Fantini Cosmi L04BM2A Manual


Læs nedenfor 📖 manual på dansk for Fantini Cosmi L04BM2A (2 sider) i kategorien Thermostaat. Denne guide var nyttig for 13 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
reference instrument.
Exit from calibration by pressing button .
To get access to the parameter configuration menu, press button + for 5 seconds.
With button or select the parameter to be modified.
Press button to display the value.
By keeping button pressed, use button or to set the desired value.
When button is released, the newl programmed value is stored and the following parameter is displayed.y
To exit from the setup, press button or wait for 30 seconds.
PAR RANGE DESCRIPTION
SCL 1°C;
2°C;
°F
Readout scale (see table of input specifications)
Caution: upon changing the SCL value, it is then absolutely necessary to the param-reconfigure
eters relevant to the absolute and relative temperatures (SPL, SPH, 1SP, 1HY etc..)
SPL -50°...SPH Minimum limit for 1SP setting
SPH SPL...150° Maximum limit for 1SP setting.
1SP SPL... SPH Setpoint (value to be maintained in the room).
1CM HY; PID Control mode.
With 1CM=H you select control with hysteresis: parameters 1HY Y, 1T0 and 1T1 are used.
With 1CM=PID you select a Proportional-Integral-Derivative control mode: parameters 1PB, 1IT,
1DT, 1AR, 1C will be used.T
1CH REF; HEA Refrigerating (REF) or Heating (HEA) control mode.
1CM=HY
1HY 0...19.9° With 1HY=0 the output is always oOFF/ON thermostat differential. ff.
1T0 0...30min Minimum off time.
After f, 1T0 output 1 has been turned of it remains inactive for minutes regardless of the
temperature value measured.
1T1 0...30min ).Minimum on time. (the following parameter will be 1PF
After output 1 has been turned it remains active for 1T1 minutes regardless of the temperature on,
value measured.
1CM=PID
1PB 0...19.9° Proportional bandwidth.
Temperature control takes place by changing the
ON time of the the closer the temperature output:
to the the less time of activation. small setpoint, A
proportional band increases the promptness of
response of the system to temperature variations,
but tends to make it less stable. A purely
proportional control stabilises the temperature
within the proportional band but does not cancel
the deviation from setpoint.
With 1PB=0 the output is always off.
1IT 0...999s Integral action time.
The steady-state error is cancelled by inserting an
integral action. The integral action determines time,
the speed the steady-state temperature with which
is but a high speed (1IT may be the achieved, low)
cause of overshoot and instability in the response.
With 1IT=0 the integral control is disabled.
1DT 0...999s Derivative action time.
Response overshoot may be reduced by inserting
a derivative Action. A high derivative action (1DT
high) makes the system very sensitive to small
temperature variations and causes instability. With
1DT=0 the derivative control is disabled.
1AR 0...100% Reset of integral action time referred to 1PB
Decreasing the parameter reduces the integral control action and consequently the 1AR zone,
overshoot (see figure on paragraph 1IT).
1CT 1...255s Cycle time.
It’s the period in the output ON time changes. The quicker the system to be controlled which
reacts to temperature the smaller the cycle time must in order to obtain higher variations, be,
temperature stability and less sensitivity to load variations.
1PF ON/OFF Output state in case of probe failure.
OAU NON;
THR;
AL0;
AL1
AUX output operation.
NON : output disabled (always o f). (fthe next parameter will be ATM)
THR : output programmed for second thermostat control ( ).the next parameter will be 2SM
