Operating instructions
IO-Link master with PROFINET interface
DataLine
4 ports
IP 65 / IP 66 / IP 67 / IP 69K
AL1301
Firmware: 3.1.x
English
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
2
Contents
1 Preliminary note 5
1.1 Legal and copyright information ........................................................................................... 5
1.2 Purpose of the document ..................................................................................................... 5
1.3 Explanation of Symbols ....................................................................................................... 5
1.4 Change history ..................................................................................................................... 6
2 Safety instructions 7
2.1 General ................................................................................................................................ 7
2.2 Required background knowledge ........................................................................................ 7
2.3 Safety symbols on the device .............................................................................................. 7
2.4 IT security ............................................................................................................................. 8
3 Functions and features 9
4 Function 10
4.1 Communication, parameter setting, evaluation ................................................................. 11
4.1.1 - IO Link........................................................................................................................................ 11
4.1.2 PROFINET ................................................................................................................................. 11
4.1.3 Internet of Things (IoT) ............................................................................................................... 11
4.1.4 Security mode ............................................................................................................................ 11
4.1.5 Parameter setting ....................................................................................................................... 11
4.1.6 Visual indication .........................................................................................................................12
4.2 Digital inputs ....................................................................................................................... 12
4.3 -Link supply IO .................................................................................................................... 12
5 Mounting 13
5.1 Mount the device ................................................................................................................ 13
6 Electrical connection 14
6.1 Notes .................................................................................................................................. 14
6.2 Connecting the PROFINET ports .......................................................................................15
6.3 Connecting the IoT port ..................................................................................................... 15
6.4 -Link ports IO ....................................................................................................................... 16
6.4.1 Connecting IO-Link devices for Class A operation ..................................................................... 16
6.5 Connecting the device ....................................................................................................... 17
7 Operating and display elements 18
7.1 Overview ............................................................................................................................ 18
7.2 LED indicators .................................................................................................................... 19
7.2.1 Status LEDs ............................................................................................................................... 19
7.2.2 Ethernet ports ............................................................................................................................. 19
7.2.3 IoT port ....................................................................................................................................... 20
7.2.4 Voltage supply ............................................................................................................................ 20
7.2.5 -Link Ports (Class A) IO ............................................................................................................... 20
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
3
8 Set- up 21
9 Configuration 22
9.1 LR DEVICE ........................................................................................................................ 23
9.1.1 Remarks ..................................................................................................................................... 24
9.1.2 IoT: Congure IP settings ........................................................................................................... 24
9.1.3 IoT: Congure security mode ..................................................................................................... 25
9.1.4 IoT: Conguring access rights .................................................................................................... 26
9.1.5 IoT: Congure the interface to LR AGENT or LR SMARTOBSERVER ...................................... 27
9.1.6 Fieldbus: Congure IP settings ................................................................................................... 27
9.1.7 -Link ports: Activate data transfer to LR AGENT or LR SMARTOBSERVER IO ......................... 28
9.1.8 -Link ports: Congure operating mode IO ....................................................................................29
9.1.9 - nk ports: Set the device validation and data storage IO Li .......................................................... 30
9.1.10 Info: Show device information .................................................................................................... 31
9.1.11 Firmware: Reset device to factory settings ................................................................................. 31
9.1.12 Firmware: Reboot the device ...................................................................................................... 31
9.1.13 Congure IO-Link devices .......................................................................................................... 32
9.2 ifm IoT Core ....................................................................................................................... 33
9.2.1 Programmers' notes ................................................................................................................... 34
9.2.2 First steps ................................................................................................................................... 38
9.2.3 General functions ....................................................................................................................... 38
9.2.4 IoT: Conguring access rights .................................................................................................... 42
9.2.5 IoT: Conguring IP settings ........................................................................................................ 42
9.2.6 IoT: Conguring the LR AGENT or LR SMARTOBSERVER interface ....................................... 43
9.2.7 IoT: Conguring security mode ................................................................................................... 43
9.2.8 Fieldbus: Conguring IP settings ................................................................................................ 46
9.2.9 -Link ports: Setting the operating mode of pin 4 (US) IO ............................................................. 46
9.2.10 -Link ports: Conguring device validation and data storage IO ................................................... 47
9.2.11 -Link ports: Conguring data transfer to LR AGENT or LR SMARTOBSERVER IO .................... 48
9.2.12 -Link ports: Reading / writing process data IO ............................................................................. 49
9.2.13 -Link ports: Indicating port events IO ........................................................................................... 52
9.2.14 -Link devices: Accessing parameters IO ..................................................................................... 52
9.2.15 -Link devices: Reading an writing device information IO ............................................................. 54
9.2.16 -Link devices: Indicating IO-Link events IO ................................................................................. 54
9.2.17 Gateway: Resetting, rebooting and localising the device ........................................................... 54
9.2.18 Gateway: Reading device information ........................................................................................ 55
9.2.19 Gateway: Reading status and diagnostic information ................................................................. 55
9.2.20 Gateway: Updating the rmware ................................................................................................ 56
9.2.21 Gateway: Setting the application tag .......................................................................................... 57
9.2.22 Subscribing to notications ......................................................................................................... 58
9.2.23 Using Web Socket ...................................................................................................................... 62
9.2.24 MQTT support ............................................................................................................................ 64
9.2.25 Using the IoT-Core Visualizer ..................................................................................................... 68
9.3 PROFINET ......................................................................................................................... 75
9.3.1 Install GSD Files ......................................................................................................................... 76
9.3.2 Integrate the IO-Link master in the project ................................................................................. 76
9.3.3 Congure the IO-Link master ..................................................................................................... 77
9.3.4 Congure IO- nk ports Li .............................................................................................................. 78
9.3.5 Congure IO-Link devices .......................................................................................................... 79
9.3.6 Read and write cyclic process data ............................................................................................ 79
9.3.7 Read I&M datasets ..................................................................................................................... 80
9.3.8 Detect diagnostics and alarms ................................................................................................... 80
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
4
10 81 Operation
10.1 Using web-based management ......................................................................................... 81
11 82 Maintenance, repair and disposal
11.1 Cleaning process ............................................................................................................... 82
11.2 Updating the rmware ........................................................................................................ 82
11.3 Replacing IO-Link device ................................................................................................... 82
12 83 Factory settings
13 84 Accessories
14 85 Appendix
14.1 Technical data .................................................................................................................... 86
14.1.1 Application .................................................................................................................................. 86
14.1.2 Electrical data ............................................................................................................................. 86
14.1.3 Inputs / outputs ........................................................................................................................... 86
14.1.4 Inputs .........................................................................................................................................87
14.1.5 Outputs ....................................................................................................................................... 87
14.1.6 Interfaces .................................................................................................................................... 87
14.1.7 Operating conditions ..................................................................................................................88
14.1.8 Approvals / tests ......................................................................................................................... 88
14.1.9 Mechanical data ......................................................................................................................... 88
14.1.10 Electrical connection ..................................................................................................................89
14.2 PROFINET ......................................................................................................................... 90
14.2.1 Parameter data ........................................................................................................................... 90
14.2.2 Cyclic data .................................................................................................................................. 93
14.2.3 Acyclic data ................................................................................................................................ 95
14.3 ifm IoT Core ....................................................................................................................... 97
14.3.1 Overview: IoT prole ..................................................................................................................98
14.3.2 Overview: IoT types .................................................................................................................. 105
14.3.3 Overview: IoT services ............................................................................................................. 106
15 120 Index
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
5
1 Preliminary note
Content
Legal and copyright information ............................................................................................................... 5
Purpose of the document ......................................................................................................................... 5
Explanation of Symbols ............................................................................................................................ 5
Change history ........................................................................................................................................ 6
33203
>
1.1 Legal and copyright information
33117
© All rights reserved by ifm electronic gmbh. No part of this manual may be reproduced and used
without the consent of ifm electronic gmbh.
All product names, pictures, companies or other brands used on our pages are the property of the
respective rights owners:
-i is the property of the AS-International Association, ( AS www.as-interface.net)
CAN is the property of the CiA (CAN in Automation e.V.), Germany ( ) www.can-cia.org
CODESYS™ is the property of the CODESYS GmbH, Germany (→ ) www.codesys.com
DeviceNet™ is the property of the ODVA™ (Open DeviceNet Vendor Association), USA
( ) www.odva.org
EtherNet/IP® is the property of the → ODVA™
EtherCAT® is a registered trade mark and patented technology, licensed by Beckho Automation
GmbH, Germany
-LinkIO ® is the property of the PROFIBUS Nutzerorganisation e.V., Germany
( ) www.io-link.com
ISOBUS is the property of the AEF Agricultural Industry Electronics Foundation e.V.,
Deutschland ( www.aef-online.org)
Microsoft® is the property of the Microsoft Corporation, USA ( ) www.microsoft.com
Modbus® is the property of the Schneider Electric SE, France ( ) www.schneider-electric.com
PROFIBUS®
is the property of the PROFIBUS Nutzerorganisation e.V., Germany
( ) www.probus.com
PROFINET® is the property of the PROFIBUS Nutzerorganisation e.V., Germany
Windows® is the property of the Microsoft Corporation, USA
>
1.2 Purpose of the document
34227
This document is only for device types "IO-Link master - PROFINET gateway (DataLine) 4 port IP 65 /
IP 66 / IP 67 / IP 69K" (art. no.: AL1301).
It is part of the device and contains information about the correct handling of the product.
Read this document before using the device.
Keep this document during the service e of the device. lif
>
1.3 Explanation of Symbols
34171
WARNING
Warning of serious personal injury.
Death or serious irreversible injuries may result.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
6
CAUTION
Warning of personaly injury.
Slight reversible injuries may result.
NOTICE
Warning of damage to property
Important note
Non-compliance can result in malfunction or interference
Information
Supplementary note
...
Request for action
> ...
Reaction, result
...
"see"
abc
Cross-reference
123
0x123
0b010
Decimal number
Hexadecimal number
Binary number
[...]
Designation of pushbuttons, buttons or indications
>
1.4 Change history
42782
Version
Topic
Date
00
New creation of the document
04 / 2019
01
Corrected: Technical data - current rating per output
09 / 2019
02
Added: New IoT core functions
Added: IoT Core Visualizer
Correction: Description SENS PWR and AUX PWR
Correction: Description of the IoT Core Service getsubscriptioninfo
10 / 2020
03
Deleted: ifm IoT Core D support NS
10 / 2021
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
7
2 Safety instructions
Content
General ..................................................................................................................................................... 7
Required background knowledge ............................................................................................................. 7
Safety symbols on the device ................................................................................................................... 7
IT security ................................................................................................................................................. 8
28333
>
2.1 General
58525
The device described is a subcomponent for integration into a system. The manufacturer is
responsible for the safety of the system. The system manufacturer undertakes to perform a risk
assessment and to create documentation in accordance with legal and normative requirements to
be provided to the operator and user of the system. This documentation must contain all
necessary information and safety instructions for the operator, the user and, if applicable, for any
service personnel authorised by the manufacturer of the system.
Read this document before setting up the product and keep it during the entire service life.
The product must be suitable for the corresponding applications and environmental conditions
without any restrictions.
Only use the product for its intended purpose ( Functions and features ( p. 9)).
If the operating instructions or the technical data are not adhered to, personal injury and/or
damage to property may occur.
The manufacturer assumes no liability or warranty for any consequences caused by tampering
with the product or incorrect use by the operator.
Installation, electrical connection, set-up, programming, conguration, operation and maintenance
of the product must be carried out by personnel qualied and authorised for the respective activity.
Protect units and cables against damage.
>
2.2 Required background knowledge
34185
This document is intended for specialists. Specialists are people who, based on their relevant training
and experience, are capable of identifying risks and avoiding potential hazards that may be caused
during operation or maintenance of the product.
The document contains information about the correct handling of the product.
>
2.3 Safety symbols on the device
34199
General warning
Observe instructions in chapter "Electrical connection" ( ( Electrical connection p. 14))!
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
8
2.4 security IT
54678
NOTICE!
If the device is operated in an unprotected network environment.
> Unauthorised read or write access to data is possible.
> Unauthorised manipulation of the device function is possible.
Check and restrict access options to the device:
Restrict access to authorised persons.
Do not connect the device to open networks or the internet.
If access from the internet is inevitable:
choose a safe method to connect with the device (e. g. VPN).
Use encrypted data transmission (e. g. https / TLS).
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
9
3 Functions and features
58284
The device may only be used for the following purposes:
as IO-Link master for conguration, management and operation of IO-Link devices
as gateway between IO-Link devices and AS- network i
The device is designed for use without a control cabinet in the food industry.
Only use the device within the limits of the technical data ( Technical data ( p. 86)).
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
10
4 Function
Content
Communication, parameter setting, evaluation ...................................................................................... 11
Digital inputs ........................................................................................................................................... 12
IO-Link supply ......................................................................................................................................... 12
33836
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
11
4.1 Communication, parameter setting, evaluation
Content
IO-Link .................................................................................................................................................... 11
PROFINET .............................................................................................................................................11
Internet of Things (IoT) ........................................................................................................................... 11
Security mode ......................................................................................................................................... 11
Parameter setting ................................................................................................................................... 11
Visual indication ...................................................................................................................................... 12
33860
>
4.1.1 -Link IO
34084
The device oers the following IO-Link functions:
-Link master (IO-Link revision 1.0 and 1.1) IO
4 IO-Link ports for connection of IO-Link devices
Provision of process data of the connected IO-Link devices for LR SMARTOBSERVER monitoring
software ( ) www.ifm.com
>
4.1.2 PROFINET
52555
The device oers the following PROFINET functions:
Pronet RT Device (Class B)
2 port switch for access to the PROFINET interface; integrated switch is RT and IRT conform
according to PROFINET V2.3
Gateway for transmission of the process and parameter data between the connected IO-Link
devices and the higher-level PROFINET controller
Supported protocols: SNMP, LLDP, MRP, DCP, RTA, RTC Class 1 (not synchronized)
PROFINET fea res: FSU, I&M0 - 4 read/write tu
Device description: GSDML file
>
4.1.3 Internet of Things (IoT)
54679
The device oers the following IoT functions:
Gateway for the transmission of process, parameter and monitoring data between IO-L kmaster / in
IO-Link devices and the IT network level
REST-API to access process and parameter data
Supported protocols: TCP/IP JSON, MQTT
>
4.1.4 Security mode
54697
The IoT interface oers the following optional sercurity functions:
Secure d a transfer via encrypted connection (Secure Layer Transport - TLS) at
Access protection via authentication
>
4.1.5 Parameter setting
34210
The device provides the following conguration options:
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
12
Parameter setting of the IO-Link master of the AL1301 with LR DEVICE parameter setting
software, PROFINET projection software or ifm IoT-Core services.
Parameter setting of the connected IO-Link devices (sensors, actuators) with LR DEVICE
parameter setting software, PROFINET projection software or ifm IoT-Core services
Storage of parameter sets of the connected IO-Link devices for automatic recovery (data storage)
>
4.1.6 Visual indication
34192
The device has the following visual indicators:
Status and error indication of the gateway, of the PROFINET connection and of the system
Status display of the voltage supply
Status and activity display of the Ethernet connection
Status, error and short circuit/overload indication of the IO-Link ports
>
4.2 Digital inputs
33817
The device has 4 additional digital inputs (type 2 according to EN 61131-2).
The digital inputs are on pin 2 of the ports X01...X04.
All inputs refer to the potential of the device supply (pin 3).
>
4.3 -Link supply IO
34077
The device has 4 supplies for IO-Link devices.
The IO-Link ports X01...X04 are ports class A.
Every supply provides short circuit monitoring.
The device ensures re protection for the connected IO-Link devices by providing a power-restricted
circuit at the IO-Link ports (according to IEC61010-1 and Class 2 according to UL1310).
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
13
5 Mounting
Content
Mount the device .................................................................................................................................... 13
34058
>
5.1 Mount the device
34059
Disconnect the system from power before installation.
For installation choose a at mounting surface.
Please observe the maximum tightening torque.
Fix the unit to the mounting surface using 2 M5 mounting screws and washers.
Tightening torque: 1.8 Nm
Ground the unit via the two mounting screws of the upper mounting lugs.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
14
6 Electrical connection
Content
Notes ...................................................................................................................................................... 14
Connecting the PROFINET ports ........................................................................................................... 15
Connecting the IoT port .......................................................................................................................... 15
IO-Link ports ........................................................................................................................................... 16
Connecting the device ............................................................................................................................ 17
33805
>
6.1 Notes
51957
A qualied electrician must connect the unit.
The national and international for regulations setting up electrical equipment must be
complied with.
The unit is only suitable for operation using SELV/PELV voltages.
Please note the information concerning IO-Link wiring!
This unit contains components that may be damaged or destroyed by electrostatic discharge
(ESD).
Please observe the required precautions against electrostatic discharge!
The M12 connection parts in the device comply with the ingress resistance requirements of
the standard EN 61076-2-101. To adhere to the protection rating, only cables certified to this
standard must be used. The system creators undertake to ensure ingress resistance for
cables which they cut to length themselves.
Carry out the tting according to the indications of the cable manufacturer. A maximum of
0.8 Nm is permitted.
During installation, place the M12 connector vertically so that the coupling nut will not
damage the thread.
Depending on the mounting conditions, cables must be provided with a strain relief to
avoid unacceptable loads on the mounting points and M12 connections.
Make sure that the M12 connection parts are correctly seated and mounted correctly. The
specied protection rating can not be guaranteed if this is not observed.
For UL applications:
To connect the IO-Link master and the IO-Link devices, only use UL-certied cables of the
CYJV or PVVA category with a minimum temperature of 80 °C (75 °C in case of maximum
ambient temperature of 40 °C).
Wiring: ( Technical data p. ) 86
By means of basic insulation according to EN61010-1, the circuits are separated from each other and
from device surfaces that could be touched (secondary circuit with 28 V DC maximum, supplied from
mains circuit up to 300 V overvoltage category II).
By means of basic insulation according to EN61010-1, the communication interfaces are separated
from each other and from device surfaces that could be touched (secondary circuit with 28 V DC
maximum, supplied from mains circuit up to 300 V overvoltage category II). They are designed for
network environment 0 according to IEC TR62102.
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
15
6.2 Connecting the PROFINET ports
33671
Connect the device via the M12 socket X21 and/or X22 to the
PROFINET network
(e.g. PROFINET PLC, additional PROFINET device)
To connect the devices, use M12 connectors with protection rating
IP 65 / IP 66 / IP 67 / IP 69K or higher ( ( Accessories p. 84)).
Cover the unused sockets with M12 protective caps (art no.
E12542).
>
6.3 Connecting the IoT port
34044
Connect the device via the M12 socket X23 to the IT network (e.g.
laptop/PC with LR DEVICE parameter setting software, laptop/PC
with LR SMARTOBSERVER monitoring software, laptop/PC with
software capable of processing http requests).
To connect the devices, use M12 connectors with protection rating
IP 65 / IP 66 / IP 67 / IP 69K or higher ( ( Accessories p. 84)).
Cover the unused sockets with M12 protective caps (art no.
E12542)
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
16
6.4 -Link ports IO
51958
The IO-Link ports of the AL1301 meet the requirements of the IO-Link specications 1.0 to 1.1.2.
Please note the information concerning IO-Link wiring!
Cover unused sockets with M12 protective caps (art. no.: E12542).
>
6.4.1 Connecting IO-Link devices for Class A operation
51959
Wiring informati on:
The connected IO-Link devices must be supplied exclusively via the IO-Link master.
The additional digital inputs IO-Link ports X01...X04 (pin 2) have a type 2 behaviour according to
the standard EN61131-2. The connected electronics must be electrically suited for this.
Connect the connectors of the IO-Link devices with the M12
sockets of the IO-Link ports X01...X04.
Maximum cable length per IO-Link port: 20 m
To connect the devices, use M12 connectors with protection
rating IP 65 / IP 66 / IP 67 / IP 69K or higher ( Accessories
( )). p. 84
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
17
>
6.5 Connecting the device
33882
Disconnect power.
Connect the IO-Link Master via M12 socket X31 to 24 V DC
(20...28 V SELV/PELV; according to EN61010-1, secondary circuit
with maximum 30 V DC supplied by mains circuit up to 300 V of
overvoltage category II).
Maximum cable length: 25 m
To connect the device, use M12 connectors with protection rating IP
65 / IP 66 / IP 67 / IP 69K or higher ( ( Accessories p. 84)).
When using cable length greater than 25 m keep in mind the voltage drop as well as the
required minimum voltage supply of 20 V!
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
18
7 Operating and display elements
Content
Overview ................................................................................................................................................. 18
LED indicators ........................................................................................................................................ 19
34063
>
7.1 Overview
34356
1
RDY, BF and SF status LEDs
→ → (Status LEDs ) p. 19
2
LNK and ACT status LEDs of the PROFINET
interfaces 1 (X21) and 2 (X22)
→ → (Ethernet ports ) p. 19
3
LNK, ACT status-LEDs and IoT LED of the IoT
interface (X23)
→ → (IoT port ) p. 20
4
IOL and DI status-LEDs of the IO-Link port (X01...X04)
→ → (IO-Link Ports (Class A) p. 20)
5
PWR status LED of the voltage supply (X31)
→ → (Voltage supply p. 20)
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
19
>
7.2 LED indicators
34047
The device only has the following LED indicators:
>
7.2.1 Status LEDs
34549
The RDY LED shows the status of the gateway.
The BF LED (Bus Failure) shows the status of the PROFINET connection.
The SF LED (System Failure) shows the status of the system.
Status LED
Description
RDY
green
on
Status: OK
ashes 5 Hz
Status: Error
ashes (200 ms on,
800 ms o)
Status: Firmware update is running
off
Status: Gateway not running or gateway booting
BF
red
on
Bus error
ashes 1 Hz
No connection to the PROFINET controller
off
error-free
SF
red
on
Error in gateway
At least 1 IO-Link device sends warning / alarm (temperature,
over/under current, over/under voltage, shortcut)
off
error-free
>
7.2.2 Ethernet ports
34348
Each Ethernet port has 2 LEDs (LNK and ACT). The LEDs indicate the status of the Ethernet
connection.
Status LED
Description
LNK
green
on
Ethernet connection established
off
No Ethernet connection
ACT
yellow
ashes
Data is transmitted via the Ethernet interface.
off
No data transmission
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
20
>
7.2.3 IoT port
34043
The IoT port has the 3 LNK, ACT and IoT LEDs. The LEDs indicate the status of the Ethernet
connection and the device identication.
Status LED
Description
LNK
green
on
Ethernet connection established
off
No Ethernet connection
ACT
yellow
ashes
Data is transmitted via the Ethernet interface.
off
No data transmission
IoT
green
ashes
Device identication active
>
7.2.4 Voltage supply
34191
The interface for voltage supply (X31) has the LED that is marked as US. The LED indicates the status
of the voltage supply.
Status LED
Description
US
green
on
The supply voltage Us is applied.
off
No supply voltage is applied or the applied supply voltage is too low.
>
7.2.5 -Link Ports (Class A) IO
34074
Each IO-Link Port Class A has 2 LEDs labelled IOL and DI. The LEDs indicate the status of the
IO-Link port.
Status LED
Description
IOL
yellow
O
Port congured as DI/DO: pin 4 (C/Q) = OFF
on
Port congured as DI/DO: pin 4 (C/Q) =ON
green
ashing 1 Hz
Port congured asIO-Link: no IO-Link device found
Flashing with 2 Hz
Port congured asIO-Link: Status PREOPERATE
on
Port congured asIO-Link: Status OPERATE
red
Flashing with 2 Hz
Port conguration error or short circuit / overload on US
on
Transmission Error
DI
yellow
O
Digital input: pin 2 = OFF
on
Digital input: pin 2 = ON
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
21
8 Set- up
52357
When the supply voltage is switched on, the AL1301 starts with the factory settings. The display
