Hager JK201SPD Manual


Læs nedenfor 📖 manual på dansk for Hager JK201SPD (1 sider) i kategorien Ikke kategoriseret. Denne guide var nyttig for 5 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/1
Hager Ltd. Hortonwood 50, Hortonwood, Telford, TF1 7FT / 01952 675 675 1
Commercial Distribution
Surge Protection Kits
JK20 SPD1 & JKD201SPD
Surge Protection Kit
Type Surge Protection Kit for Hager 1 + 2
25 A TP&N Distribution Boards to aid 0
compliance with 18th Edition 67 . BS 7 1
-Plug-in lightning and surge arrester combination, in accordance with
Type 1+2/Class 1+ , for 3-phase power supply networks, with separate2
N and PE (L 1, L2, L3, PE, N).
Green = Healthy, Red = Replace
-Directly coordinated combination of type 1 spark gap without line follow
current and type 2 varistor arrester
-Particularly suitable for maximum protection of sensitive devices in harsh
environments
-High continuous voltage of 350 V AC for 230/400 V AC networks with high
voltage fluctuations
-Pluggable
-Low voltage protection level of 1.5 kV
-Optical, mechanical status indicator
-Floating remote indication contact
Product escription D
A Surge protection device (SPD) kit specifically developed
for Hager standard TPN (Type B) Distribution boards. 250A
Developed to ensure optimal performance of SPD
technology ithin ager istribution oards. PD s T2 w H d b S i C
type to ensure compatibility with all common UK Earthing
arrangements e.g. TN-C-S (PME), TN-S and TT earthing
arrangements. This is an IEC Type SPD for 3 – phase 1+ 2
power supply networks. A type SPD is generally used in 1
the primary distribution board.
This SPD kit fits within the standard distribution board. Line,
Neutral and Earth connections are via copper links,
mi S c lnimising PD onductor osses, maximising the effective
performance of the SPD (Up effective).
Key Specifications
- Power Supply System -TN / TT
- Requirement class -SPD class II acc. to IEC 61643-11
2011; SPD Type acc. to EN 61643-11 1 2012
- Max. continuous operating voltage Uc -L-N: 275 V a.c. /
N-PE: 260 V a.c.
- Nominal voltage Un -2 0/4 V AC 50/60 Hz4 15
-Impulse discharge current (10/350) µs (L-N/ -PE), peakL
current value Ilmp 25 kA
-Impulse discharge current (10/350) µs (N-PE), peak current
value Ilmp 100 kA
- Nominal discharge current In (8/20) microseconds 20 kA
- Max. discharge current I max (8/20) microseconds 40 kA
SPD Protection level Up -L-N: < 1.35 kV/ N-PE: <1.5 kV
Solution Protection level Up (measured at the main effective
busbars on the TPN board) -L-N: <1.5kV/ N-PE: < 1.5kV
Short-circuit current rating lSCCR -25kA
Degree of protection - IP20
Tightening torque - see installation instructions.
Dimensional Drawing
Circuit Diagram


Produkt Specifikationer

Mærke: Hager
Kategori: Ikke kategoriseret
Model: JK201SPD

Har du brug for hjælp?

Hvis du har brug for hjælp til Hager JK201SPD stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Hager Manualer

Hager

Hager FN247E Manual

9 December 2024
Hager

Hager FN217E Manual

9 December 2024
Hager

Hager FN092E Manual

9 December 2024
Hager

Hager FN093E Manual

9 December 2024
Hager

Hager FZ760E Manual

9 December 2024
Hager

Hager FN266E Manual

9 December 2024
Hager

Hager FN216E Manual

9 December 2024
Hager

Hager FN101E Manual

9 December 2024
Hager

Hager FN277E Manual

9 December 2024
Hager

Hager FN356E Manual

9 December 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer