorted.
If the Back-UPS switches to battery power too frequently or too infrequently, adjust the transfer voltage and
sensitivity settings:
1 . Ensure the Back-UPS is off. Plug it into AC power.
2 . Press and hold the ON/OFF button until the LED repeatedly flashes. The unit is now in Program Mode.
3 . Release the button. The LED will indicate the current setting by flashing once, twice, or three times per
second, and emitting audible beeps.
4 . If the button is not pressed within five seconds, the Back-UPS will exit the Program Mode.
No-load Shutdown
If the UPS is operating on battery power and detects that the connected equipment is using less than 15 W of
energy for more than 15 minutes, it will shut down to conserve energy.
When the UPS is reconnected to AC power, the UPS will automatically switch on.
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure is to replace the
original unit with a factory reconditioned unit. Customers who must have the original unit back due to the
assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT
Technical Support representative. SEIT will ship the replacement unit once
the defective unit has been received
by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for
shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the
customer.
LED
Flashing
Audible
Indicator
Voltage
Sensitvity
Setting
Input
Voltage
Range
No-load
Shutdown Description
Once per
second
None Low 140-300 Disabled The Back-UPS will switch to battery
power less often.
Once per
second
4 beeps per
second
Low 140-300 Enabled The Back-UPS will switch to battery
power less often.
Twice per
second
None Medium 140-300 Disabled Use when the input AC power is normal,
without any fluctuation in voltage levels.
Twice per
second
4 beeps per
second
Medium
(factory
default)
140-300 Enabled Use when the input AC power is normal,
without any fluctuation in voltage levels.
Three times
per second
None High 150-290 Disabled The Back-UPS will switch to battery
power during any small fluctuation in
voltage.
Three times
per second
4 beeps per
second
High 150-290 Enabled The Back-UPS will switch to battery
power during any small fluctuation in
voltage.
6
Troubleshooting and Service
1 . If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the Schneider
Electric web site, www.apc.com.
a. Note the model number and serial number and the date of purchase
. The model and serial numbers are
located on the rear panel of the unit and are available through the LCD display on select models.
b. Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If this is
not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the Schneider Electric web site for
country specific instructions.
2 . Prepare to troubleshoot the problem over the phone. If this is not successful, and the unit is still under
warranty, the Technical Support Representative will provide all necessary informatio
n to return the unit for
replacement
APC by Schneider Electric IT Customer
Support Worldwide
For country specific customer support, go to the APC by Schneider Electric web site, www.apc.com.
Input Voltage 220 - 240 VAC
Frequency 50/60 Hz ± 3 Hz (Auto-sensing)
Brownout Transfer / Over-voltage Transfer 140 VAC, typical / 300 VAC, typical
Output UPS Capacity (total) 700 VA / 390 W
Voltage On Battery 230 Vac rms
Frequency - On Battery 50/60 Hz ± 1 Hz
Transfer Time 4ms typical
Protection AC Input Resettable circuit breaker
Battery Type (maintenance-free, lead acid) 12V, 7.2 AH
Average Life The battery typically lasts for three to
five years. Environmental factors impact
battery life. Elevated temperatures, high
humidity, poor quality mains power, and
frequent, short duration discharges will
shorten battery life.
The battery in the Back-UPS BX700U
Series is not user-replaceable. Contact
SEIT Technical Support for a list of
authorized service centers near you.
Typical Recharge Time 6 hours
Physical Net Weight 6.0 kg
Dimensions (H x W x D) 19.9 cm x 11.5 cm x 25.6 cm
e
Power button Telephone/Network port (BX700UI/BX700U-AZ/BX700U-MS only)
Battery connector AC Power Inlet
Circuit breaker Battery Backup + Surge Protection outlets
See outlet type and quantity breakdown for each model on the
graphic below.
