Brief description
Translation of the original instructions
8101652
2018-11a
[8101654]
Bus node CPX-FB39 English. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
For all available product documentation è www.festo.com/pk
1 Intended use
The module described in this document is intended for use as a participant in a
Sercos-III network in an industrial environment. Outside of industrial environ
ments, e.g. in commercial and mixed-residential areas, actions to suppress inter
ference may have to be taken.
The module is intended exclusively for use in CPX terminals from Festo for
installation in machines or automated systems and may be used only in the
following ways:
in an excellent technical status
in original status without unauthorised modifications, except for the adapta
tions described in this documentation
within the limits of the product defined through the technical data.
You can find detailed information in the module description
(è P.BE-CPX-FB39-...) and in the CPX system description
(è P.BE-CPX-SYS-...).
2 Safety
This documentation is directed exclusively at technicians trained in control and
automation technology.
Warning
Electrical voltage
Injury caused by electric shock, damage to machine and to system
For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1 (Protective Extra-Low Voltage, PELV).
Observe the general requirements of IEC 60204-1 for PELV circuits.
Use only voltage sources which guarantee reliable electrical isolation of the
operating and load voltage in accordance with IEC 60204-1.
Always connect all circuits for operating and load voltage supplies U
EL/SEN,
UVAL and UOUT
.
Note
Electrostatically sensitive devices
Do not touch any components.
Observe the handling specifications for electrostatically sensitive
devices.
Note
Take into consideration the specifications and notes in the module description
and the assembly instructions for the components.
Commission the module only if fully mounted and wired.
SERCOS® is a registered trademark of its respective trademark holder in
certain countries.
3 Connection and display components
1
2
3
4
5
1Rating plate
2Network/CPX-specific LEDs
3Network connections X1 and X21)
4Cover for DIL switches
5Service interface CPX-MMI or
CPX-FMT2)
1) Connection socket: M12, D-coded, 4-pin 2) Connection socket: M12, A-coded, 5-pin
Fig. 1
3.1 Network connections
Socket Connection [X1] Connection [X2]
Pin Signal/explanation Pin Signal/explanation
M12, 4-pin
1
2
3
4
Housing
TX+
RX+
TX–
RX–
FE
Transmitted data +
Received data +
Transmitted data
Received data
Screening/FE1)
1
2
3
4
Housing
RX+
TX+
RX–
TX–
FE
Received data +
Transmitted data +
Received data
Transmitted data
Screening/FE1)
1) The screened connection is connected to the earth potential of the CPX terminal through an RC element.
Fig. 2
3.2 LED indicators - normal operating status
Behaviour of the LED indicators in normal operating status:
The LEDs S, SD, PS and PL illuminate green.
The LEDs TP1 and TP2 illuminate or flash green.
The yellow LED (M) illuminates, flashes or is dark.
The red LED (SF) is dark.
Network-specific LED indicators CPX-specific LED indicators2)
S (green, orange, red) Sercos III1) PS (green) Power System
SD (green, orange, red) Sub Device1) PL (green) Power Load
TP1 (green) Traffic Port 1 SF (red) System Failure
3)
TP2 (green) Traffic Port 2 M (yellow) Modify4)
1) Detailed information (è Description for the module P.BE-CPX-FB39-…)
2) Detailed information (è CPX system description P.BE-CPX-SYS-…)
3) Flashes in case of error, error diagnostics (è CPX system description P.BE-CPX-SYS-…)
4) Parameterisation revised or “Forceactive.
Fig. 3
4 Mounting and dismantling
Warning
Electrical voltage
Injury caused by electric shock, damage to machine and to system
Switch supply power off before assembly work.
2
3
1
1Screws
2Module
3Interlinking block
Fig. 4


Produkt Specifikationer

Mærke: Festo
Kategori: Ikke kategoriseret
Model: CPX-FB39

Har du brug for hjælp?

Hvis du har brug for hjælp til Festo CPX-FB39 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Festo Manualer

Festo

Festo HMIA-E07 Manual

13 Oktober 2024
Festo

Festo DASI-B10-25-S8 Manual

13 Oktober 2024
Festo

Festo SASC-P4-A-M8-A Manual

13 Oktober 2024
Festo

Festo HMIZF-E03-DA18 Manual

13 Oktober 2024
Festo

Festo EAPM-L4-SLS Manual

13 Oktober 2024
Festo

Festo MH1 Manual

13 Oktober 2024
Festo

Festo CTEU-CC Manual

13 Oktober 2024
Festo

Festo CPX-FB36 Manual

13 Oktober 2024
Festo

Festo CPX-FB37 Manual

13 Oktober 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer