Fujitsu AUYF12LAL Manual
Læs nedenfor 📖 manual på dansk for Fujitsu AUYF12LAL (3 sider) i kategorien Splitter. Denne guide var nyttig for 19 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere
Side 1/3
INDOOR UNIT (Compact cassette type)
INSTALLATION INSTRUCTION SHEET
(PART No. 9374318261-04)
For authorized service personnel only.
AIR CONDITIONER
1INSTALLATION THE UNIT
PIPE INSTALLATION
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the fl are nut (always use the fl are nut attached to the indoor
and outdoor units respectively) onto the pipe and perform the fl are
processing with a fl are tool.
Use the special R410A fl are tool, or the conventional fl are tool.
Check if [L] is fl ared uniformly and
is not cracked or scratched. B
Die
A
Pipe
Width across
fl ats
When using conventional fl are tools to fl are R410A pipes, the dimension
A should be approximately 0.5 mm more than indicated in the table (for
fl aring with R410A fl are tools) to achieve the specifi ed fl aring. Use a
thickness gauge to measure the dimension A.
The pipes are shaped by your hands. Be careful not to collapse them.
Do not bend the pipes in an angle more than 90 °.
When pipes are repeatedly bend or stretched, the material will harden,
making it diffi cult to bend or stretch them any more. Do not bend or
stretch the pipes more than three times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or over.
If the pipe is bent repeatedly at the same place, it will break.
2. BENDING PIPES
(3) When the fl are nut is tightened properly by your hand, use a torque
wrench to fi nally tighten it.
Torque wrench
Holding spanner
Body side
(2) Centering the pipe against port on the indoor unit, turn the fl are nut
with your hand.
3. PIPE CONNECTION
Indoor unit
(1) Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on the indoor unit
correctly. If the centering is improper, the fl are nut cannot
be tightened smoothly. If the fl are nut is forced to turn, the
threads will be damaged.
Do not remove the fl are nut from the indoor unit pipe until
immediately before connecting the connection pipe.
3
STANDARD PARTS
The following installation parts are furnished.
Use them as required.
INDOOR UNIT ACCESSORIES
Discharge Direction Setting
• The discharge direction can be selected as shown below. 45
INSTALLING HEAT INSULATION
CAUTION
After checking for gas leaks (refer to the Installation Manual of the
outdoor unit), perform this section.
Install heat insulation around both the large (gas) and small (liquid)
pipes. Failure to do so may cause water leaks.
Must fi t tightly against body without any gap.
After checking for gas leaks, insulate by wrapping insulation around the
2 parts (gas and liquid) of the indoor unit coupling, using the Coupler
Heat Insulation.
After installing the Coupler Heat Insulation, wrap both ends with vinyl tape
so that there is no gap.
Coupler heat insulation
Coupler heat
insulation
Be sure to overlap
the insulation
No gap
No gap
Body
ELECTRICAL WIRING (2) After wiring is complete, secure the remote controller cable, connection
cable, and power cable with the wire clamps.
(3) Install control box cover.
2. BODY INSTALLATION
(1) Install special nut A, then special nut B onto the hanging bolt.
(2)
Raise the body and mount its hooks onto the hanging bolt between the special nuts.
(3) Turn special nut B to adjust the height of the body.
Special nut A
Special nut B
Hook
Hanging bolt
30 mm
or more
After installing the
body, tighten the nuts.
19 mm Ceiling
3. LEVELING
Using a level, or vinyl hose fi lled with water, fi ne adjust so that the body is level.
Inclined installation so as the drain pipe side is higher may cause a mal-
function of the fl oat switch, and may cause water leakage.
INSTALLATION WORK
Install the air conditioner as follows:
* For a 3-way outlet, make sure to perform the Function Setting on the
remote controller. Also, make sure to use the optional shutter panel to
block the outlet.
* The ceiling height cannot be set in the 3-way outlet mode. Therefore, do
not change the setting in the “Setting the Ceiling Height” at
8
FUNC-
TION SETTING.
* When the outlet is shut, be sure to install the optional Air outlet shut-
ter plate kit.
For the details of installation, please refer to Installation Manual of kit.
(Continued to the next page)
To prevent gas leakage, coat the fl are
surface with alkylbenzene oil (HAB).