USB port
Specifications
EN 990-5398A-002 12/2016
© 2016 APC by Schneider Electric. APC, the APC logo, Ba ned by Schneider Electric ck-UPS, and PowerChute are ow
Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.
bu391b
Model Outlet Type and
Quantity
BX700U-AZ x 3
BX700U-FR x 3
BX700U-GR x 4
BX700U-MS
x 2
x 1
BX700UI x 4
For BX700UI and BX700U-MS only:
IEC jumper cable for PC connection
Install PowerChute™ Software
To install PowerChute Personal Edition (PCPE) software, connect a USB cable to the data port on the UPS and
the other end to a computer with access to the web.
On the computer, go to www.apc.com/tools/download. Select “Software Upgrades - PowerChute Personal
Edition” in the “Filter by Software/Firmware” drop down menu. Select the appropriate operating system.
Follow directions to download the software.
bu382b
Produkt Specifikationer
Mærke: | APC |
Kategori: | Server |
Model: | APBX700UI |
Har du brug for hjælp?
Hvis du har brug for hjælp til APC APBX700UI stil et spørgsmål nedenfor, og andre brugere vil svare dig
Server APC Manualer
26 September 2024
18 September 2024
11 August 2024
11 August 2024
7 August 2024
31 Juli 2024
30 Juli 2024
28 Juli 2024
28 Juli 2024
27 Juli 2024
Server Manualer
- Server QNAP
- Server Bosch
- Server Acer
- Server Sony
- Server HP
- Server D-Link
- Server Asus
- Server Gigabyte
- Server Toshiba
- Server Lenovo
- Server Abus
- Server Planet
- Server Black Box
- Server TRENDnet
- Server Buffalo
- Server Medion
- Server Linksys
- Server Megasat
- Server Cisco
- Server Seagate
- Server Netgear
- Server Tripp Lite
- Server Western Digital
- Server Technics
- Server Digitus
- Server Dell
- Server Fujitsu
- Server NEC
- Server LevelOne
- Server FLIR
- Server ZyXEL
- Server Eaton
- Server ELAC
- Server Synology
- Server Hikvision
- Server Monacor
- Server AVerMedia
- Server Asustor
- Server Kramer
- Server Hanwha
- Server LaCie
- Server Naim
- Server Fantec
- Server Provision-ISR
- Server Quantum
- Server Axis
- Server ACTi
- Server Digi
- Server ATen
- Server Teo
- Server Vimar
- Server Smart-AVI
- Server Intel
- Server Supermicro
- Server StarTech.com
- Server Conceptronic
- Server Rocstor
- Server IStarUSA
- Server Blackmagic Design
- Server Lindy
- Server Veritas
- Server Promise Technology
- Server Sitecom
- Server HGST
- Server AMX
- Server Intellinet
- Server Iomega
- Server Silverstone
- Server Geovision
- Server Ernitec
- Server KanexPro
- Server Gefen
- Server Moxa
- Server C2G
- Server Allnet
- Server Maxdata
- Server Matrox
- Server Valcom
- Server Freecom
- Server Revox
- Server G-Technology
- Server Areca
- Server SEH
- Server Ibm
- Server Sonnet
- Server TAIDEN
- Server SIIG
- Server Advantech
- Server Mobotix
- Server Extron
- Server Avocent
- Server Silex
- Server In Win
- Server Sun
- Server Atlona
- Server MvixUSA
- Server Dual Bay
- Server Raidsonic
- Server EMC
- Server Infortrend
- Server Opengear
- Server EXSYS
- Server Raritan
- Server Chenbro Micom
- Server Mr. Signal
- Server Atlantis Land
- Server Lantronix
- Server NETSCOUT
- Server Origin Storage
- Server IMC Networks
Nyeste Server Manualer
19 November 2024
19 November 2024
14 November 2024
13 Oktober 2024
12 Oktober 2024
12 Oktober 2024
11 Oktober 2024
11 Oktober 2024
11 Oktober 2024
10 Oktober 2024