elements signal the current operating mode ( Operating and display elements ( )). p. 18
To enable parameter setting of the AL1301, the IoT interface and / or the eldbus interface must be
congured according to the network environment.
Congure IoT interface (LR DEVICE: IoT: Congure IP settings IoT: ( ) or p. 24
Conguring IP settings ( p. 42)).
Congure eldbus interface (LR DEVICE: Fieldbus: Congure IP settings ( p. ) or IoT: 27
Feldbus-Schnittstelle kongurieren).
> IoT / eldbus interface has valid IP settings.
> User can set the parameters of the AL1301.
Further steps:
Optional: Update rmware of AL1301 ( Updating the rmware ( )). p. 82
Set the parameters of the AL1301 ( ( )). Conguration p. 22
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
22
9 Configuration
Content
LR DEVICE ............................................................................................................................................. 23
ifm IoT Core ............................................................................................................................................ 33
PROFINET .............................................................................................................................................75
33858
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
23
9.1 LR DEVICE
Content
Remarks ................................................................................................................................................. 24
IoT: Configure IP settings ....................................................................................................................... 24
IoT: Configure security mode ................................................................................................................. 25
IoT: Configuring access rights ................................................................................................................ 26
IoT: Configure the interface to LR AGENT or LR SMARTOBSERVER ................................................. 27
Fieldbus: Configure IP settings .............................................................................................................. 27
IO-Link ports: Activate data transfer to LR AGENT or LR SMARTOBSERVER .................................. 28
IO-Link ports: Configure operating mode ............................................................................................... 29
IO-Link ports: Set the device validation and data storage ...................................................................... 30
Info: Show device information ................................................................................................................ 31
Firmware: Reset device to factory settings ............................................................................................ 31
Firmware: Reboot the device.................................................................................................................. 31
Configure IO-Link devices ...................................................................................................................... 32
33692
On delivery, the AL1301 is configured with the factory settings ( ( Factory settings → p. 83)).
Required software: LR DEVICE (1.5.0.x or higher) (art.-no.: QA0011/QA0012)
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
24
9.1.1 Remarks
Content
Offline parameter setting ........................................................................................................................ 24
VPN connection ...................................................................................................................................... 24
34180
>
Offline parameter setting
34060
The AL1301 supports the offline parameter setting. In this context, the user creates and stores a
configuration for the IO-Link master and the connected IO-Link devices without being connected to the
AL1301 (OFFLINE mode). The configuration created in this way can be stored as a file (*.lrp) and
loaded to the AL1301 and activated at a later date.
Further information about offline parameter setting: Operating instructions LR DEVICE
>
VPN connection
34382
An active VPN connection blocks the access of the parameter setting software LR DEVICE to
the PROFINET interface of the AL1301.
Deactivate the VPN connection in order to be able to access the AL1301 with the LR
DEVICE.
>
9.1.2 IoT: Configure IP settings
34049
For access to the IO-Link master via the IT infrastructure the user has to set the IP settings of the IoT
port.
To configure the IP settings with DHCP, a DHCP server has to be active in the IT network. If
no DHCP server can be reached in the IT network, an IP address is automatically assigned to
the IoT port with the Zeroconfig protocol (address range: ( Factory settings → p. 83)).
To configure the IP settings of the IoT interface:
Select [IoT] menu.
> The menu page shows the current settings.
Set the following parameters as required:
Name
Description
Possible values
[DHCP]
Activate/deactivate the DHCP client of the
device
[Static IP]
IP settings were set by the user
[DHCP]
IP settings are set by a DHCP
server in the network.
[IP address]*
IP address of the IoT port
Factory setting: 169.254.X.X
[Subnet mask]*
Subnet mask of the Ethernet network
Factory setting: 255.255.0.0
[Default gateway IP address]*
IP address of the network gateway
Factory setting: 0.0.0.0
[MAC address]
MAC address of the IoT port
The value is firmly set.
* ... can only be edited if parameter [DHCP] = [Static IP]
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
25
Save changed values on the device.
>
9.1.3 IoT: Configure security mode
54680
The IoT interface of the IO-Link offers a security mode. It enables secure data transmission via
transport encryption and restriction of the access to IO-Link masters and IO-Link devices via user
authentication.
To configure the security mode:
Select [IoT] menu.
> The menu page shows the current settings.
Set the following parameters as required:
Name
Description
Possible values
[Security mode HTTPS]
Set the security mode
[Disabled]
Security mode disabled
[Enabled]
Security mode enabled
[Security password]
Password
Note: The set password is not displayed.
Save changed values on the device.
The security mode only protects the access to the device via the IoT interfac e.
The user name "administrator" cannot be changed.
The security mode can be enabled without setting the password. During the attempt to write to
the device, LR DEVICE requires to enter and confirm the password.
After entering the password, the user has unrestricted access to IO-Link masters and
connected IO-Link devices. The password will only be requested again if the current LR
DEVICE session is over (e. g. after restarting the LR DEVICE).
To change the set password:
Sign in with a valid password.
Enter the new password in the field [Security password].
Write changes to the device.
> The new password is set.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
26
>
9.1.4 IoT: Configuring access rights
34046
The access rights define which instance may read and / or write the parameter data, process data and
event/diagnostic messages.
In order to configure the access rights to the IO-Link master:
Select [IoT] menu.
> The menu page shows the current settings.
Set the following parameters as required:
Name
Description
Possible values
[Access Rights]
The access rights to the
parameter data, process data
and the event/diagnostic
messages of the IO-Link master
as well as the connected IO-Link
devices
[PROFINET + IoT]*
PROFINET and IoT Core have read
and write access rights to parameters
and process data
PROFINET and IoT Core have read
access rights to events/alarms
[PROFINET + IoT
(read-only)]
PROFINET has read and write access
rights to parameters and process data
PROFINET has read access rights to
events/alarms
IoT Core only has read access rights to
parameters, process data and
events/alarms
[IoT only]
IoT Core has read and write access
rights to parameters and process data
IoT has read access rights to
events/alarms
PROFINET has no access rights
* ... Factory setting
Save changed values on the device.
If in LR DEVICE and PROFINET projection software the parameter [Access Rights] is =
[PROFINET + IoT], the parameter values set in the PROFINET projection software will always
apply.
If the parameter [Access Rights] in LR DEVICE is = [IoT only], set the parameter [Access
Rights] = [Keep settings] in the PROFINET projection software.
If the parameter [Access Rigts] in LR DEVICE is = [<Fieldbus> + IoT (re -only)], write access ad
to the device configuration via LR DEVICE and IoT core services is blocked. To enable write
access again, set the parameter to [<Fieldbus> + IoT] via fieldbus configuration software.
Changes of the parameter [Access Rights] will only be effective after restarting the IO-Link
master ( Firmware: Reboot the device ( )). → p. 31
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
27
>
9.1.5 IoT: Configure the interface to LR AGENT or LR SMARTOBSERVER
34048
To enable transfer of process data from the IO-Link master to LR AGENT or LR SMARTOBSERVER,
the interface has to be configured accordingly.
Select [IoT] menu.
> The menu page shows the current settings.
Set the following parameters as required:
Name
Description
Possible values
[IP address LR Agent or
SMARTOBSERVER]
IP address of LR AGENT or
LR SMARTOBSERVER
Factory setting: 255.255.255.255
[Port LR Agent or
SMARTOBSERVER]
Port number that is used to send process data
to LR AGENT or LR SMARTOBSERVER
0
...
65535
Factory setting:: 35100
[Interval LR Agent or
SMARTOBSERVER]
Cycle time for the transfer of the process data to
LR AGENT or LR SMARTOBSERVER (value in
milliseconds)
[Off]
no transfer
500
...
2147483647
500 ms
...
2147483647 ms
[Application Tag]
Source identifier of the IO-Link master in the
structure of LR AGENT or
LR SMARTOBSERVER (String32)
Factory setting: AL1301
After changing the parameter [Port LR Agent or SMARTOBSERVER] or [Application Tag], it
may take 120 seconds before the device establishes a new TCP connection.
To prevent the delay:
Reboot the device after changing the the parameter.
Save changed values on the device.
>
9.1.6 Fieldbus: Configure IP settings
34527
The PROFINET interface (ports X21/X22) has to be configured in order to acces the IO-Link master
via the PROFINET.
To set the IP properties of the fieldbus interface:
Select [Fieldbus] menu.
> The menu page shows the current settings.
Set the following parameters as required:
Parameter
Description
Possible values
[IP address]
IP address of the PROFINET interface
Factory setting: 0.0.0.0
[Subnet mask]
Subnet mask of the PROFINET network
Factory setting: 0.0.0.0
[Default gateway IP address]
IP address of the gateway
Factory setting: 0.0.0.0
[Hostname]
Name of the device in the PROFINET network
e.g. al1xxx
[MAC address]
MAC address of the device
The value is firmly set.
Save changed values on the device.
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
28
9.1.7 -Link ports: Activate data transfer to LR AGENT or IO
LR SMARTOBSERVER
33690
The user can decide separately for each IO-Link port whether the process data of the connected
IO-Link devices should be transferred to LR AGENT or LR SMARTOBSERVER.
To transfer process data the interface to the LR AGENT or LR SMARTOBSERVER has to be
correctly congured ( IoT: Configure the interface to LR AGENT or LR
SMARTOBSERVER ( p. 27)).
To activate / deactivate data transfer:
Select [Port x] menu (x = 1...4).
> The menu page shows the current settings.
Set the following parameters as required:
Name
Description
Possible values
[Transmission to LR
Agent
or SMARTOBSERVER]
Transfer of process data of the connected
IO-Link device to LR AGENT oder
LR SMARTOBSERVER
[Disabled]
Transfer process data
[Enabled]
Don't transfer process data
Save changed values on the device.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
29
>
9.1.8 -Link ports: Configure operating mode IO
33694
The IO-Link ports X01...X04 of the device support the following operating modes:
Disabled: no data transfer at pin 4 (C/Q) of the IO-Link port
Digital input (DI): binary input signal at pin 4 (C/Q) of the IO-Link port
Digital output (DO): binary output signal at pin 4 (C/Q) of the IO-Link port
-Link: IO-Link data transfer via pin 4 (C/Q) of the IO-Link port IO
The user can set the operating mode separately for each IO-Link port.
To set the operating mode of an IO-Link port:
Select [Port x] menu (x = 1...4).
> The menu page shows the current settings.
Set the following parameters as required:
Name
Description
Possible values
[Mode Pin4 US]
Operating mode of pin 4 of the -Link port IO
[Disabled]
Port deactivated
[DI]
Operation as digital input
[DO]
Operation as digital output
[IO-Link]
Operation as IO-Link interface
[Cycle time actual]**
Current cycle time of the data transfer between
IO IO-Link master and -Link device on the port
(value in microseconds)
Parameter can only be read
[Cycle time preset]*
Cycle time of the data transfer between the IO-Link
master and the IO-Link device at the port (value in
microseconds)
0
The device automatically sets
the fastest possible cycle time.
1
...
132800
1 microsecond
...
132800 microseconds
[Bitrate]**
Current transmission rate of the data transfer
between the IO-Link master and the IO-Link device
on the port
Parameter can only be read
* ... Parameter only available if [Mode] = [IO-Link]
** ... Parameter only visible if the IO-Link device is connected to the IO-Link port.
Save changed values on the device.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
30
>
9.1.9 -Link ports: Set the device validation and data storage IO
33697
The user can choose how the IO-Link ports are to behave with regard to the device validation and the
storage / recovery of parameter data of the connected IO-Link device.
The following options are available:
Option
Validation of the IO-Link
device
Storage of the parameter values
Recovery of the parameter
values
[No check and clear]
no
no
no
[Type compatible
V1.0 device]
yes, test the compatibility with
IO-Link standard V1.0
no
no
[Type compatible
V1.1 device]
yes, test the compatibility with
IO-Link standard V1.1
no
no
[Type compatible
V1.1 device with
Backup + Restore]
yes, test the compatibility with
IO-Link standard V1.1 and
identity of design (vendor ID
and device ID)
yes, automatic storage of the
parameter values; changes of the
current parameter values will be
stored
yes, recovery of the parameter
values when connecting an
identical IO-Link device with
factory settings
[Type compatible
V1.1 device with
Restore]
yes, test the compatibility with
IO-Link standard V1.1 and
identity of design (vendor ID
and device ID)
no, there is no automatic storage
changes of the current parameter
values will not be stored
yes, recovery of the parameter
values when connecting an
identical IO-Link device with
factory settings
The options only apply if the IO-Link port is in the operating mode "IO-Link".
For options [Type compatible V1.1 device with Backup + Restore] and [Type compatible V1.1
device with Restore]: If the vendor ID and device ID are changed in the online mode, the data
memory will be deleted and a new backup of the parameter values of the connected IO-Link
device will be created in the IO-Link master.
To configure the device validation and the data storage:
select [Port x] menu (x = 1...4).
> The menu page shows the current settings.
Set the following parameters as required:
Name
Description
Possible values
[Validation / Data
Storage]
Supported IO-Link standard and behaviour of the
IO-Link master when connecting a new IO-Link
device at port x (x = 1...4)
[No check and clear]
[Type compatible V1.0
device]
[Type compatible V1.1
device]
[Type compatible V1.1 device
with Backup + Restore]
[Type compatible V1.1 device
with Restore]
[Vendor ID]
ID of the manufacturer that is to be validated
0...65535
Factory setting: 0#
ifm electronic: 310
[Device ID]
ID of the IO-Link device that is to be validated
0...16777215
Factory setting: 0
Save changed values on the device.
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
31
9.1.10 Info: Show device information
34065
To read the general information of the ifm IO-Link master:
Select [Info] menu.
> The menu page shows the current settings.
Name
Description
Possible values
[Product code]
Article number of t -Link master he IO
AL1301
[Device family]
Device family of the IO-Link master
IO-Link master
[Vendor]
Vendor
ifm electronic gmbh
[SW-Revision]
Firmware of the IO-Link master
[HW revision]
Hardware version of the IO-Link master
[Bootloader revision]
Bootloader version of the IO-Link master
[Serial number]
Serial number
>
9.1.11 Firmware: Reset device to factory settings
33838
When the IO-Link master is reset, all parameters are set to the factory settings:
To reset the device to factory settings:
Select [Firmware] menu.
> The menu page shows the current settings.
Click on [Factory Reset] to reset the device.
> LR DEVICE sets the device to the factory settings.
>
9.1.12 Firmware: Reboot the device
33832
When rebooting the device, all settings are kept.
To restart the AL1301:
Select [Firmware] menu.
> The menu page shows the current settings.
Click on [Reboot] to reboot the device.
> LR DEVICE reboots the ifm IO-Link master.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
32
>
9.1.13 Configure IO-Link devices
33856
To configure the IO-Link devices connected to the device with the LR DEVICEparameter setting
software:
Requirements:
> -Link master is correctly installed and connected to the LR DEVICE parameter setting software. IO
> The IO-Link device is connected correctly with the AL1301.
> Operating mode of the IO-Link port is "IO-Link" ( IO-Link ports: Configure operating mode
( )). → p. 29
> IoT has write access rights to the IO-Link master ( IoT: Configuring access rights ( → p. 26)).
1 Select IO- nk master Li
Start LR DEVICE.
Update IODD file library
OR:
Import IODD file of the IO-Link device manually.
Scan network for devices.
> LR DEVICE detects IO-Link master.
2 Add IO-Link device
Under [ONLINE]: Click on the required IO-Link master.
> LR DEVICE automatically detects the IO-Link devices connected to -Link master (e.g. ifm sensor KG5065). the IO
3 Configure IO-Link device
Mouse click on the port to which the IO-Link device is connected.
> LR DEVICE reads and shows the current parameter values of the IO-Link device.
Configure IO-Link device.
Information about the available parameters of the IO-Link device: IO Device Description
(IODD) des IO-Link Devices
Save the changed configuration on the IO-Link device.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
33
9.2 ifm IoT Core
Content
Programmers' notes ............................................................................................................................... 34
First steps ..............................................................................................................................................38
General functions ................................................................................................................................... 38
IoT: Configuring access rights ................................................................................................................ 42
IoT: Configuring IP settings .................................................................................................................... 42
IoT: Configuring the LR AGENT or LR SMARTOBSERVER interface .................................................. 43
IoT: Configuring security mode ..............................................................................................................43
Fieldbus: Configuring IP settings ............................................................................................................ 46
IO-Link ports: Setting the operating mode of pin 4 (US) ........................................................................ 46
IO-Link ports: Configuring device validation and data storage ............................................................... 47
IO-Link ports: Configuring data transfer to LR AGENT or LR SMARTOBSERVER .............................. 48
IO-Link ports: Reading / writing process data ........................................................................................ 49
IO-Link ports: Indicating port events ....................................................................................................... 52
IO-Link devices: Accessing parameters ................................................................................................. 52
IO-Link devices: Reading an writing device information ........................................................................ 54
IO-Link devices: Indicating IO-Link events ............................................................................................. 54
Gateway: Resetting, rebooting and localising the device ....................................................................... 54
Gateway: Reading device information .................................................................................................... 55
Gateway: Reading status and diagnostic information ............................................................................ 55
Gateway: Updating the firmware ............................................................................................................ 56
Gateway: Setting the application tag .................................................................................................... 57
Subscribing to notifications ..................................................................................................................... 58
Using Web Socket .................................................................................................................................. 62
MQTT support ........................................................................................................................................ 64
Using the IoT-Core Visualizer ................................................................................................................ 68
52244
General notes on the ifm IoT Core: ( ) Programmers' notes → p. 34
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
34
9.2.1 Programmers' notes
Content
IoT Core: General information ................................................................................................................ 34
Access the ifm IoT Core ......................................................................................................................... 35
IoT Core: Diagnostic codes .................................................................................................................... 37
34229
>
IoT Core: General information
52256
The DataLine device family has an IoT Core. The IoT Core allows the user to address the AL1301
from IT networks via a REST API and to integrate it into Internet- -Things applications. of
A device description is stored on the AL1301. This device description is a structured,
machine-readable data object in JSON format. All current values of parameters, process data,
diagnostic data and device information are mapped in this data object. These data values can be read
and changed by means of services.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
35
>
Access the ifm IoT Core
52257
The user can access the ifm IoT Core via HTTP requests. The following request methods are
available.
>
GET request
33804
Using the GET method the user has read access to a data point.
The syntax of the request to the IoT Core is:
http://ip/datapoint/service
Parameter
Description
ip
IP address of the IoT interface
data_point
Data point which is to be accessed
service
Service
The syntax of the return of the IoT Core is:
{
"cid":id,
"data":{"value":resp_data},
"code":diag_code
}
Parameter
Description
id
Correlation ID for the assignment of request and return
resp_data
Value of the data point; depending on the data type of the data point
diag_code
Diagnostic code ( ( IoT Core: Diagnostic codes → p. 37))
>
Example: GET request
54033
Request (via browser):
http://192.168.0.250/devicetag/applicationtag/getdata
Response:
{
"cid":-1,
"data":{"value":"AL1301"},
"code":200
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
36
>
POST request
54700
Using a POST request the user has read and write access to a data point.
The syntax of the request to the IoT Core is:
{
"code":"code_id",
"cid":id,
"adr":"data_point/service",
"data":{req_data},
"auth":{"user":"usr_id","passwd":"password"}
}
Field
Parameter
Description
code
code_id
Service class
request
Request
transaction
Transaction
event
Event
cid
id
Correlation ID for the assignment of request and response; ID freely assignable by the user
adr
data_point
Data point of the element tree which is to be accessed
service
Service to be performed ( ( Overview: IoT services → p. 106))
data*
req_data
Data to be transferred to the IoT Core (e.g. new values); syntax depending on the service
auth**
usr_id
user name (base64 coded); default value: administrator
password
password (base64 coded)
* = optional; only required for services, that submit data to the IoT core (e. g. setdata)
** = optional; only required, if security mode is activated
The syntax of the return of the IoT Core is:
{
"cid":id,
"data":{resp_data},
"code":diag_code
}
Field
Parameter
Description
cid
id
Correlation ID for the assignment of request and response (see request)
data*
resp_data
Value of the data point; syntax depending on the service
code
diag_code
Diagnostic code ( ( IoT Core: Diagnostic codes → p. 37))
* = optional; only required for services, that receive data from the IoT core (e.g. getdata)
>
Example: POST request
54035
Request:
{
"code":"request",
"cid":4711,
"adr":"devicetag/applicationtag/getdata"
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
37
Response:
{
"cid":4711,
"data":{"value":"AL1301"},
"code":200
}
>
IoT Core: Diagnostic codes
54688
Code
Text
Description
200
OK
Request successfully processed
230
OK but needs reboot
Request successfully processed; IO-Link master must be restarted
231
OK but block request not finished
Request successfully processed; blockwise request, but not yet
finished
232
Data has been accepted, but internally modified
New values have been accepted, but were adjusted by the IO-Link
master (Master cycle time)
233
IP settings (of IoT-Port) have been updated.
Application needs to reload device. Wait at least
1 second before reloading device.
IP settings have been successfully changed, IO-Link master will be
reloaded; wait for at least 1 second
400
Bad request
Invalid request
401
Unauthorized
Non authorised request
403
Forbidden
Forbidden request
500
Internal Server Error
Internal fault
503
Service Unavailable
The service is not available (e. -Link port in wrong operating g. IO
mode; no IO-Link device at IO-Link port)
530
The requested data is invalid
Invalid process data
531
IO-Link error
Error in IO-Link Master / device
532
PLC connected Error
Error while setting data, because IO-Link master is still connected
to fieldbus PLC
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
38
>
9.2.2 First steps
52245
To read the device description of the AL1301:
Send the following POST request to the AL1301:
{"code":"request","cid":-1,"adr":"gettree"}
> AL1301 returns the device description as structured JSON object.
Identify all substructures and the data points contained therein in the tree structure of the JSON
object.
Identify the applicable services for the access to substructures and the data points contained
therein.
>
9.2.3 General functions
61148
The AL1301 has the type device ( ( )). Overview: IoT types → p. 105
The following services can be used on the root element of the type : device
Service
Description
../gettree
Provide the complete tree or subtree of the device description (JSON)
../getidentity
Reading device information
../getdatamulti
Reading several parameter values sequentially
../getelementinfo
Reading detailed information of an element
../getsubscriberlist
Print a list of all active notification subscriptions
../querytree
Search device description for specific elements
Depending on the read and write access rights, the following services can be applied to elements of
type : data
Service
Description
../getdata
Reading the value of the element
../setdata
Write the value of the element
>
Example: Reading properties of an element
59782
Task: Determine the data type and value range of the accessrights parameter.
Solution: Read the properties of the element of the getelementinfo service. iotsetup/accessrights
The fields type (data type) and valuation (range of values) contain the required information.
Request:
{
"code":"request",
"cid":4711,
"adr":"getelementinfo",
"data":{"adr":"iotsetup/accessrights"}
}
Response:
{
"cid":4711,
"data":{
"identifier":"accessrights",
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
39
"type":"data",
"uid":null,
"profiles":["parameter"],
"format":{
"type":"enum",
"namespace":"json",
"encoding":"integer",
"valuation":{
"valuelist":{
"0":"Fieldbus + IoT",
"1":"Fieldbus + IoT (read-only)",
"3":"IoT only"}}}},
"code":200
}
The accessrights parameter has the data type ENUM with the valid values "Fieldbus + IoT", "Fieldbus
+ IoT (read only)" and "IoT only".
>
Example: output subtree
61149
Task: Output all direct sub-elements of the node . firmware
Solution: Use the service gettree to output the required subtree (root node: firmware, sub-levels to be
shown: 1)
Request:
{
"code":"request",
"cid":4711,
"adr":"gettree",
"data":{
"adr":"firmware",
"level":1}
}
Response:
{
"cid":4711,
"data":{
"identifier":"firmware",
"type":"structure",
"profiles":[
"software","software/uploadablesoftware"],
"subs":[
{
"identifier":"version","type":"data","profiles":["parameter"],
"format":{"type":"string","namespace":"json","encoding":"UTF-8"}},
{
"identifier":"type","type":"data",
"format":{"type":"string","namespace":"json","encoding":"UTF-8"}},
{
"identifier":"install","type":"service"},
{
"identifier":"factoryreset","type":"service"},
{
"identifier":"signal","type":"service"},
{
"identifier":"container","type":"data",
"format":{"type":"binary","namespace":"json","encoding":"base64"}},
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
40
{
"identifier":"reboot","type":"service"}]
},
"code":200
}
>
Example: Read several parameter values of the IO-Link master simultaneously
33840
Task: The following current values are to be read by the IO-Link master: temperature, serial number
Solution: Read the current parameter values using the getdatamulti service (data point temperature:
/processdatamaster/temperature; data point serial number: /deviceinfo/serialnumber)
Request:
{
"code":"request",
"cid":4711,
"adr":"/getdatamulti",
"data":{"datatosend":["/processdatamaster/temperature","/deviceinfo/serialnumber"]
}
}
Response:
{
"cid":4711,
"data":{"processdatamaster/temperature":{"code":200,"data":44},
"deviceinfo/serialnumber":{"code":200,"data":"000174210147"}},
"code":200
}
>
Example: Browsing device description
61150
Task: List all elements with the designation "status" and the profile "runcontrol".
Solution: Use the service querytree to browse the device description with the parameters "status"
(name) and "runcorntrol" (profile)
Request:
{
"cid":4711,
"adr":"querytree",
"code": request","
"data":{
"profile":"runcontrol",
"name":"status"}
}
Response:
{
"cid":4711,
"data":{
"adrList":[
"device/connections/mqttConnection/status",
"device/connections/mqttConnection/mqttCmdChannel/status"]},
"code":200
}
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
41
Setting the storage durati on
61153
The IoT Core offers the possibility to set the storage duration of data and notifications. The Services
Service: setdata ( ) and ( → p. 116 Service: subscribe p. 118) therefore have the parameter
"duration".
>
Example: Subscribing to notifications
61154
Task: The current values of the following parameters are to be sent regularly to a network server with
IP address 192.168.0.4:
Product name of the IO-Link Devices an IO-Link port X02
Cyclic input data of the IO-Link Devices an IO-Link port X02
Operating temperature of the IO-Link master.
The subscription is only to be active until the next restart of the IO-Link master.
Solution: Subscribe to the required data using the subscribe service.
Request:
{
"code":"request",
"cid":4711,
"adr":"/timer[1]/counter/datachanged/subscribe",
"data":{
"callback":"http://192.168.0.4:80/temp",
"datatosend":[
"/iolinkmaster/port[2]/iolinkdevice/productname",
"/iolinkmaster/port[2]/iolinkdevice/pdin",
"/processdatamaster/temperature"],
"duration":"uptime"}
}
Response:
{
"cid":4711,
"code":200
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
42
>
9.2.4 IoT: Configuring access rights
59785
Substructure: iotsetup
Available data points:
Name
Description
Access
../accessrights
Access rights to the IO-Link master
rw
rw ... read and write
If in IoT and PROFINET projection software the parameter [Access Rights] is = [PROFINET +
IoT], the parameter values set in the PROFINET projection software will always apply.
If in IoT the parameter [Access Rights] is = [IoT only], set the parameter [Access Rights] =
[Keep settings] in the PROFINET projection software.
If in LR DEVICE the parameter [Access Rigts] is = [EtherCAT + IoT (read-only)], write access
to the device conguration via LR DEVICE and IoT core services is blocked. To enable write
access again, set the parameter to [EtherCAT + IoT] via eldbus conguration software.
Changes of the parameter [Access Rights] will only be eective after restarting the IO-Link
master ( Firmware: Reboot the device ( )). p. 31
>
9.2.5 IoT: Configuring IP settings
61155
Substructure: iotsetup
Available data points:
Name
Description
Access
../network/dhcp
Conguration of the IP settings of the IoT port
rw
../network/ipaddress
IP address of the IoT port
rw
../network/subnetmask
Subnet mask of the network segment
rw
../network/ipdefaultgateway
IP address of the network gateway
rw
rw ... read and write
Applicable services:
Name
Description
../network/setblock
Write all values of the substructure blockwise
Change the IP parameters in the substructure network only blockwise with the setblock
service!
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
43
>
9.2.6 IoT: Configuring the LR AGENT or LR SMARTOBSERVER interface
59786
Substructure: iotsetup
Avalable data points:
Name
Description
Access
../smobip
IP address of the SMARTOBSERVER LR
rw
../smobport
Port number of the LR SMARTOBSERVER
rw
../smobinterval
Cycle time for data transmission to LR SMARTOBERVER (value in milliseconds)
rw
rw ... read and write
>
9.2.7 IoT: Configuring security mode
54683
The access to the IoT interface of the IO-Link master can be protected with a security mode:
Substructure: iotsetup
Available data points:
Name
Description
Access
../security/securitymode
active security mode
rw
../security/password
Password for authentication (Base64 coded)
w
rw ... read and write
w ... write only
Valid character set for the Base64 coding / decoding of the password: UTF-8
Online tool for coding / decoding: www.base64encode.org
>
Note: Security mode
54684
The security mode enables restricting access to the -Link master and the connected IO-Link devices IO
from the IT network. In the activated security mode, the following restrictions apply:
Access only with authentication (password-protected user account)
Access only via secure https connection (Transport Layer Security - TLS)
The security mode only protects the access to the device via the IoT interface.
The standard value for users is: administrator
The set password cannot be read with getdata.
The current status of the security function can be read with the getidentity service ( Servicet:
getidentity ( )). → p. 109
For the authentication, the user must additionally provide the POST requests with a valid user name
and password in the field "auth". The user name and the password will be shown as Base64-coded
character strings ( Example: Request with authentication ( → p. 44)).
The following requests can be done if the security mode is enabled, also without authentication:
/getidentity
/deviceinfo/vendor/getdata
/deviceinfo/productcode/getda ta
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
44
Example: Activate security mode
54701
Task: Activate the security mode of the IO-Link interface of the IO-Link master. Set the password
"password" (Base64 coded: cGFzc3dvcmQ=)
Solution: The activation sonsists of 2 steps:
1 Activate security mode
Use service setdata with datapoint iotsetup/security/securitymode to activate the security mode.
Request:
{
"code":"request",
"cid":-1,
"adr":"/iotsetup/security/securitymode/setdata",
"data":{"newvalue":"1"}
}
Response:
{
"cid":-1,
"code":200
}
2 Set required password
Use service setdata with data point iotsetup/security/password to set the required password.
Request:
{
"code":"request",
"cid":-1,
"adr":"/iotsetup/security/password/setdata",
"data":{"newvalue":"cGFzc3dvcmQ="}
}
Response:
{
"cid":-1,
"code":200
}
>
Example: Request with authentication
54685
Task: The temperature of the IO-Link master is to be read. The security function is enabled (current
password: password).
Solution: Read the data point processdatamaster/temperature with the getdata service. The request
must be sent using https. The user name and the password are transferred as a Base64-coded
character string ("administrator" = "YWRtaW5pc3RyYXRvcg==", "password" = "cGFzc3dvcmQ=")
Request:
{
"code":"request",
"cid":-1,
"adr":"processdatamaster/temperature/getdata",
"auth":{"user":"YWRtaW5pc3RyYXRvcg==","passwd":"cGFzc3dvcmQ="}
}
Response:
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
45
{
"cid":-1,
"data":{"value":37},
"code":200
}
>
Example: reset password
54686
Task: The existing password is to be reset.
Solution: To reset a password, disable the security mode. To disable it, enter the user name and the
password (the fields "user" and "passwd").
Request:
{
"code":"request",
"cid":-1,
"adr":"iotsetup/security/securitymode/setdata",
"data":{"newvalue":0},
"auth":{"user":"YWRtaW5pc3RyYXRvcg==","passwd":"SW9UNGlmbQ=="}
}
Response:
{
"cid":-1,
"code":200
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
46
>
9.2.8 Fieldbus: Configuring IP settings
59808
Substructure: fieldbussetup
Available data points:
Name
Description
Access
../hostname
Name of the IO-Link master in the fieldbus project
rw
../fieldbusfirmware
Firmware version of the IO-Link master
r
../network/macaddress
MAC address of the fieldbus port
r
../network/ipaddress
IP address of the fieldbus port
rw*
../network/subnetmask
Subnet mask of the network segment
rw*
../network/ipdefaultgateway
IP address of the network gateway
rw*
../connectionstatus
Status of the connection to the PROFINET network
r
r ... read only
rw ... read and write
* ... only changeable, if the PROFINET controller is not in RUNNING state
>
9.2.9 -Link ports: Setting the operating mode of pin 4 (US) IO
59793
Substructure (n = 1...4). : iolinkmaster/port[n]
Available data points:
Name
Description
Access
../mode
Operating mode of the IO-Link port
rw*
../mastercycletime_preset
Cycle time of the data transfer at the IO-Link port (value in ms)
rw*
../mastercycletime_actual
Current cycle time of the data transfer at the IO-Link port (value in ms)
r
../comspeed
Data transfer rate of the IO-Link port
r
r ... read only
rw ... read and write
* ... only changeable, if the <Feldsbus> plc is not in RUNNING state
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
47
>
9.2.10 -Link ports: Configuring device validation and data storage IO
59792
Substructure: iolinkmaster/port[n] (n = 1...4).
Available data points:
Name
Description
Access
../validation_datastorage_mode
Response of the IO-Link port when a new IO-Link device is connected
rw*
../validation_vendorid
IO-Link ID of the manufacturer that is to be validated
rw*
../validation_deviceid
IO-Link ID of the device that is to be validated
rw*
../datastorage
Structure for port data storage
rw
../datastorage/maxsize
Maximum size of the data storage content (in bytes)
r
../datastorage/chunksize
Size of a data segment (in bytes)
r
../datastorage/size
Size of the data storage content (in bytes)
r
r ... read only
rw ... read and write
* ... can only be changed if the PROFINET PLC is not in RUNNING state
Applicable services:
Service
Description
../validation_useconnecteddevice
Validate the IO-Link device connected to the IO-Link port*
../datastorage/getblobdata
Reading the content of the data storage area
../datastorage/stream_set
Transfer an individual data segment*
../datastorage/start_stream_set
Start sequential transmission of several data segments*
* ... can only be changed if the PROFINET PLC is not in the RUNNING state
>
Example: Clone the Data Storage of an IO-Link port
52344
Task: Save the Data Storage of IO-Link port X02 of IO-Link master 1 and restore the data at IO-Link
master 2.
Solution: The cloning process consists of 2 steps. In the first step, the Data Storage of the IO-Link
port of IO-Link master 1 is saved. In the second step, the saved data is restored at the Data Storage of
port IO-Link port of IO-Link master 2.
Save Data Storage:
1 Preparations
Read size of segments of Data Storage (h = number of bytes):
{"code":"request", "cid": -1,"adr":"/iolinkmaster/port[2]/datastorage/chunksize/getdata"}
Example: h = 256
Read total size of Data Storage area (g = number of bytes):
{"code": "request", "cid": -1, "adr": "/iolinkmaster/port[2]/datastorage/size/getdata"}
Example: g = 550
Calcuate the number of reading steps n: n = first integer value to which the following applies: g < n*h
Example: n= 3, because 550 < 3*256
2 Read Data Storage of IO-Link port
Read Data Storage segment by segment ("pos" is the byte offset, at which the reading process with length "length"
starts).
{"code": "request", "cid": -1, "adr": "/iolinkmaster/port[2]/datastorage/getblobdata", "data": {"pos": 0, "length": h}}
{"code": "request", "cid": -1, "adr": "/iolinkmaster/port[2]/datastorage/getblobdata", "data": {"pos": h, "length": h}}
{"code": "request", "cid": -1, "adr": "/iolinkmaster/port[2]/datastorage/getblobdata", "data": {"pos": 2*h, "length": h}}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
48
...
{"code": "request", "cid": -1, "adr": "/iolinkmaster/port[2]/datastorage/getblobdata", "data": {"pos": n*h, "length": h}}
Example:
1st read request: pos = 0, length = 256
2nd read resquest: pos = 256, length =256
3rd read request: pos = 512, length = 256
> Each segment value will be returned as BASE64 coded string.
Join segments.
Restore Data Storage:
1 Preparations
Determine the size of the saved Data Storage value (n = number of bytes).
Example: n = 550
Read size of segments (s = number of bytes):
{"code":"request", "cid": -1,"adr":"/iolinkmaster/port[1]/datastorage/chunksize/getdata"}
Example: s = 256
2 Transfer Data Storage strings
Start transfer of Data Storage string ("size" = size of Data Storage string):
{"code":"request", "cid": -1, "adr":"/iolinkmaster/port[1]/datastorage/start_stream_set", "data": {"size": n}}
Example: size = 550
Transfer Data Storage string segment by segment ("value" = string value of length s):
{"code": "request", "cid": -1, "adr": "/iolinkmaster/port[1]/datastorage/stream_set", "data": {"value":
"aWZtfgIAAABBTDF4NXhfY25faXRfdDIuMi43Nw..."}
>
9.2.11 -Link ports: Configuring data transfer to LR AGENT or LR IO
SMARTOBSERVER
59795
Substructure: iolinkmaster/port[n] (n = 1...4).
Available data points:
Name
Description
Access
../senddatatosmob
Process data to LR AGENT or LR SMARTOBSERVER
rw
rw ... read and write
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
49
>
9.2.12 -Link ports: Reading / writing process data IO
61156
Substructure: iolinkmaster/port[n] (n = 1...4)
Available data points:
Name
Description
Access
../pin2in
Value of the digital input on pin 2 of the IO-Link port
r
../iolinkdevice/pdin
Value of the IO-Link input on pin 4 of the IO-Link port
r
../iolinkdevice/pdout
Value of the IO-Link -Link port output on pin 4 of the IO
rw*
r ... read only
rw ... read and write
*... can only be changed if the fieldbus PLC is not in RUNNING state
>
Example: Read IO-Link process data (operating mode "IO-Link")
33842
Task: Read the current measured value of the ifm temperature sensor TN2531 at IO-Link port X02
Solution: Read the data point for the process input data with the service. getdata
Request:
{
"code":"request",
"cid":4711,
"adr":"/iolinkmaster/port[2]/iolinkdevice/pdin/getdata"
}
Response:
{
"cid":4711,
"data":{"value": "03C9"},
"code":200
}
The return value is given in hexadecimal format. Besides the temperature value the return value
comprises additional information ( IO Device Description (IODD) of the sensor). The temperature
value is shown in bits 2 to 15.
0x03C9 = 0b 1111001001
Temperature value: 0b11110010 = 242
Therefore: The current temperature value is 24.2 °C.
>
Example: Writing IO-Link value (operating mode "IO-Link")
59804
Task: Switch on the buzzer of DV2500 at IO-Link Port X2. The DV2500 operates in On/Off mode.
Solution: The IODD of the DV2500 shows the structure of the IO-Link process value ( e.g. LED
activity). The buzzer will be switched using bit 40 of the process value (OFF = 0, ON = 1).
To switch the buzzer:
1. Read the current process value ( Example: Read IO-Link process data (operating mode
"IO-Link") ( → p. 49)).
2. t bit 40 of the read value to 1. Se
3. Write the process value to the IO-Link device.
Example:
Read process value:
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
50
0x0000 0000 004D = 0b0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0100 1101
New process value:
0b0000 000 0000 0000 0000 0000 0000 0000 0100 1101 = 0x0100 0000 004D 1 0000 0000
Request:
{
"code":"request",
"cid":10,
"adr":"iolinkmaster/port[2]/iolinkdevice/pdout/setdata",
"data":{"newvalue":"01000000004D"}
}
Response:
{
"cid":10,
"code":200
}
>
Example: Writing digital output (operating mode "DO")
59803
Task: Set the output value of the IO-Link devices at IO-Link Port X1 to "ON". The operating mode of
the IO-Link port is "Digital Output (DO)".
Solution: Write the value 1 to data point ut. The value has to be written as hexadecimal value with pdo
a length of 1 byte (OFF = "00", ON = "01").
Request:
{
"code":"request",
"cid":10,
"adr":"iolinkmaster/port[1]/iolinkdevice/pdout/setdata",
"data":{"newvalue":"01"}
}
Response:
{
"cid":10,
"code":200
}
>
Example: Reading digital input (operating mode "DI")
59802
Task: Read the current input value of the IO-Link device at IO-Link port X5. The operating mode of the
IO-Link port is "Digital Intput (DI)".
Solution: Read the value of data point pdin. The value will be returned as hexadecimal value with a
length of 1 byte (OFF = "00", ON = "01"').
Request:
{
"code":"request",
"cid":10,
"adr":"iolinkmaster/port[5]/iolinkdevice/pdin/getdata"
}
Response:
{
"cid":10,
"data":{"value":"00"},
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
51
"code":200
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
52
>
9.2.13 -Link ports: Indicating port events IO
59796
Substructure: iolinkmaster/port[n] (n = 1...4).
Available data points:
Name
Description
Access
../portevent
Indication of the following events at IO-Link port n:
plugging IO-Link device
pulling IO-Link device
changing operating mode of IO-Link port
r
r ... read only
Subscribing events: Subscribing to notications ( ) p. 58
>
9.2.14 -Link devices: Accessing parameters IO
59800
The ifm IoT Core supports the conguration of the connected IO-Link devices. A parameter is
accessed via IO-Link index and subindex ( IO Device Description (IODD) of the device).
Substructure: iolinkmaster/port[n]/iolinkdevice (n = 1...4)
Applicable services:
Service
Description
../iolreadacyclic
Read a parameter of an IO-Link device (acyclic)
../iolwriteacyclic
Write a parameter of an IO-Link device (acyclic)
>
Example: Read the parameter value of an IO-Link device
33847
Task: Read the serial number of the ifm temperature sensor TN2531 at IO-Link port X02
Solution: Read the serial number with the service from the IO-Link device (index: iolreadacyclic
21, subindex: 0)
Request:
{
"code":"request",
"cid":4711,
"adr":"/iolinkmaster/port[2]/iolinkdevice/iolreadacyclic",
"data":{"index":21,"subindex":0}
}
Return:
{
"cid":4711,
"data":{"value":"4730323134323830373130"},
"code":200
}
The returned value is given in hexadecimal format. The conversion of the HEX value in a STRING
value is: G0214280710
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
53
Example: Change the parameter value of an IO-Link device
33844
Task: Set the output conguration OUT1 of the ifm temperature sensor TN2531 at IO-Link port X02 to
the value "Hnc / hysteresis function, normally closed".
Solution: Change the parameter [ou1] of the sensor to the value 4 using the iolwriteacyclicdata
service. The parameter can be accessed via IO-Link index 580, subindex 0 ( -Link description of IO
the sensor).
Request:
{
"code":"request",
"cid":4711,
"adr":"/iolinkmaster/port[2]/iolinkdevice/iolwriteacyclic",
"data":{"index":580,"subindex":0,"value":"34"}
}
The value has to be given in hexadecimal format. The conversion of the STRING value in a HEX value
is: 34.
Response:
{
"cid":4711,
"code":200
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
54
>
9.2.15 IO-Link devices: Reading an writing device information
59797
Substructure: iolinkmaster/port[n]/iolinkdevice (n = 1...4)
Available data points:
Name
Description
Access
../status
Status of the connected IO-Link device
r
../vendorid
IO-Link ID of the vendor
r
../deviceid
IO-Link ID of the IO-Link device
r
../productname
Product name of the IO-Link device
r
../serial
Serial number of the IO-Link device
r
../applicationspecictag
Device-specic identication (application tag)
rw
r ... read only
rw ... read and write
>
9.2.16 -Link devices: Indicating IO-Link events IO
59798
Substructure: iolinkmaster/port[n]/iolinkdevice (n = 1...4).
Available data points:
Name
Description
Access
../iolinkevent
Indication of IO-Link events
r
r ... read only
Subscribing events: Subscribing to notications ( ) p. 58
>
9.2.17 Gateway: Resetting, rebooting and localising the device
59790
Substructure: firmware
Applicable services:
Name
Description
../factoryreset
Reset IO-Link master to factory settings
../reboot
Reboot IO-Link master
../signal
Trigger the ashing of the status LED
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
55
>
9.2.18 Gateway: Reading device information
52254
Substructure: deviceinfo
Available data points:
Name
Description
Access
../productcode
Article number
r
../vendor
Manufacturer
r
../devicefamily
Device family
r
../hwrevision
Hardware revision
r
../serialnumber
Serial number
r
../revision
Firmware version
r
../bootloaderrevision
Bootloader version
r
../extensionrevisions
Firmware and bootloader version
r
../eldbustype
Fieldbus
r
r ... read only
Additional information about the AL1301 can be read with the service (getidentity Servicet:
getidentity ( )). p. 109
>
9.2.19 Gateway: Reading status and diagnostic information
61157
Substructure: processdatamaster
Available data points:
Name
Description
Access
../temperature
Temperature of the IO-Link master (value in °C)
r
../voltage
Present voltage value of the supply voltage US (value in mV)
r
../current
Present current value of the sensor supply US (value in mA)
r
../supervisionstatus
Status of the device supply US
r
r ... read only
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
56
>
9.2.20 Gateway: Updating the firmware
59789
Substructure: firmware
Available data points:
Name
Description
Access
../version
Software version
r
../type
Software type
r
../container
Structure for updating the rmware
w
../container/maxsize
Maximum size of the container structure (in bytes)
r
../container/chunksize
Size of a data segment (in bytes)
r
../container/size
Size of the container content (in bytes)
r
r = only read
w = write only
Applicable services:
Name
Description
../install
Install rmware transferred to the IO-Link master
../container/stream_set
Transfer an individual data segment
../container/start_stream_set
Start sequential transmission of several data segments
>
Example: Update rmware
52252
Task:
Update the rmware of the device; size of the rmware le: 356676 bytes
Solution:
The rmware is transferred to the device in fragments (chunks). The size of the fragments depends on
the size of the ash memory of the IO-Link master. To transfer the rmware, the rmware le must be
converted into a character string using BASE64.
1 Preparations
Determine the size of the fragments (g = number of bytes):
{"code":"request", "cid": -1, "adr":"/firmware/container/chunksize/getdata"}
Convert the firmware file into a BASE64 string.
2 Start the transfer of the firmware
Start the transfer of the firmware via the service start_stream_set (parameter "size": size of the firmware file):
{"code":"request", "cid": -1, "adr":"/firmware/container/start_stream_set", "data":{"size":356676}}
3 Load the firmware into the flash memory of the IO-Link master
Send the BASE64 string of the firmware file to the IO-Link master fragment by fragment (value = string value with
length g).
{"code": "request", "cid": -1, "adr": "/firmware/container/stream_set", "cid": -1, "data": {"value":
"aWZtfgIAAABBTDF4NXhfY25faXRfdDIuMi43Nw..."}
Repeat step 3 until all fragments of the firmware file have been sent to the IO-Link master.
> -Link master stores the segments received in the container area. IO
4 Install firmware
Start the installation of the transmitted firmware.
{"code": "request", "cid": -1, "adr": "/firmware/install", "data": {}}
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
57
9.2.21 Gateway: Setting the application tag
59791
Substructure: devicetag
Available data points:
Name
Description
Access
../applicationtag
Name of the IO-Link master (application tag)
rw
rw ... read and write
For the storage of the applicationtag 32 bytes are available on the IO-Link master. If the
memory area is exceeded during writing with setdata, the IoT core aborts the write process
and returns the diagnostics code 400.
When writing the application tag, note the dierent memory requirements of the individual
UTF-8 characters:
characters 0-127: 1 byte per character
characters >127: more than 1 byte per character
>
Example: Change name of the IO-Link master
a33823
Task: Set the name of the IO-Link master to AL1301 for the representation in the
LR SMARTOBSERVER.
Solution: Change the parameter [Application Tag] with the setdata service to the value [AL1301].
The data point of the parameter [Application Tag] in the device description object is
/devicetag/applicationtag.
Request:
{
"code":"request",
"cid":4711,
"adr":"/devicetag/applicationtag/setdata",
"data":{"newvalue":"AL1301"}
}
Response:
{"cid":4711,"code":200}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
58
>
9.2.22 Subscribing to notifications
61159
If a data point has the sub-element datachanged, the user can subscribe to notications on value and
condition changes. Notications can be triggered by the expiration of a timer or an event. The IoT Core
supports the output of notications in CSV or JSON format.
Available data points:
Name
Description
Access
timer[x]/counter
Timer for triggering a notication
rw
timer[x]/interval
Cycle time of the up date of the subscribed values
rw
iolinkmaster/port[n]/portevent
Display of the following events on -Link port n: IO
-Link device connected IO
-Link device disconnected IO
Operating mode of the IO-Link port changed
rw
iolinkmaster/port[n]/iolinkdevice/iolinkevent
Display of IO-Link events
rw
r ... read only
rw ... read and write
x = [1,2]
n = 1...4
Applicable services:
Name
Description
../datachanged/subscribe
Subsrscibe to notication
../datachanged/unsubsribe
Unsubscribe notication
../datachanged/getsubscriptioninfo
Show information about notications
Additionally, the user can use ( ) show all active subscriptions. Service: getsubscriberlist p. 110
>
Example: Subscribing to notications
61160
Task: The current values of the following parameters are to be sent regularly to a network server with
IP address 192.168.0.4:
cyclic input data of the IO-Link Devices an IO-Link port X02
Operating temperature of the IO-Link master.
Solution: Subscribe to the required data using the subscribe service.
The following options are additionally available:
via WebSockets (ws://): Example: Subscribing notications via WebSocket ( p. ) 62
via MQTT (mqtt://): Example: Conguring the MQTT command channel ( p. ) 65
Request:
{
"code":"request",
"cid":4711,
"adr":"/timer[1]/counter/datachanged/subscribe",
"data":
{
"callback":"http://192.168.0.4:80/temp",
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
59
"datatosend":[
"/iolinkmaster/port[2]/iolinkdevice/pdin",
"/processdatamaster/temperature"]
}
}
In addition, the time interval of the timer[1] must be set to a value between 500 ms and
2147483647 ms.
Request:
{
"code":"request",
"cid":4712,
"adr":"/timer[1]/interval/setdata",
"data":{"newvalue":500}
}
Response:
{
"cid":4712,
"code":200
}
Notication (JSON)
{
"code":"event",
"cid":4711,
"adr":"",
"data":{
"eventno":"6317",
"srcurl":"/timer[1]/counter/datachanged",
"payload":{
"/timer[1]/counter":{"code":200,"data":1},
"/processdatamaster/temperature":{"code":200,"data":39},
"/iolinkmaster/port[2]/iolinkdevice/pdin":{"code":200,"data":"03B0"}}}
}
>
Example: Changing a subscription
61161
Task: The existing subscription (Example: Subscribing to notications ( )) is to be changed. p. 58
Instead of the temperature of the IO-Link master, the operating voltage applied is to be transmitted.
Solution: Overwrite the existing subscription. For this purpose, the parameter values for "cid" and
"callback" in the request must be the same as those of the existing subscription.
Request:
{
"code":"request",
"cid":4711,
"adr":"/timer[1]/counter/datachanged/subscribe",
"data":{
"callback":"http://192.168.0.4:80/temp",
"datatosend":[
"/iolinkmaster/port[2]/iolinkdevice/pdin",
"/processdatamaster/voltage"]}
}
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
60
Example: Subscribing to notications in CSV format
61162
Task: Every 2 seconds, the current values of the following parameters are to be sent to a network
server with the IP address 192.168.0.4
cyclic IO-Link input data of the IO-Link device at port X02
Operating temperature of the IO-Link master.
The data should be transmitted in CSV format (comma separator).
Solution:
Use the subscribe service to subscribe to the required data and set the output format to "csv0".
Data in CSV format can only be sent via TCP protocol.
Request:
{
"cid": 1,
"adr":"/timer[1]/counter/datachanged/subscribe",
"code":"request",
"callback":"tcp://192.168.50.59:1883/topic",
"codec":"csv0",
"data":{
"datatosend":[
"/iolinkmaster/port[2]/iolinkdevice/pdin",
"/processdatamaster/temperature"]}
}
Set the interval of the timer to 2 seconds:
Request:
{
"code":"request",
"cid":4712,
"adr":"/timer[1]/interval/setdata",
"data":{"newvalue":2000}
}
The cyclically sent notication has the following structure:
/timer[1]/counter/datachanged,6317,200,1,200,39,200,03B0
>
Example: Unsubscribing from notications
61163
Task: The existing subscription (Example: Subscribing to notications ( )) is to be deleted. p. 58
Solution: Use the unsubscribe service to delete the subscription. For this purpose, the value of the
parameter "callback" in the request must be equal to the value of the existing subscription.
{
"code":"request",
"cid":4711,
"adr":"/timer[1]/counter/datachanged/unsubscribe",
"data":{
"callback":"http://192.168.0.4:80/temp"
}
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
61
Example: Checking subscriptions
61164
Task: Information about the existing subscription (Example: Subscribing to notications
( )Show p. 58 Example: Subscribing to notications ( )). p. 58
Solution: Use the service getsubscriptioninfo and the parameter values cid, "adr" and "callback" of the
existing subscription to retrieve the information.
Request:
{
"code":"request",
"cid":4711,
"adr":"/timer[1]/counter/datachanged/getsubscriptioninfo",
"data":{
"callback":"http://192.168.0.4:80/temp"}
}
Respons e:
{
"cid." 4711,
"data":{
"callback":"http://192.168.0.4:80/temp",
"datatosend":[
"/iolinkmaster/port[2]/iolinkdevice/productname",
"/iolinkmaster/port[2]/iolinkdevice/pdin",
"/processdatamaster/temperature"]},
"code":200
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
62
>
9.2.23 Using Web Socket
61165
The IoT Core supports communication via WebSocket protocol. With Web Sockets, the user can
establish a full-duplex communication channel via a TCP connection.
WebSockets can be used for the following services:
subscribe / unsubscribe
Maximum number of WebSocket connections: 8
Fail-safe WebSocket connections (wss://) are not supported.
To transmit notications via a WebSockets connectio n:
Establish the WebSocket connection (e.g. ) "ws://192.168.0.55:80/websocket"
Option 1: without parameter "callback”
make subscribe/unsubscribe request without parameter "callback".
> IoT-Core sends notications about existing WebSocket connections.
Option 2. with parameter "callback”
make subscribe/unsubscribe requests with parameter "callback" ("ws:///myTopic").
> IoT-Core sends notications about existing WebSocket connections to the topic . myTopic
>
Example: Subscribing notications via WebSocket
61166
Task: The current values of the following parameters are to be sent regularly to the data sink myTopic
via an existing WebSocket connection:
Product name of the IO-Link Devices an IO-Link port X02
cyclic input data of the IO-Link Devices an IO-Link port X02
Operating temperature of the IO-Link master.
Solution: Subscribe to the required data using the subscribe service.
Request:
{
"code":"request",
"cid":4711,
"adr":"/timer[1]/counter/datachanged/subscribe",
"data":{
"callback":"ws:///myTopic",
"datatosend":[
"/iolinkmaster/port[2]/iolinkdevice/productname",
"/iolinkmaster/port[2]/iolinkdevice/pdin",
"/processdatamaster/temperature"]}
}
If the notications are to be transmitted via the existing WebSocket connection, but without a special
data sink, the callback parameter is not required.
Request:
{
"code":"request",
"cid":4711,
"adr":"/timer[1]/counter/datachanged/subscribe",
"data":{
"datatosend":[
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
63
"/iolinkmaster/port[2]/iolinkdevice/productname",
"/iolinkmaster/port[2]/iolinkdevice/pdin",
"/processdatamaster/temperature"]}
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
64
>
9.2.24 MQTT support
61168
The IoT Core supports the MQTT protocol. The protocol allows an MQTT client to communicate with
the IoT Core via an MQTT broker to request and receive data. The IoT Core can publish data via the
MQTT connection.
>
Conguring the MQTT command channel
61169
To enable MQTT communication, the user needs to activate and congure an MQTT command
channel.
Substructure: connections/mqttConnection
Name
Description
Access
../type
Type of the connection (MQTT)
r
../status
Global MQTT status
r
../status/preset
Presetting of the MQTT status; Basic settings:
running
r
../MQTTSetup
Substructure for general MQTT settings
w
../MQTTSetup/QoS
Quality of Service of the MQTT communication
0: QoS Level 0 - PUBLISH (without
conrmation)
1: QoS Level 1 - PUBLISH > PUBREC
(one-time conrmation)
2: QoS Level 2 - PUBLISH > PUBREC >
PUBREL > PUBCOMP (double conrmation)
rw
../MQTTSetup/version
MQTT version
r
../mqttCmdChannel
Substructure of the MQTT command channel
w
../mqttCmdChannel/type
Type of the MQTT command channel
r
../mqttCmdChannel/status
Status of the MQTT command channel
r
../mqttCmdChannel/status/preset
Presetting of the MQTT status; Basic setting:
stopped
r
../mqttCmdChannel/mqttCmdChannelSetup
Structure for settings of the command channel
w
../mqttCmdChannel/mqttCmdChannelSetup/brokerIP
IP address of the MQTT broker
rw
../mqttCmdChannel/mqttCmdChannelSetup/brokerPort
Port number of the MQTT broker
rw
../mqttCmdChannel/mqttCmdChannelSetup/cmdTopic
Designation of the MQTT topic
rw
../mqttCmdChannel/mqttCmdChannelSetup/defaultReplyTopic
Standard response topic
rw
Applicable services:
Name
Description
../status/start
Enable MQTT
../status/stop
Deactivate MQTT
../status/reset
Reset MQTT
../mqttCmdChannel/status/start
Activate MQTT command channel
../mqttCmdChannel/status/stop
Deactivate MQTT command channel
../mqttCmdChannel/status/reset
Reset MQTT command channel
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
65
Notes on the states of an MQTT connection: Note: Connection states ( ) p. 65
To create an MQTT connection, perform the following steps in sequence:
Ensure that the MQTT broker can be reached and that the selected port of the MQTT broker is
enabled for data transmission.
Max. number of simultaneous MQTT connections: 10
Wildcards "+" and "#" in topics are not supported.
Activate MQTT command channel.
Set the IP address of the MQTT.
Set the port number of the MQTT broker.
Set topic.
Set standard response topic.
> The command channel is created with the selected properties.
> The user can publish on the topic with the IoT Core.
> MQTT clients can subscribe to the topic.
>
Note: Connection states
61170
The following status diagram shows the inuence of the services "start", "stop" and "reset" on the
status of an MQTT connection:
After the initialisation in the "init" state has been completed, the connection automatically changes to
the "running" state.
The connection automatically switches to the "error" state if at least one of the following events occurs:
no MQTT broker available
>
Example: Conguring the MQTT command channel
61171
Task: Conguring and activating the MQTT command channel (IP address MQTT broker:
192.168.82.100, port: 1883, topic: abc).
Solution:
Check whether MQTT broker can be reached and the port has been released.
Activate command channel
Request:
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
66
{
"code":"request",
"cid":4711,
"adr":"/connections/mqttConnection/MQTTSetup/mqttCmdChannel/status/start"
}
Set the IP address of the MQTT broker/server.
Request:
{
"code":"request",
"cid":4712,
"adr":"/connections/mqttConnection/mqttCmdChannel/mqttCmdChannelSetup/brokerIP/set
data"
"data":{"192.168.82.100"}
}
Set the port number of the MQTT broker/server.
Request:
{
"code":"request",
"cid":4713,
"adr":"/connections/mqttConnection/mqttCmdChannel/mqttCmdChannelSetup/brokerPort/s
etdata"
"data":{"1883"}
}
Set topic.
Request:
{
"code":"request",
"cid":4714,
"adr":"/connections/mqttConnection/mqttCmdChannel/mqttCmdChannelSetup/cmdTopic/set
data"
"data":{"abc"}
}
Set standard response topic.
Request:
{
"code":"request",
"cid":4715,
"adr":"/connections/mqttConnection/mqttCmdChannel/mqttCmdChannelSetup/defaultReply
Topic/setdata"
"data":{"xyz"}
}
Set the QoS.
Request:
{
"code":"request",
"cid":4716,
"adr":"/connections/mqttConnection/MQTTSetup/QoS/setdata",
"data":{"QoS2"}
}
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
67
Example: Publish the temperature to an MQTT broker
54687
Task: Publish the temperature of the IO-Link master to an MQTT broker (IP address MQTT broker:
192.168.82.100, port: 1883, topic: abc
Solution:
Request:
{
"code":"request",
"cid":-1,
"adr":"/timer[1]/counter/datachanged/subscribe",
"data":{
"callback":"mqtt://192.168.82.100:1883/abc",
"datatosend":["processdatamaster/temperature"}
}
Response:
{
"cid":-1,
"code":200
}
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
68
9.2.25 Using the IoT-Core Visualizer
Content
Managing notifications ............................................................................................................................ 69
Searching for elements in the device tree .............................................................................................. 71
Configuring IO-Link the master .............................................................................................................. 72
Reading and writing process data .......................................................................................................... 73
Updating the firmware ............................................................................................................................ 74
61173
The ifm-IoT Core Visualizer of the IO-Link master provides a graphical user interface for accessing
functions of the ifm-IoT Core.
To start the IoT Core Visualizer:
Start web browser.
Call the following address: http://ipaddress/web/subscribe
> Browser shows IoT Core Visualizer:
The navigation menu gives the user access to the following functions:
[Notification]: Creating and managing notifications (subscribe / unsubscribe)
[Elements]: Searching for elements in device description
[Parameter]: Configuring IO-Link master
[Processdata]: Reading and writing process data
[Update]: Updating the firmware of the IO-Link master
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
69
>
Managing notifications
61174
The menu page allows you to perform the following functions
Creating notifications
Showing active notificatio ns
Deleting notifications (single, all)
Requirements:
Iot-Core Visualizer has been started.
Click on [Notification].
> The menu page for managing notifications appears.
> The menu page shows all registered notifications in a table
>
Creating a new notification
61175
A wizard is used to register new notifications.
Requirements:
The [Notification] menu page is open.
Click on [+] on the right side of the table.
> The wizard for the creation of notifications appears.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
70
Use the wizard to enter the required notification parameters step by step.
> Created notification subscription is displayed in the table.
For cyclical notifications via timer[1] or timer[2], the user also needs to set the interval time of
the timer in question.
>
Deleting a notification
61176
Requirements:
The [Notification] menu page is open.
At least one notification is active.
Click on [x] in the column [Unsubscribe].
> The selected notification will be deleted (unsubscribe).
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
71
>
Searching for elements in the device tree
61177
The [Elements] menu page allows you to search the device description for elements with specific
properties (status, profile, name) and to output the results.
Requirements:
Iot-Core Visualizer has been started.
Click on [Elements].
> The input mask appears.
Enter the search criteria of the required item in the [identifier], [profile] and [type] boxes.
Click on [Search for ...].
> IoT-Core Visualizer searches device description for elements with selected search criteria.
> The result list shows all elements found.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
72
>
Configuring IO-Link the master
61178
The [Parameter] menu page allows you to configure the IO-Link master.
Available options:
Reading and writing individual parameters
Backup and restore the current configuration of the machine.
Requirements:
Iot-Core Visualizer has been started.
Click on [Parameter].
> The menu page shows the available parameters of the IO-Link master.
> Current parameter values are displayed.
> Editable parameters can be changed.
To change a parameter:
Navigate to the desired parameter in the device description.
Changing the parameter value
Click on the pencil icon to save the change on the IO-Link master.
> The changed parameter value is active.
ional: Repeat the procedure to change further parameter values. Opt