AL0 : contacts open when an alarm condition occurs (the next parameter will be ATM).
AL1 : contacts make when an alarm condition occurs (the next parameter will be ATM).
OAU=THR
2SM ABS;
REL
Setpoint 2 mode.
Channel 2 setpoint may be absolute (2SM=ABS), or a differential relative to setpoint 1 (2SM=REL)
2SM=ABS
2SP SPL...SPH Auxiliary output switchover temperature ( )the next parameter will be 2CH
2SM=REL
2DF -19.9...19.9° Temperature dif P. ferential relative to 1S The auxiliary output setpoint is equal to 1SP+2DF
ON/OFF refrigerating control
( Y1CM=H , =REF)1CH
ON/OFF heating control
( Y1CM=H , =HEA)1CH
1SP 1SP+1HY T[°]
ON
OFF
1SP1SP-1HY T[°]
ON
OFF
Time
Temperature
Process
temperature
Overshoot Steady-st ate error
1PB
1SP
Time
Temperature
Process
temperature
Overshoot
1PB1PBx1AR%
integral control
action area
1SP
Time
Temperature
Process
temperature
Overshoot
1PB
1SP
2SP 2SP+2HY T[°]
ON
OFF
2SP2SP-2HY T[°]
ON
OFF
ON/OFF control in refrigeration
(2SM=ABS, 2CH=REF)
ON/OFF control in heating
(2SM=ABS, 2CH=HEA)
1SP+2DF
1SP
2DF>0 1SP+2DF+2HY T[°]
ON
OFF
1SP
1SP+2DF
2DF<0
1SP+2DF-2HY T[°]
ON
OFF
ON/OFF control in refrigeration. Setpoint 2
relative to setpoint 1 (OAU=THR, 2CH=REF)
ON/OFF control in heating. Setpoint 2
relative to setpoint 1 (OAU=THR, 2CH=HEA)
Power supply
L04B--/L24E-- V230 ac±10%, 50/60Hz, 2W
Relay outputs
OUT1 8(3)A 240V~
OUT2 8(3)A 240V~
Inputs
see table of input specifications
Measurement range
see table of input specifications
Measurement accuracy
see table of input specifications
Operating conditions
-10 … +50°C; 15%...80% r.H.
CE (Reference Norms)
EN60730-1; EN60730-2-9;
EN55022 (Class B); EN50082-1
Front protection
IP55
Via Dell’Osio 6
20090 Caleppio di Settala MI
TEL. +39 - 02956821
FAX +39 - 0295307006
e-mail: info@fantinicosmi.it
http://www.fantinicosmi.it
OAU=THR
2CH REF; HEA Refrigerating control (REF) or heating control mode (HEA) for the auxiliary output.
2HY 0...19.9° ferential of thermostat 2. With 2HY=0 the auxiliary output always remains oDif ff.
2T0 0...30min Minimum off time.
After output 2 has been turned of it remains inactive for f, 2T0 minutes regardless of the temperature
value measured.
2T1 0...30min Minimum on time.
After output 2 has been turned it remains active for 2T1 minutes regardless of the temperature on,
value measured.
2PF ON/OFF Auxiliary output state in case of probe failure.
ATM NON;
ABS;
REL
Alarm threshold management.
NON : all temperature alarms are inhibited (the following parameter will be SB).
ABS : the values programmed in ALA and AHA represent the real alarm thresholds.
REL : t
he values programmed in ALR and AHR are alarm differentials referred to 1 P and 1S SP+1HY.
ATM=ABS
ALA -50°...AHA Low temperature alarm threshold.
AHA ALA...15 High temperature alarm threshold.
ATM=REL
ALR -12.0...0° Low temperature alarm differential.
With ALR=0 the low temperature alarm is excluded.
AHR 0...12.0° High temperature alarm differential.
With AHR=0 the high temperature alarm is excluded.
ATD 0...120min Delay before alarm temperature warning.
SB NO/YES Stand-by button enabling.
INP ST1/SN4
(LS120/LS130)
Sensor input selection (see table of input specifications).
In the models L04BM2A... only.
RLO -19.9...RHI Minimum range value
RLO takes the minimum value measured by the transmitter (i.e. the value matching 0V).
RHI RLO...99.9 Maximum range value
RHI takes the maximum value measured by the transmitter (i.e. the value matching 1V)
OS1 -12.5...12. Probe T1 offset.
TLD 1...30min Delay for minimum temperature (TLO) and maximum temperature (THI) logging.
SIM 0...100 Display slowdown
ADR 1...255 L04-- address for PC communication
MODEL INPUT
RANGE [MEASUREMENT ACCURACY]
SCL=1°C SCL=2°C SCL=°F
L24EM2 0÷1V (LS160A) RLO÷RHI [< 3mV]± ---
L04BM2A
INP=ST1 PTC 1000 Ω
(LS120)
-50/-19.9 ÷ 99.9/150°C
[0.3°C(-30÷130°),±1°C]
-50 ÷ 150°C
[<±0.3°C(-30÷130°), ±1°C]
-60 ÷ 300°F
[< ±0.6°F(-20÷260°),±2°F]
INP=SN4 NTC 10K Ω
(LS130)
-40/-19.9 ÷ 99.9/125°C
[0.3°C(-40÷100°),±1°C]
-40 ÷ 125°C
[<±0.3°C(-40÷100°),±1°C]
-40 ÷ 260°F
[<±0.6°F(-40÷210°), ±2°F]
1SP
1SP-ALR
T[°]
ON
OFF
1SP+1HY+AHR 1SP1SP-1HY -ALR 1SP+AHR
T[°]
ON
OFF
Temperature alarm with relative thresholds,
refrigerating control (ATM=REL, 1CH=REF)
Temperature alarm with relative thresholds,
heating control (ATM=REL, 1CH=HEA).
L04BM2A
data I/O
230V ~
OUT 2
8(3)A
OUT 1
8(3)A
3 4
8 9 10 6 7
RS485
L24EM2
data I/O
230V ~
OUT 2
8(3)A
OUT 1
8(3)A
3 54
8 9 10 6 7
TTL
rH
V
V V+V-IN
DISPLAY
During normal operation, the display shows either the temperature measured or one of the following indications:
Controller in stand-by Controller in autotuning
Probe T1 overrange or failure In tuning: timeout1 error
Room high temperature alarm In tuning: timeout2 error
Room low temperature alarm In tuning: overrange error
MENU INFO
The information available in this menu is:
Maximum temperature recorded Keypad state lock
Minimum temperature recorded
Access to menu and information displayed.
Press and immediately release button .
With button or select the data to be displayed.
Press button to display value.
To exit from the menu, press button or wait for 10 seconds.
Reset of THI, TLO recordings
With button or select the data to be reset.
Display the value with button .
While keeping button pressed, use button .
CHANNEL 1 SETPOINT (display and modification of desired temperature value)
Press and release button : the ED blinL L1 ks, the display shows 1 P for 1 second and then the setpoint associated value.S
Press buttons or to set the desired value (adjustment is within the minimum SPL and maximum SPH limit).
To store the new value press button , or wait for 10 seconds.
To go back to normal mode without saving the new value, press .
CHANNEL 2 SETPOINT
With the auxiliary output set as thermostat control ( ■ =THR),OAU it’s possible to modify setpoint 2 during the normal operation
of the controller.
Press and release button : LED L2 blinks, shows 2S the the display P for 1 second if setpoint 2 is an absolute threshold
( alternatively the display 2DF2SM=ABS), shows , =REL), if setpoint 2 is a threshold relative to setpoint 1 (2SM then the value
associated to the parameter appears.
Press buttons or to set the desired value.
To store the new value press button or wait for 10 seconds.
To go back to normal mode without saving the new value, press .
STAND-BY
Button , when pressed for 3 seconds, allows the controller to be put on a standby or output control to be resumed (with SB=YES only).
KEYPAD LOCK
The keypad lock avoids potentially dangerous might be attempted the controllers is operating undesired, operations, which when
in a public place. In the INFO set parameter to inhibit all functions of the buttons. To resume normal operation menu, LOC=YES
of keypad, adjust setting so that LOC=NO.
CONTROLLER AUTOTUNING IN PID MODE
Before starting
In the setup mode (see set =PID; make sure that matches the desired operation mode configuration parameters): 1CM 1CH
(1CH 1CH=REF for refrigerating control, =HEA for heating control); then adjust setpoint 1SP at the desired value.
Start autotuning
During normal keep buttons operation, + pressed for seconds. 1CT blinks on the display. With + or set the cycle 3
time in order to the dynamic of the process to be controlled. To abort the autotuning press define function, ; to start autotuning
press + or wait for 30 seconds.
During autotuning
