APC Symmetra LX 16kVA N+1 Manual

APC UPS Symmetra LX 16kVA N+1

Læs nedenfor 📖 manual på dansk for APC Symmetra LX 16kVA N+1 (2 sider) i kategorien UPS. Denne guide var nyttig for 11 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
Remove screws and slide out the hardwire assembly .
Attach an input conduit and if required, an output conduit .
Larger holes can be punched if necessary.
Detach the strain relief panel using nuts for easier access.
q
q
Symmetra LX
Rack-mount UPS
Symmetra LX
Tower UPS
Complete Pre-installation Checklist
Check that the circuit breaker to be used to power the UPS is in the
OFF position.
Check that the input circuit breaker on the UPS is in the OFF
position.
Before beginning the electrical installation, perform the following procedures.
1
Read, understand and follow ALL safety instructions contained in
the
Failure to follow safety instructions and warnings could
result in equipment damage, serious injury, or death.
Symmetra LX Safety Instructions and General Information
Guide.
Electrical
Hazard Maximum
Load
Maximum
Load
8 kVA
Circuit
Breaker
Rating*
Circuit
Breaker
Rating*
50 A
Connection
Connection
§
§
§
§
§
40 in-lb
4.5 -m)
1-phase: 3-Wire
-Wire (
External circuit breaker
#3 AWG (25 mm )
Torque to
( N
(L1-N-G)
3-phase: 5 L1-L2-
L3-N-G)
2
§
§
§
§
§
40 in-lb
4.5 -m)
1-phase: 3-Wire
-Wire (
External circuit breaker
#6 AWG (16 mm )
Torque to
( N
(L1-N-G)
3-phase: 5 L1-L2-
L3-N-G)
2
Voltage
(Vac)
Voltage
(Vac)
16 kVA 100 A
1-phase:
220 or 230
or 240
3-phase:
380 or 400
or 415
1-phase:
220 or 230
or 240
3-phase:
380 or 400
or 415
8 kVA 50 A §
§
§
§
40 in-lb
4.5 -m)
1-phase: 3-Wire
External circuit breaker
#6 AWG (16 mm )
Torque to
( N
(L1-N-G)
2
§
§
6 (IEC 320 C19) sockets
with 6 (15A, 250V) circuit
breakers
8 (IEC 320 C13) sockets
with 2 (10A 250V) circuit
breakers
16 kVA 100 A
220 or
230 or
240
220 or
230 or
240
§
§
§
§
40 in-lb
4.5 -m)
1-phase: 3-Wire L1 G
External circuit breaker
#3 AWG (25 mm )
Torque to
( N
( -N- )
2
§
§
10 (IEC 320 C19) sockets
with 10 (15A, 250V) circuit
breakers)
8 (IEC 320 C13) sockets
with 2 (10A 250V) circuit
breakers
Input Connections: Tower and Rack-mount UPS
Method
Method
Hardwired
(Standard on
tower and
rack-mount)
Hardwired
(Standard on
tower and
rack-mount)
Hardwired
(Standard on
tower and
rack-mount)
Hardwired
(Standard on
tower and
rack-mount)
Output
sockets
(Standard on
rack-mount)
Output
sockets
(Standard on
rack-mount)
220 or
230 or
240
220 or
230 or
240
§
§
§
Refer to local and national codes. Many locations require hardwiring
by a licensed electrician.
Strain relief is required for all hardwiring.
All openings in the hardwire assembly must be covered. Failure to
do so may result in personal injury or equipment damage.
Hardwire the UPS
2
1.1
1.2
Caution
®
®
All UPS configurations can be wired 3-phase in / 1-phase out, or
1-phase in / 1-phase out.
Note
!
!
!
!!
Output Connections: Tower and Rack-mount UPS
2.1
2.2
990-1540B-001, 04/2006
Important Safety and Installation Instructions
This manual provides instructions on the wiring and connections for the
Symmetra LX tower and rack-mount UPS.
All electrical power and power control wiring must be installed by a qualified
electrician and comply with local and national regulations.
See and retain the product documentation shipped with your system for
other important installation, operation, and maintenance instructions.
Illustrations are representative. Your Symmetra LX configuration, including
components and optional APC equipment, may be different from the models
shown in this guide.
Entire contents copyright 2006 by American Power Conversion Corporation.
All rights reserved. Reproduction in whole or in part without permission is
prohibited.
Symmetra LX
Electrical Installation Guide
Tower and Rack-mount UPS
®
For use with Symmetra LX UPS Models:
APC, the APC logo, PowerChute, InfraStruXure, Smart-UPS and Symmetra
are registered trademarks of American Power Conversion Corporation. All
other trademarks are the property of their respective owners.
Electrical Installation
* Recommended
** Note: Wire connection “G” represents protective earth ground .
220/230/240 V, 4 8 kV A
220/230/240 V, 4 16 kV A


Produkt Specifikationer

Mærke: APC
Kategori: UPS