Finder 80.91 Manual


Læs nedenfor 📖 manual på dansk for Finder 80.91 (1 sider) i kategorien Ikke kategoriseret. Denne guide var nyttig for 38 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/1
Open Type Device
Pollution degree 2 Installation Environment
Maximum Surrounding Air Temperature 40°C
Use 60/75°C copper (Cu) conductor only and
wire ranges No. 14–18 AWG, stranded or solid
Terminal tightening torque of 7.1 Ib.in. (0.8 Nm)
80.91.0.240.0000
UN (12...240) V AC (50/60 Hz) / DC
U 10.8 V A DCmin C/
Umax 265 V A DCC/
P <1.8 VA (50 Hz) / <1 W
1 CO (SPDT)
16 A 250 V AC
AC1 4000 VA
AC15 (230 V AC) 750 VA
(230 V AC) 0.55 kW
DC1 (30/110/220) V (16/0.3/0.12) A
(–10...+50)°C
IP20
M
LED UN
15 - 18 15 - 16
15 - 18 15 - 16
15 - 16
15 - 16 15 - 18
3
3a
3b
3c 3d 3e
A
B
C
D
E88.8 mm
60.8 mm
17.5 mm
A
B
12
Utility Model - IB8091001 - 10/21 - Finder S.p.A. con unico socio - 10040 ALMESE (TO) - ITALY
80.91
80.91
MODULAR TIMER ASYMMETRICAL RECYCLING
FRONT VIEW
A Time scales rotary selector (T1)
B Time setting (T1)
C LED
D Functions rotary selector (T2)
E Time scales rotary selector (T2)
TIME SCALES
(Eg. T=20 min: set =20 m and =T max)A B
WIRING DIAGRAM AND FUNCTIONS
( : the functions must be set before energising the timer)WARNING
3a Without signal START function
Start via contact in supply line (A1)
LI = Asymmetrical asher (starting pulse on)
3b With signal START function
Start via contact into control terminal (B1)
LE = Asymmetrical asher (starting pulse on) with control signal
3c Possible to control an external load, such as another relay coil or
timer, connected to the signal start terminal B1
3d With DC supply, positive polarity has to be connected to B1 terminal
(according to EN 60204-1)
3e A voltage other than the supply voltage can be applied to the
command Start (B1), example:
A1-A2 = 230 V AC
B1-A2 = 12 V DC
OTHER DATA
Minimum control impulse: 50 ms
Recovery time: 100 ms
35 mm rail mount (EN 60715)
WORKING CONDITIONS
In conformity with the European Directive on EMC 2014/30/EU,
the timer relay has a level of immunity, against radiated and conducted
disturbances, considerably higher than requirements of EN 61812-1
standard. However, devices like transformers, motors, contactors,
switches and power cables may cause disturbances and even damage
the timer electronic circuit. For that reason, the wiring cables must be
as short as possible, and, when necessary, the timer shall be protected
by the relevant RC network, varistor or surge voltage protector.
1
2
3
ENGLISH