During the entire autotuning the display alternates the actual temperature measured. In case of phase, TUN with power failure,
when power resumed, phase, is after the initial autotest the controller resumes the autotuning function. To abort the autotuning,
without parameters, modifying the previous control keep button pressed for seconds. the autotuning has taken place 3 After
successfully, the controller updates the control parameters and start to control.
Errors
If the autotuning function failed, the display shows an error code:
E1 timeout1 the controller could not bring the temperature the proportional band. Increase error: within 1SP in case of heating
control, vice versa, decrease 1SP in case of refrigerating control and re-start the process.
E2 timeout2 the autotuning has not ended the maximum time cycle Re-start the autotuning error: within allowed (1000 times).
process and set a longer cycle time .1CT
E3 overrange: was malfunction, temperature check that the error not caused by a probe then decrease 1SP in case of heating
control, vice versa increase 1SP in case of refrigerating control and then re-start the process.
To eliminate the error indication and return to the normal mode, press button .
Control improvement
To reduce overshoot, reduce the integral action reset 1AR
To increase the response speed of the system
,
reduce the proportional band
1PB. Caution: doing this makes the system less stable.
To reduce in steady-state swings
temperature,
increase the integral action time m stability is thus although increased,
its response speed is decreased.
To increase the speed of response to the variations in increase the derivative action time temperature,■ Caution:1DT. a high
value makes the system sensitive to small variations and it may be a source of instability.
RECALIBRATION
Have a precision reference thermometer or a calibrator to hand. Ensure that =0 and =0.OS1 SIM
Switch the controller off then on again.
During the auto-test phase, press buttons 0AD+ and keep them pressed till the controller shows .
With buttons and select or a calibration of inserting a constant correction over the scale 0AD SAD 0AD: allows 0, whole
of measurement. a calibration of the top part of the measurement scale a proportional correction the SAD allows with between
calibration point and 0.
Press to display the value and then use + or to make the read value coincide the value measured by the with
The L04-- sizes
110x75x55 (WxHxD). mm Fix the plate to the panel using 2 cheese-headed screws with 4 or 5 mm diameter
and then apply the instrument casing to the plate. This should be done for vertical panels and for correct positioning of the
instrument with the outlets at the bottom.
Make sure that electrical connections comply the paragraph diagrams”. To reduce the effects of electromagnetic with “wiring
disturbance, keep the sensor and signal cables well separate from the power wires.
Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.
OUT1
OUT2
L1
L2
Channel 1 output
Channel 2 output
Alarm
Channel 1 setpoint modification
Channel 2 setpoint modification
Fig.1 - Front panel
Thank you for having chosen a Fantini Cosmi product. Before installing the instrument, please read these instructions carefully
to ensure maximum performance and safety.
L04-- INSTRUCTION FOR USE
Info / Enter button Modify Setpoint 1 / Decrease button
Increase / Modify Setpoint 2 button Exit / Stand-by button
5679450


Produkt Specifikationer

Mærke: Fantini Cosmi
Kategori: Thermostaat
Model: L04BM2A

Har du brug for hjælp?

Hvis du har brug for hjælp til Fantini Cosmi L04BM2A stil et spørgsmål nedenfor, og andre brugere vil svare dig




Thermostaat Fantini Cosmi Manualer

Thermostaat Manualer

Nyeste Thermostaat Manualer