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
73
>
Reading and writing process data
61179
The menu page allows the process data of the IO-Link master and the connected IO-Link devices to
be read and written.
Requirements:
Iot-Core Visualizer has been started.
Click on [Processdata].
> Menu page shows the substructures of the device description that contain process data and
events.
> The current process values are displayed.
> Editable process data can be changed.
To change the value of a process date:
Navigate to the required process date in the device description.
Change the process value.
Click on the pencil icon to save the change on the IO-Link master.
> The changed process value is active.
Optional: Repeat the procedure to change further process values.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
74
>
Updating the firmware
61180
The [Update] menu page allows you to update the firmware of the IO-Link master:
Requirements:
Iot-Core Visualizer has been started.
Click on [Update].
> Menu page displays information about the current firmware version.
Click on [Load software file] and select a new firmware file (*.bin).
Click on [Update] to start the update process.
> The firmware of the IO-Link master will be updated.
> The area shows the progress bar.
> If the update process has been successful, the IO-Link master will restart automatically.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
75
9.3 PROFINET
Content
Install GSD Files ..................................................................................................................................... 76
Integrate the IO-Link master in the project ............................................................................................. 76
Configure the IO-Link master ................................................................................................................. 77
Configure IO-Link ports .......................................................................................................................... 78
Configure IO-Link devices ...................................................................................................................... 79
Read and write cyclic process data ........................................................................................................ 79
Read I&M datasets ................................................................................................................................. 80
Detect diagnostics and alarms .............................................................................................................. 80
34541
On the field bus side, the device can be configured with the following options:
PROFINET projection software STEP 7 (version 5.5 SP 4 or higher)
PROFINET projection software TIA portal
Further information about operation and functions of the PROFINET parameter setting
software:
Use the help function of the PROFINET projection software!
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
76
9.3.1 Install GSD Files
52478
ifm provides a GSD file to integrate the AL1301 in the PROFINET projection software. All parameters,
process data and their valid value ranges are defined in the GSD file. The user can download the GSD
file from the ifm website ( www.ifm.com).
To add the IO-Link master to the hardware catalogue of the PROFINET projection software:
Download the GSD file of the AL1301 from the ifm website.
Launch the PROFINET projection software.
Install the GSD file of the AL1301.
Once the GSD file is installed, the AL1301 is in the hardware catalogue in the following folder:
> [PROFINET IO] > [Addiotional Field Devices] > [IO] > [ifm electronic]
1
AL1301
2
IO-Link ports
3
PROFINET modules
>
9.3.2 Integrate the IO-Link master in the project
52479
The AL1301 can be integrated from the hardware catalogue into the project.
Create new project /open project
Create and configure PROFINET controller and coupling units.
Create and configure PROFINET connection.
Drag the [AL1301] node from the hardware catalogue and drop it on the PROFINET connection.
> The AL1301 is displayed as part of the PROFINET network.
To integrate the AL1301 in the network infrastructure, the fieldbus interface must be configured
correspondingly.
Double click on slot 0 to open the configuration of the AL1301.
Configure the Ethernet interface of the IO-Link master.
Drag the [4 Ports] node from the hardware catalogue and drop it on slot 1 of the IO-Link master.
Save the project.
The IO-Link master is integrated in the project and can be configured.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
77
>
9.3.3 Configure the IO-Link master
52480
You can access the configuration of the IO-Link master via slot 1.1 of the AL1301.
The parameter [Access Rights] determines which controller instance may have read and write access
to the data of the IO-Link master.
To set the parameters of the IO-Link master:
In the project: Double click on slot 1.1 of the AL1301.
Set parameters [Access Rights] as required ( ( Parameter of the IO-Link master → p. 90)).
Save the project.
If the parameter [Access Rights] = [PROFINET + IoT] in LR DEVICE and the PROFINET
projection software, the parameter values set in the PROFINET projection software will always
apply.
If the parameter [Access Rights] = [IoT only] in LR DEVICE, set the parameter [Access Rights]
= [Keep settings] in the projection software.
Changes of the parameter [Access Rights] will only be effective after restarting the IO-Link
master ( Firmware: Reboot the device ( )). → p. 31
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
78
>
9.3.4 Configure IO-Link ports
52481
You can access the configuration of the IO-Link ports via the slots 1.2 ... 1.5 of the AL1301. The
following assignment applies
Slot
IO-Link port of the AL1301
1.2
Port X01
1.3
Port X02
...
...
1.5
Port X04
The available PROFINET modules are defined in the GSD file ( PROFINET modules ( )). A → p. 93
PROFINET module determines the following properties of an IO-Link port:
Operating mode (IO-Link, DI, DO, deactivated)
Type and length of the process data
Optional data (fail-safe values, device validation, data storage, cycle time, events)
The following table shows the available parameters depending on the selected operating mode:
Operating mode of the IO-Link
ports
Available parameters
Fail-safe
mode
Pattern
Value
Validation /
Data
storage
Vendor
ID (VID)
Device ID
Port cycle
time
IO-Link
events
DI: digital input
--
--
--
--
--
--
--
DO: digital output
X
--
--
--
--
--
--
IO-Link: input
--
--
X
X
X
X
X
IO-Link: output
X
X
X
X
X
X
X
IO-Link: input and output
X
X
X
X
X
X
X
-- = not available
X = available
To configure an IO-Link port of the AL1301:
Drag the required PROFINET module from the hardware catalogue and drop it on the slot of the IO-Link port.
Double click on the slot of the IO-Link port
Set the parameters as required ( Parameters of the IO-Link ports ( → p. 91)).
Configure unused IO-Link ports with PROFINET module "Deactivated".
Repeat the steps to configure further IO-Link ports.
Save the project.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
79
9.3.5 Configure IO-Link devices
52482
The AL1301 supports the configuration of the connected IO-Link devices via the PROFINET
application. The configurable parameters depend on the IO-Link device that is used.
Configurable parameters of the IO-Link devices: IO Device Description (IODD) of the
IO-Link Devices
The following options are available:
Function block
Description
Notes
IO_LINK_DEVICE
Acyclic access to the parameters of an
IO-Link device
Input parameter:
CAP: Access point for function
AL1301: 0xB 400
PORT: Slot/sub-slot of the IO-Link interface of the
connected IO-Link device
Port X01: 1
Port X02: 2
...
Port X04: 4
IOL_INDEX and IOL_SUBINDEX: Index and
sub-index of the parameter (depends on the IO-Link
device: IO Device Description (IODD))
IOL_CALL
Acyclic access to the parameters of an
IO-Link devices (obsolete)
→ IO_LINK_DEVICE
>
9.3.6 Read and write cyclic process data
52483
While the IO-Link ports are being configured, IEC addresses are generated automatically for inputs
and outputs as well as the PQI byte. To enable access to the cyclic process data in the application, the
user must couple the IEC addresses with symbolic variables. This can be done in global lists of
variables (STEP 7: [Symbols]; TIA portal: [PLC tags]).
Take the following actions in global lists of variables of the PROFINET controller:
Create a symbolic name and select the data type
Assign an IEC address to the symbolic name
Save the project.
Using the symbolic name, the user can read the inputs and write the outputs from the application.
To check the validity of the cyclic process data, evaluate the PQI byte ( PQI (Port
Qualifier Information) ( p. 94)).
Even if the fieldbus connection is interrupted, the PQI byte indicates that the process data is
valid. This may have an unintended impact on the control process.
Take suitable measures to detect an interruption of the fieldbus connection.
>
Read additional digital input
52549
IO-Link ports X01...X04 have a additional digital input (pin 2). The current value is mapped to the PQI
byte ( PQI (Port Qualifier Information) ( → p. 94)).
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
80
9.3.7 Read I&M datasets
52484
I&M0 provide the user with devi -specific basic information. This ensures reliable identification of the ce
device, the device's hardware and software components as well as the manufacturer.
The datasets I&M1 to 3 offer the programmer the possibility to store project-specific information on the
device.
The programmer can access the I&M0 datasets of the slots 0 and 1 in the PROFINET projection
software by means of the following functions:
Symbol
Description
Notes
GET_IM_DATA
Function block for reading the I&M datasets of a device
GET_IM_DATA only supports the reading of the I&M0
dataset
Input parameters:
IM_TYPE = 0
RDREC
Function block for acyclic reading of datasets
Input parameters:
I&M0: Index = 0xAFF0
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3
WRREC
Function block for acyclic writing of datasets
Observe access rights on datasets!
Input parameters:
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3
>
9.3.8 Detect diagnostics and alarms
52485
Available alarms and diagnostic messages: Diagnostic and alarms ( ) → p. 96
Symbol
Operational block
Description
I/O_FLT1
OB82
Diagnostic alarms
I/O_FLT2
OB83
Connect/disconnect alarms
RACK_FLT
OB86
Module rack failure
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
81
10 Operation
Content
Using web-based management .............................................................................................................. 81
34061
>
10.1 Using web-based management
61181
The device has an integrated web server The web server generates a website with the following data:
Status information of the ports
Access to product page of connected IO-Link devices (only ifm devices)
Diagnostic information of the device
Version information of the installed firmware components
To access the web interface of the IO-Link master:
Connect the IO-Link master to the laptop / PC via the IoT port.
Optional: Check the IP settings of the IoT interface.
Start web browser.
In the address field of the web browser, enter the IP address of the IoT interface and confirm with
[ENTER].
> The web browser shows the website with the status and diagnostic information of the device.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
82
11 Maintenance, repair and disposal
Content
Cleaning process .................................................................................................................................... 82
Updating the firmware ............................................................................................................................ 82
Replacing IO-Link device ........................................................................................................................ 82
51990
The operation of the unit is maintenance-free.
Dispose of the unit in an environmentally friendly way in accordance with the applicable national
regulations when it is no longer used.
>
11.1 Cleaning process
51991
Clean the surface of the unit when necessary.
Do not use any caustic cleaning agents for this!
In case of severe soiling, use a damp cloth.
Do not use any caustic cleaning agents for this!
>
11.2 Updating the firmware
61183
The firmware of the IO-Link master can be updated via the IoT Core Visualizer → Updating the
firmware ( → p. 74, → p. 82)).
>
11.3 Replacing IO-Link device
34182
To replace an IO-Link device:
Requirement:
> New IO-Link device is with factory settings.
> New -Link device supports IO-Link standard 1.1 or higher. IO
1 Set data storage
Set the following parameters of the IO-Link port
Set Validation and Data Storage to [Type compatible V1.1 device with Restore] or [Type compatible V1.1. device
with Backup + Restore]
Set correct values to [Vendor ID] and [Device ID] according to properties of the IO-Link device.
Save changes.
2 Replace IO-Link device
Disconnect old IO-Link device from IO-Link master.
Connect new IO-Link device with the same IO-Link port of the AL1301.
> -Link master copies parameter values from the data memory to the new IO-Link device. IO
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
83
12 Factory settings
34509
In the factory settings, the device has the following parameter settings:
Parameter
Factory setting
[IP address] (PROFINET)
0.0.0.0
[Subnet mask] (PROFINET)
0.0.0.0
[IP gateway address] (PROFINET)
0.0.0.0
[IP address] (IoT interface)
169.254.X.X
[Subnet mask] (IoT interface)
255.255.0.0
[IP gateway address] (IoT interface)
0.0.0.0
[PROFINET name]
blank
Data memory (Data Storage)
empty
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
84
13 Accessories
33870
List of accessories of AL1301: > Product page > Accessories www.ifm.com
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
85
14 Appendix
Content
Technical data ........................................................................................................................................ 86
PROFINET .............................................................................................................................................90
ifm IoT Core ............................................................................................................................................ 97
33879
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
86
14.1 Technical data
Content
Application .............................................................................................................................................. 86
Electrical data ......................................................................................................................................... 86
Inputs / outputs ....................................................................................................................................... 86
Inputs ...................................................................................................................................................... 87
Outputs ................................................................................................................................................... 87
Interfaces ................................................................................................................................................ 87
Operating conditions ............................................................................................................................... 88
Approvals / tests ..................................................................................................................................... 88
Mechanical data .................................................................................................................................... 88
Electrical connection ............................................................................................................................... 89
34188
>
14.1.1 Application
33878
Application
Application
Hygienic systems; I/O modules for field applications
Daisy-chain function
Fieldbus interface
>
14.1.2 Electrical data
33808
Electrical data
Operating voltage [V]
20...28 DC; (US; to SELV/PELV)
Current Consumption [mA]
300...3900; (US)
Protection class
III
Sensor supply US
Max. current load total [A]
3.6
>
14.1.3 Inputs / outputs
34068
Inputs / outputs
Total number of inputs and outputs
8; (configurable)
Number of Inputs and Outputs
Number of digital inputs: 8; Number of digital outputs: 4
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
87
>
14.1.4 Inputs
34069
Inputs
Number of digital inputs
8; (IO-Link Port Class A: 4 x 2)
Switching level high [V]
11...28
Switching level low [V]
0...5
Digital inputs protected against short circuits
yes
>
14.1.5 Outputs
34053
Outputs
Number of digital outputs
4; (IO-Link Port Class A: 4 x 1)
Max. current load per output [mA]
300
Short-circuit protection
yes
>
14.1.6 Interfaces
34389
Interfaces
Communication interface
Ethernet; IO-Link
Communication interface
IO-Link; TCP/IP; PROFINET IO
Ethernet
Transmission standard
10Base-T; 100Base- TX
Transmission rate [MBit/s]
10; 100
Protocol
TCP/IP; PROFINET IO
Factory settings
IP address: 0.0.0.0
Subnet mask: 0.0.0.0
Gateway IP address: 0.0.0.0
MAC address: see type label
IO-Link master
Type of transmission
COM 1 / COM 2 / COM 3
IO-Link revision
V1.1
Number of ports Class A
4
IoT interface
Transmission standard
10Base-T; 100Base- TX
Transmission rate [Mbits/s]
10; 100
Protocol
DCP, DCHP, Auto IP
Factory settings
IP address: 169.254.X.X
Subnet mask: 255.255.0.0
Gateway IP address: 0.0.0.0
address: see type label MAC
>
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
88