Do not use mineral oil.
Indoor unit
Connection pipe
(Liquid)
Connection pipe
(Gas)
Connection cable
(to outdoor unit)
Wired remote controller
cable (option)
G
Wire clamp Connection cable
(to outdoor unit)
Wired remote controller
cable (option)
Wire clamp
It is necessary to use seamless copper pipes and it is desirable that the
amount of residual oil is less than 40 mg/10 m. Do not use copper pipes
having a collapsed, deformed or discolored portion (especially on the interior
surface). Otherwise, the expansion valve or capillary tube may become
blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when
using conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than that in the table even when it is
available on the market.
Copper pipes
3. CONNECTION OF WIRING
(1) Remove the control box cover and install each connection wire
Screw Control box cover
Power supply cable
or connection cable
20 mm
30 mm or more
Earth (ground)
wire
• Use a 4-core wire cable.
Keep the earth (ground) wire longer than the other wires.
2. CONNECTION CABLE PREPARATION
1. CONNECTION DIAGRAMS
Connection wire (to outdoor unit)
Wired remote controller wire (option)
Power line
Control line
3
2
1
Indoor
unit side
* Ground the remote controller ip it has a ground wire
Black
White
Red
3
2
1
*
Indoor
unit side
530 mm (Hanging bolt position)
540 mm (Hanging bolt position)
570 mm (Indoor unit)
580 – 660 mm (Ceiling openings)
700 mm (Cassette grille)
135 mm 250 mm
Min.450 mm
Drain pipe (O.D. ø25.4)
40 mm 99 mm102 mm
114 mm
215 mm
30 mm
262 mm
30 mm
58 mm
123 mm
Ceiling
Control box
Liquid pipe Gas pipe
75 mm
Min.450 mm
150 mm
– 200 mm
Maintenance
space
Be sure to keep suffi cient space in the designated position for
future maintenance.
*Please ensure suffi cient
maintenance space during
installation.
(4 directions) (3 directions)
100 mm or more*
DANGER This mark indicates procedures which, if improperly performed, are most likely to result in the death of
or serious injury to the user or service personnel.
WARNING This mark indicates procedures which, if improperly performed, might lead to the death or serious injury
of the user.
CAUTION This mark indicates procedures which, if improperly performed, might possibly result in personal harm
to the user, or damage to property.
DANGER
Never touch electrical components immediately after the power supply has been turned off. Electrical shock may occur. After
turning off the power, always wait 5 minutes or more before touching electrical components.
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and installation
and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the conven-
tional piping and fl are nuts with the R410A piping and fl are nuts.
Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with con-
ventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20
threads per inch.]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when storing
the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and always
charge from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name Contents of change
Gauge manifold
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm 2) for high pressure. –0.1 to
3.8 MPa (–76 cmHg to 38 kgf/cm2) for low pressure.
Charge hose To increase pressure resistance, the hose material and base size were changed.
Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter.
Gas leakage detector Special gas leakage detector for HFC refrigerant R410A.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter Thickness
6.35 mm (1/4 in.) 0.80 mm
9.52 mm (3/8 in.) 0.80 mm
12.70 mm (1/2 in.) 0.80 mm
15.88 mm (5/8 in.) 1.00 mm
19.05 mm (3/4 in.) 1.20 mm
Name and Shape Q’ty Application
Coupler heat
insulation
2
For indoor side pipe joint
Special nut A
(large fl ange)
4
For installing indoor unit
Special nut B
(small fl ange) 4
For installing indoor unit
Template
(Carton top)
1
For ceiling openings cutting
Also used as packing
Remote
controller
1
For air conditioner operation
Battery 2
For remote controller
Remote controller holder
1
For installing the remote
controller holder installation
Tapping screw
2
For mounting the remote
controller
CASSETTE GRILLE ACCESSORIES
Name and Shape Q’ty Application
Connector cover
1
For covering connector
Screw
4
For mounting cassette
grille
Screw
1
For mounting connector
cover
For authorized service personnel only.
WARNING
For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
Connect the indoor unit and outdoor unit with the air conditioner piping and cables available from our standards parts. This
installation instruction sheet describes the correct connections using the installation set available from our standard parts.
Installation work must be performed in accordance with national wiring standards by authorized personnel only.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a fl ame, it produces a toxic gas.
Do not use an extension cable.
Do not turn on the power until all installation work is complete.
CAUTION
This installation instruction sheet describes how to install the indoor unit only.
To install the outdoor unit, refer to the installation instruction sheet included with the outdoor unit.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
CONNECTION PIPE REQUIREMENT
CAUTION
Refer to the installation instruction sheet of the outdoor unit for description of the length of connecting pipe or for difference
of its elevation.
MODEL 9,000/12,000
BTU/h model
14,000/18,000
BTU/h model
24,000
BTU/h model
Diameter Liquid 6.35 mm (1/4 in.) 6.35 mm (1/4 in.) 6.35 mm (1/4 in.)
Gas 9.52 mm (3/8 in.) 12.70 mm (1/2 in.) 15.88 mm (5/8 in.)
Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat
insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker
and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specifi ed, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
ELECTRICAL REQUIREMENT
Connection cord (mm2)
MAX. MIN.
2.5 1.5
Use conformed wire with Type 60245 IEC57.
Install all electrical works in accordance to the standard.
Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units. (Both indoor unit and outdoor unit)
SELECTING AN INSTALLA-
TION LOCATION
Decide the mounting position with the customer as follows:
WARNING
Select installation locations that can properly support the weight
of the indoor unit. Install the units securely so that they do not
topple or fall.
CAUTION
Do not install the indoor unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate
metal parts, causing the parts to fail or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed
oil or steam, such as a kitchen. It will deteriorate plastic parts, caus-
ing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment,
such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the
copper pipes and brazed joints to corrode, which can cause refriger-
ant leakage.
• Area that can cause combustible gas to leak, contains suspended
carbon fibers or flammable dust, or volatile inflammables such as
paint thinner or gasoline. If gas leaks and settles around the unit, it
can cause a fi re.
• Area where animals may urinate on the unit or ammonia may be
generated.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or fl ammable gas.
Install the indoor unit, outdoor unit, power supply cable, transmission
cable, and remote control cable at least 1 m away from a television or
radio receivers. The purpose of this is to prevent TV reception interfer-
ence or radio noise. (Even if they are installed more than 1 m apart,
you could still receive noise under some signal conditions.)
If children under 10 years old may approach the unit, take preventive
measures so that they cannot reach the unit.
Use the “Insulation kit for high humidity” (option), when the condition
under the roof is over 80% in humidity and over 30°C in temperature.
Otherwise, there is a risk of condensation on the ceiling.
(1) Install the indoor unit in a location having suffi cient strength to sup-
port the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be
able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(4) Locate where the air can be distributed evenly throughout the room
by the unit.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibration is not amplifi ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also
install the unit where the fi lter can be removed.
Obstruction
1,800 mm
or more
1,000 mm
or more
1,000 mm
or more
Floor
Strong and durable ceiling
262 mm
or more
This product can be installed at a height of up to 3.0 m. Perform the Function
Setting on the remote controller in accordance with the installed height.
(See 8 FUNCTION SETTING.)
WARNING
Install the air conditioner in a location which can withstand
a load of do at least fi ve times the weight of the main unit
and which will not amplify sound or vibration. If the instal-
lation location is not strong enough, the indoor unit may
fall and cause injuries.
If the job is done with the panel frame only, there is a risk
that the unit will come loose. Please take care.
1.
POSITION THE CEILING HOLE AND HANGING BOLTS
Ceiling openings and hanging bolt installation diagram
WARNING
When fastening the hangers, make the bolt positions
uniform.
WARNING
Perform fi nal tightening by tightening the double nut fi rmly.
WARNING
Electrical work must be performed in accordanc e with t his
Manual by a person certified under the national or regional
regulations. Be sure to use a dedicated circuit for the unit.
An insuffi cient power supply circuit or improperly performed electrical
work can cause serious accidents such as electric shock or fi re.
Before starting work, check that power is not being supplied to the in-
door unit and outdoor unit.
Use the included transmission cables and power cables or ones speci-
fi ed by the manufacturer. Improper connections, insuffi cient insulation,
or exceeding the allowable current can cause electric shock or fi re.
For wiring, use the prescribed type of wires, connect them securely, mak-
ing sure that there are no external forces of the wires applied to the termi-
nal connections. Improperly connected or secured wires can cause seri-
ous accidents such as overheating the terminals, electric shock, or fi re.
Do not modify the power cables, use extension cables, or use any
branches in the wiring. Improper connections, insuffi cient insulation, or
exceeding the allowable current can cause electric shock or fi re.
Match the terminal block numbers and connection cable colors with those of the out-
door unit or branch box. Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal blocks. In ad-
dition, secure the cables with wiring holders. Improper connections, ei-
ther in the wiring or at the ends of the wiring, can cause a malfunction,
electric shock, or fi re.
Always fasten the outside covering of the connection cable with the
cable clamp. (If the insulator is chafed, electric leakage may occur.)
Securely install the electrical box cover on the unit. An improperly in-
stalled electrical box cover can cause serious accidents such as elec-
tric shock or fi re through exposure to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise,
a short circuit could result.
Install a earth (ground) leakage breaker. In addition, install the earth
(ground) leakage breaker so that the entire AC main power supply is
cut off at the same time. Otherwise, electric shock or fi re could result.
Always connect the earth (ground) wire.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cable and bus wire so as not to be direct
touched with your hand.
(1) Use ring terminals with insulating sleeves as shown in the fi gure be-
low to connect to the terminal block.
(2) Securely clamp the ring terminals to the wires using an appropriate
tool so that the wires do not come loose.
(3) Use the specifi ed wires, connect them securely, and fasten them so
that there is no stress placed on the terminals.
(4)
Use an appropriate screwdriver to tighten the terminal screws. Do not
use a screwdriver that is too small, otherwise, the screw heads may
be damaged and prevent the screws from being properly tightened.
(5)
Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table 1 for the terminal screw tightening torques.
Strip 10 mm
Sleeve
Ring terminal
Screw with spe-
cial washer Screw with
special washer
Ring terminal Ring ter-
minal
Wire
Wire
Terminal block
Terminal
board
Table 1
Tightening torque
M4 screw 1.2 to 1.8 N·m (12 to 18 kgf·cm)
WARNING
Use ring terminals and tighten the terminal screws to the specifi ed
torques, otherwise, abnormal overheating may be produced and
possibly cause heavy damage inside the unit.
CAUTION
Do not use mineral oil on fl ared part. Prevent mineral oil
from getting into the system as this would reduce the
lifetime of the units.
While welding the pipes, be sure to blow dry nitrogen gas
through them.
Pipe outside diameter Dimension A (mm)
Flare tool for R410A, clutch type
6.35 mm (1/4 in.)
0 to 0.5
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Pipe outside diameter Dimension B 0
-0.4 (mm)
6.35 mm (1/4 in.) 9.1
9.52 mm (3/8 in.) 13.2
12.70 mm (1/2 in.) 16.6
15.88 mm (5/8 in.) 19.7
19.05 mm (3/4 in.) 24.0
Pipe outside diameter Width across fl ats of
Flare nut
6.35 mm (1/4 in.) 17 mm
9.52 mm (3/8 in.) 22 mm
12.70 mm (1/2 in.) 26 mm
15.88 mm (5/8 in.) 29 mm
19.05 mm (3/4 in.) 36 mm CAUTION
Hold the torque wrench at its grip, keeping it in the
right angle with the pipe, in order to tighten the fl are nut
correctly.
Flare nut Tightening torque
6.35 mm (1/4 in.) dia. 16 to 18 N·m (160 to 180 kgf·cm)
9.52 mm (3/8 in.) dia. 30 to 42 N·m (300 to 420 kgf·cm)
12.70 mm (1/2 in.) dia. 49 to 61 N·m (490 to 610 kgf·cm)
15.88 mm (5/8 in.) dia. 63 to 75 N·m (630 to 750 kgf·cm)
19.05 mm (3/4 in.) dia. 90 to 110 N·m (900 to 1100 kgf·cm)
CAUTION
Do not bundle the remote controller wire, or wire the remote
controller cord in parallel, with the indoor unit connection
wire (to the outdoor unit) and the power supply cord. It may
cause erroneous operation.
Vinyl hose
OPTIONAL PARTS
Exterior Parts name Model No. Summary
Wired remote
controller
UTB
-
UD
Unit control is
performed by
wired remote
controller
Air outlet
shutter plate UTR
-
YDZB
Install the plate at
outlet when car-
rying out 3-way
direction opera-
tion.
Cassette
grille UTG-UF*B-F
Ceiling dirt by dis-
charged wind was
made diffi cult to
cling by reviewing
the shape of the
LOUVER.
Fresh air
intake kit UTZ-VXAA
It can be taken
in fresh air of up
to 10% of “high”
air volume of the
indoor unit by
attaching Fresh
air intake kit to
cassette type
indoor unit.
External con-
nect kit UTY-XWZX
Use to connect
with various pe-
ripheral devices
and air condition-
er PC board.
Insulation
kit for high
humidity
UTZ-KXGC
Install when the
under roof condi-
tion is expected
to be the humidity
of over 80 % and
the temperature
of over 30 °C.
2INSTALLING DRAIN PIPE
Note: Install the drain pipe.
Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm (1-1/4”)]
and connect it with adhesive (polyvinyl chloride) so that there is no leakage.
When the pipe is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain pipe.
When desiring a high drain pipe height, raise it up to 700 mm or less from the ceiling within
a range of 150 mm from the body. A rise dimension over this range will cause leakage.
Max. 700 mm
Rise
Trap
Supporter
1.5 to 2.0 m
Air bleeding 150 mm or less
NG
NG
NG
NOTES:
Check for drainage
Pour about 1 liter of water from the position shown in the diagram or from the airfl ow outlet to the dew
tray. Check for any abnormalities such as strange noises and whether the drain pump functions normally
The drain pump operates when operating in the cooling mode.
Drain pipe Wire cover Screw
Watering pot
Produkt Specifikationer
Mærke: | Fujitsu |
Kategori: | Splitter |
Model: | AUYF12LAL |
Har du brug for hjælp?
Hvis du har brug for hjælp til Fujitsu AUYF12LAL stil et spørgsmål nedenfor, og andre brugere vil svare dig
Splitter Fujitsu Manualer
3 Oktober 2024
30 September 2024
29 September 2024
19 September 2024
17 September 2024
14 September 2024
10 September 2024
9 September 2024
6 September 2024
6 September 2024
Splitter Manualer
- Splitter Scheppach
- Splitter Samsung
- Splitter IFM
- Splitter Audio-Technica
- Splitter Behringer
- Splitter Zipper
- Splitter D-Link
- Splitter InFocus
- Splitter Nedis
- Splitter Abus
- Splitter Hyundai
- Splitter Black Box
- Splitter König
- Splitter Texas
- Splitter Gembird
- Splitter NewStar
- Splitter Tripp Lite
- Splitter Mercury
- Splitter Digitus
- Splitter Marmitek
- Splitter APC
- Splitter LevelOne
- Splitter Monacor
- Splitter Sun Joe
- Splitter Radial Engineering
- Splitter Furuno
- Splitter Manhattan
- Splitter Kramer
- Splitter Ideal
- Splitter Audiovox
- Splitter MuxLab
- Splitter Akasa
- Splitter Xantech
- Splitter ATen
- Splitter Shure
- Splitter Aluratek
- Splitter Smart-AVI
- Splitter StarTech.com
- Splitter Crestron
- Splitter Lindy
- Splitter Rolls
- Splitter AMX
- Splitter Comprehensive
- Splitter Key Digital
- Splitter KanexPro
- Splitter Gefen
- Splitter C2G
- Splitter WyreStorm
- Splitter Icy Box
- Splitter ACG
- Splitter SIIG
- Splitter Televés
- Splitter Botex
- Splitter Palmer
- Splitter Rose Electronics
- Splitter SmartAVI
- Splitter Rane
- Splitter Klover
- Splitter Atlona
- Splitter Omnitron Systems
- Splitter Club 3D
- Splitter CLUB3D
Nyeste Splitter Manualer
21 December 2024
21 December 2024
19 December 2024
19 December 2024
13 December 2024
9 December 2024
9 December 2024
9 December 2024
6 December 2024
6 December 2024