APC E3SOPT010 Manual

APC UPS E3SOPT010

Læs nedenfor 📖 manual på dansk for APC E3SOPT010 (4 sider) i kategorien UPS. Denne guide var nyttig for 3 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/4
Installation 990-6486-001 3/2021
Easy UPS 3S Dry Contact I/O SmartSlot Card
(E3SOPT010)
NOTE: Only one dry contact I/O SmartSlot card can be installed in the UPS.
Characteristics of output contacts (pin 3, 5 – 9):
Permissible voltage: 24 V
Permissible current: 1 A
Definitions of Output Contacts (Pin 3, 5 – 9)
Pin Pin name Description
3 Utility/mains
unavailable
Utility/mains is unavailable.
Active: low
5 UPS on UPS is in normal mode.
Active: low
6 Battery low Battery voltage reaches EOD.
Active: low
7 General alarm UPS gives off general alarm such as input out of
tolerance, battery low, manual bypass, or output
overload.
Active: low
8 Bypass active or No
output
UPS is in bypass mode, or there is no output power to
load.
Active: low
9 UPS inoperable UPS is inoperable in cases of REC inoperable, INV
inoperable or Bypass inoperable.
Active: low
Characteristics of input contact (pin 4):
NOTE: Do not duplicate the settings of the internal configurable dry contactor
(standard in the UPS) on pin 4 to shut down the UPS.
Permissible voltage: 24 V
Permissible current: 80 mA
Reverse max voltage: 6 V
Definitions of Input Contact (Pin 4)
Pin Pin name Description
4 Shut down UPS UPS can be shut down by energizing this pin with
external power supply for at least two seconds.
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com
As standards, specifications, and design
change from time to time, please ask for
confirmation of the information given in this
publication.
© 2021 – 2021 . All rightsSchneider Electric
reserved.