14.1.7 Operating conditions
34062
Operating conditions
Applications
Indoor use
Ambient temperature [°C]
- 25...60
Storage temperature [°C]
- 25...85
Max. perm. relative air humidity [%]
90
Max. height above sea level [m]
2000
Protection rating
IP 65; IP 66; IP 67; IP 69K; (operation with stainless steel protective caps: IP
69K)
Pollution Degree
2
>
14.1.8 Approvals / tests
33877
Approval / tests
EMC
-6-2 EN 61000
EN 61000-6-4
MTTF [Years]
90
>
14.1.9 Mechanical data
34050
Mechanical data
Weight [g]
312
Materials
Housing: PA grey; socket: 1.4404 (stainless steel / 316L)
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
89
>
14.1.10 Electrical connection
33806
Voltage supply IN X31
Plug and socket connection
M12
Wiring
1:
+ V DC (US) 24
2:
-
3:
GND (US)
4:
-
Ethernet IN / OUT X21, X22
Plug and socket connection
M12
Wiring
1:
TX +
2:
RX +
3:
TX -
4:
RX -
5:
-
IoT X23
Plug and socket connection
M12
Wiring
1:
TX +
2:
RX +
3:
TX -
4:
RX -
5:
-
Process connection -Link ports Class A X01...X04 IO
Plug and socket connection
M12
Wiring
1:
Sensor supply (US) L+
2:
DI
3:
Sensor supply (US) L-
4:
C/Q -Link IO
5:
-
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
90
14.2 PROFINET
Content
Parameter data ....................................................................................................................................... 90
Cyclic data .............................................................................................................................................. 93
Acyclic data ............................................................................................................................................95
33674
>
14.2.1 Parameter data
34551
Slot
Sub-slot
Name
Description
1
1
Master
Parameter data of the IO-Link master ( Parameter of the IO-Link master
( → p. 90))
2
Port X01
Parameter data of the IO-Link ports ( Parameters of the IO-Link ports
( ) → p. 91
Fieldbus modules ( ( PROFINET modules → p. 93))
3
Port X02
4
Port X03
5
Port X04
>
Parameter of the IO-Link master
34552
Parameter
Description
Possible values
[Access Rights]
The access rights to the
parameter data, process data and
events/diagnostic messages of
the IO-Link master and the
connected IO-Link devices
PROFINET + IoT
PROFINET and LR DEVICE have read
and write access rights to parameters
and process data
PROFINET and LR DEVICE have read
access rights to events/alarms
PROFINET + IoT (ro)
PROFINET has read and write access
rights to parameters and process data
PROFINET has read access rights to
events/alarms
LR DEVICE only has read access
rights to parameters, process data and
events/alarms
PROFINET only
PROFINET has read and write access
rights to parameters and process data
PROFINET has read access rights to
events/alarms
LR DEVICE has no access rights
(parameters, process data,
events/alarms, web interface, firmware
update)
keep setting
keeps settings
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
91
>
Parameters of the IO-Link ports
34528
Parameter
Description
Possible values
[Fail-safe mode]
Behaviour of outputs of the port in
case the PROFINET connection is
interrupted (only valid for operating
modes "DO" and "IO-Link")
No Fail Safe
deactivated
Fail Safe Reset Value
reset to default values
Fail Safe Old Value
maintain the most recent valid process
value
Fail Safe with Pattern
set user-defined values
[Pattern Value]*
required values for the process
data in case the connection is
interrup ted
(as hexadecimal value)
Pattern depends on the size of the
selected PROFINET module
Per byte:
0x00 ... 0xFF
[Port cycle time]
Cycle time of the data transmission at
the IO-Link port
as fast as possible
The device automatically sets the
fastest possible cycle time
2.0 ms
...
128.0 ms
2 milliseconds
...
128 milliseconds
[Validation / Data
Storage]
Supported IO-Link standard and
behaviour of the AL1301 when a new
IO-Link device is connected to the
IO-Link port
no check and clear
no verification of the vendor ID and
device ID
no data storage
Type compatible V1.0
device
-Link device is compatible with IO
the V1.0 -Link standard IO
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
no data storage
Type compatible V1.1
device
-Link device is compatible with IO
the V1.1 IO-Link standard
Verification whether it is -Link an IO
device of the same type (validation
via vendor ID and device ID)
no data storage
Type compatible V1.1
device with Backup +
Restore
-Link device is compatible with IO
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
The IO-Link master saves the
parameter values of the connected
IO-Link device; modifications of
the parameter values are also
stored ( observe the note!)
When connecting an IO-Link device
with factory settings, the parameter
values stored in the IO-Link master
are restored automatically on the
IO-Link device.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
92
Parameter
Description
Possible values
Type compatible V1.1
device with Restore
-Link device is compatible witIO h
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
The IO-Link master stores the
parameter values of the connected
IO-Link device once if the data
memory of the AL1301 is empty.
When connecting an IO-Link device
with factory settings, the parameter
values stored in the IO-Link master
are restored automatically on the
IO-Link device.
[Vendor ID (VID)]
ID of the manufacturer that is to be
validated
0 ... 65535
ID of the manufacturer of the IO-Link
device (ifm electronic: 310)
[Device ID (DID)]
ID of the IO-Link device that is to be
validated
0 ... 16777215
ID of the IO-Link device
[IO-Link Events]
Enable / disable the transmission of
IO-Link events
Diabled
IO-Link won't be transmitted
Enabled
IO-Link events will be transmitted
* ... settings are only valid if [Fail Safe Mode] = Fail Safe with Pattern
If the parameter values of an IO-Link device are changed with IO_LINK_DEVICE, the backup
mechanism remains ineffective. The changed parameter values are not stored on the IO-Link
master.
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
93
14.2.2 Cyclic data
Content
PROFINET modules ............................................................................................................................... 93
PQI (Port Qualifier Information) .............................................................................................................. 94
33814
>
PROFINET modules
34539
Module
Description
IO-Link 32I / 32 O + PQI
IO-Link activated
32 bytes input and output data and PQI
IO-Link 16I / 16O + PQI
16 bytes input and output data and PQI
IO-Link 8I / 8O + PQI
8 bytes input and output data and PQI
IO-Link 4I / 4O + PQI
4 bytes input and output data and PQI
IO-Link 2I / 2O + PQI
2 bytes input and output data and PQI
IO-Link 1I /1O + PQI
1 byte input and output data and PQI
IO-Link 1I /15O + PQI
1 byte input data and 15 bytes output data and PQI
IO-Link 32I + PQI
32 bytes input data and PQI
IO-Link 16I + PQI
16 bytes input data and PQI
IO-Link 8I + PQI
8 bytes input data and PQI
IO-Link 4I + PQI
4 bytes input data and PQI
IO-Link 2I + PQI
2 bytes input data and PQI
IO-Link 1I + PQI
1 byte input data and PQI
IO-Link 32O + P QI
32 bytes output data and PQI
IO-Link 16O + PQI
16 bytes output data and PQI
IO-Link 8O + PQI
8 bytes output data and PQI
IO-Link 4O + PQI
4 bytes output data and PQI
IO-Link 2O + PQI
2 bytes output data and PQI
IO-Link 1O + PQI
1 byte output data and PQI
DI + PQI
IO-Link deactivated
Digital input and PQI
DO + PQI
Digital output and PQI
Disabled
deactivated
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
94
>
PQI (Port Qualier Information)
34530
Port Qualier Information (PQI) contains diagnostic information about the IO-Link port. In addition to
the process data, the IO-Link master sends the PQI to the PROFINET controller.
Bit
7
6
5
4
3
2
1
0
PQ
DE
DA
--
--
--
DI2
DI4
Legend:
[DI4]
Signal status of the digital input on pin 4 (DI)
FALSE
OFF
TRUE
ON
[DI2]
Signal status of the digital input on pin 2 (if used)
FALSE
OFF
TRUE
ON
[DA]
Device Available: shows if the IO-Link device has been recognised and if the
device is in the "preoperate" or in the "operate" state
FALSE
no device
TRUE
device detected
[DE]
Device Error: shows if an error or a warning occurred; Note: The user needs to
determine the cause of the fault separately via acyclic services.
FALSE
no error
TRUE
error detected
[PQ]
Port Qualier: shows if IO data is valid
FALSE
invalid
TRUE
valid
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
95
14.2.3 Acyclic data
Content
I&M datasets ........................................................................................................................................... 95
Diagnostic and alarms ............................................................................................................................ 96
33868
>
I&M datasets
34555
The AL1301 supports the following I&M datasets (I&M = Identication & Maintenance):
>
I&M0 (Slot 0)
34545
Variable
Description
Access
Size
Vendor ID
IO-Link ID of the manufacturer
r
2
OrderID
Order number of the device (ASCII)
r
20
Serial number
Serial number of the device (ASCII)
r
16
Hardware revision
Hardware revision of the device
r
2
Software revision prex
Prex of the software revision of the device (V, R, P, U or T)
r
1
Software Revision
Software revision (numbers, e.g. x y z in "Vx.y.z")
r
3
Revision Counter
Revision counter; is incremented with each parameter change
r
2
Prole ID
ID of sub-module prole (Slot 0: 0x0000)
r
2
Prole Specic Type
additional value for prole ID; 0, if not used
r
2
IMVersion
I&M version (default value: 0x0101)
r
2
IMSupported
Suported I&M datasets (0x1110 for I&M1- 3)
r
2
r ... only read
>
I&M1 (Slot 0)
34543
Variable
Description
Access
Size
TagFunction of submodule
function of the device (ASCII)
r/w
32
TagLocation of submodule
Location of the device in the plant (ASCII)
r/w
22
r/w ... read and write
>
I&M2 (Slot 0)
34544
Variable
Description
Access
Size
Installation_Date
Installation date of the device (ASCII)
r/w
16
reserved
r/w
38
r/w ... read and write
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
96
>
I&M3 (Slot 0)
34550
Variable
Description
Access
Size
Descriptor
Description of the device (ASCII)
r/w
54
r/w ... read and write
>
I&M0 (Slot 1)
34542
Variable
Description
Access
Size
Vendor ID
IO-Link ID of the manufacturer
r
2
OrderID
Order number of the device (ASCII)
r
20
Serial number
Serial number of the device (ASCII)
r
16
Hardware revision
Hardware revision of the device
r
2
Software revision prex
Prex of the software revision of the device (V, R, P, U or T)
r
1
Software revision
Software revision (numbers e.g. x y z in "Vx.y.z")
r
3
Revision counter
Revision counter; is incremented with each parameter change
r
2
Prole ID
ID of the sub-module prole (Slot 1: 0x4E01 = IOLink)
r
2
Prole Specic Type
additional value for prole ID; 0, if not used
r
2
IMVersion
I&M version (default value: 0x0101)
r
2
IMSupported
Supported I&M datasets (0x0E for I&M1- 3)
r
2
r ... read only
>
Diagnostic and alarms
34533
ECD
code
Name
Description
Type
0x02
EVNT_CODE_M_PDU_CHECK
Receive frame with CRC error
Alarm
0x1B
EVNT_CODE_S_RETRY
Repetitions detected
Alarm
0x1E
EVNT_CODE_P_SHORT
Short circuit on C/Q cable detected
Diagnostics
0x1F
EVNT_CODE_P_SENSOR
Error in the sensor supply
Diagnostics
0x20
EVNT_CODE_P_ACTOR
Error in the actuator supply
Diagnostics
0x21
EVNT_CODE_P_POWER
Error in the power supply of the IO-Link master
Diagnostics
0x28
EVNT_CODE_DSREADY_NOACTION
Data storage completed, but no action, since CRC was
correct
Alarm
0x29
DS_FAULT_IDENT
Sensor does not match the content of the data memory
Alarm
0x2A
DS_FAULT_SIZE
Sensor parameters too large for data memory
Alarm
0x2B
DS_FAULT_UPLOAD
Error during data memory transmission from the sensor
Alarm
0x2C
DS_FAULT_DOWNLOAD
Error during data memory transmission to the sensor
Alarm
0x2F
DS_FAULT_DEVICE_LOCKED
Error during data storage because the device is blocked
Alarm
0x32
EVNT_CODES_DSREADY_DOWNLOAD
Parameter transmission to the sensor nished
Alarm
0x33
EVNT_CODE_DSREADY_UPLOAD
Parameter transmission from the sensor nished
Diagnostics
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
97
14.3 ifm IoT Core
Content
Overview: IoT prole ............................................................................................................................... 98
Overview: IoT types ..............................................................................................................................105
Overview: IoT services .........................................................................................................................106
33803
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 6 9K
98
14.3.1 Overview: IoT profile
Content
Prole: blob ............................................................................................................................................. 98
Prole: deviceinfo ................................................................................................................................... 99
Prole: devicetag .................................................................................................................................... 99
Prole: iolinkdevice_full ........................................................................................................................100
Prole: iolinkmaster ..............................................................................................................................100
Prole: mqttCmdChannel .....................................................................................................................101
Prole: mqttCmdChannelSetup ............................................................................................................101
Prole: mqttConnection ........................................................................................................................101
Prole: mqttSetup ................................................................................................................................. 102
Prole: network .....................................................................................................................................102
Prole: parameter ................................................................................................................................. 103
Prole: processdata ..............................................................................................................................103
Prole: runcontrol ................................................................................................................................. 103
Prole: service ......................................................................................................................................103
Prole: software ....................................................................................................................................103
Prole: software/uploadedablesoftware ...............................................................................................104
Prole: Timer ........................................................................................................................................104
34054
>
Prole: blob
52264
Element (identier)
Properties
Mandatory
Comment
blobname
type = data
proles = blob
labels element as device information
../size
type = data
mandatory
../chunksize
type = data
mandatory
../setblobdata
type = service
optional
../getblobdata
type = service
optional
../start_stream_set
type = service
optional
../stream_set
type = service
optional
../clear
type = service
optional
../getcrc
type = service
optional
../getmd5
type = service
optional
../getdata
type = service
optional
../setdata
type = service
optional
IO-Link master with PROFINET interface DataLine 4 ports IP 65 / IP 66 / IP 67 / IP 69K
99
>
Prole: deviceinfo
34207
Element (identier)
Properties
mandatory
Comments
deviceinfo
type = structure
prole = deviceinfo
characterises the element as device
information
../devicename
type = data
optional
../devicefamiliy
type = data
optional
../devicevariant
type = data
optional
../devicesymbol
type = data
optional
../deviceicon
type = data
optional
../serialnumber
type = data
mandatory
../productid
type = data
optional
../productname
type = data
optional
../productcode
type = data
mandatory
../producttext
type = data
optional
../ordernumber
type = data
optional
../productiondate
type = data
optional
../productioncode
type = data
optional
../hwrevision
type = data
mandatory
../swrevision
type = data
mandatory
../bootloaderrevision
type = data
optional
../vendor
type = data
optional
../vendortext
type = data
optional
../vendorurl
type = data
optional
../vendorlogo
type = data
optional
../productwebsite
type = data
optional
../supportcontact
type = data
optional
../icon
type = data
optional
../image
type = data
optional
../standards
type = data
optional
>
Prole: devicetag
34206
Element (identier)
Properties
mandatory
Comments
devicetag
type = structure
prole = devicetag
../applicationtag
type = data
mandatory
../applicationgroup
type = data
optional
../machinecode
type = data
optional
../tenant
type = data
optional
>


Produkt Specifikationer

Mærke: IFM
Kategori: Ikke kategoriseret
Model: AL1301

Har du brug for hjælp?

Hvis du har brug for hjælp til IFM AL1301 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret IFM Manualer

IFM

IFM DW3003 Manual

9 April 2025
IFM

IFM IG6084 Manual

13 Marts 2025
IFM

IFM PV2102 Manual

10 Marts 2025
IFM

IFM OVP812 Manual

25 Januar 2025
IFM

IFM AE3400 Manual

25 Januar 2025
IFM

IFM DTE932 Manual

25 Januar 2025
IFM

IFM DTE931 Manual

25 Januar 2025
IFM

IFM DTE934 Manual

25 Januar 2025
IFM

IFM EVF729 Manual

25 Januar 2025
IFM

IFM EVT728 Manual

25 Januar 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer