Intermatic BR1-28C1Q5WH-BI Manual

Intermatic Ikke kategoriseret BR1-28C1Q5WH-BI

Læs nedenfor 📖 manual på dansk for Intermatic BR1-28C1Q5WH-BI (2 sider) i kategorien Ikke kategoriseret. Denne guide var nyttig for 2 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
SP SPL... SPH Setpoint (value to be maintained in the room) (0°C).
C-H REF; HEA Refrigerating (REF) or Heating (HEA) control mode .(REF)
HY0 1...1Thermostat OFF -> ON differential .(3°C)
HY1 0...1Thermostat ON -> OFF differential .(0°C)
CRT 0...30min Compressor rest time. The output is switched on again after CRT minutes have elapsed since the previous switchover. We
recommend to set CRT=03 with HY0<2.0° .(1)
CT1 0...30min
Compressor/Heater output run when probe T1 is faulty. With CT1=0 the output will always remain OFF
(3)
.
CT2 0...30min Compressor/Heater output stop when probe T1 is faulty. With CT2=0 and CT1>0 the output will always be ON.
Example: CT1=4, CT2= 6: In case of probe T1 failure, the compressor will cycle 4 minutes ON and 6 minutes OFF
(6)
.
DFM NON;
TIM;
FRO;
RTC
Defrost start mode (NON)
NON : defrost function is disabled (the following parameter will be FCM).
TIM : regular time defrost.
FRO : the defrost time count is only increased when the conditions occur for frost to form on the evaporator (optimised
time increase). If the evaporator works at 0°C, defrost frequency depends on the thermal load and climatic conditions. With
setpoints much lower than 0°C, defrost frequency mainly depends on the refrigerator operating time.
RTC : the defrost time is scheduled by parameters DH1, DH2, ...DH6.
DFT 0...99 hours Time interval among defrosts. When this time has elapsed since the last defrost, a new defrost cycle is started.
For example, with =TIM and =06, a defrost will take place every 6 hours .DFM DFT (06)
DFB NO/YES Defrost timer backup. With DFB=YES, after a power interruption, the timer resumes the count from where it was left off with
±30 min. approximation. With DFB=NO, after a power interruption, the defrost timer will re-start to count from zero ( .NO)
DH1
...
DH6
HH.M Scheduled time for defrost 1 to 6. HH hours from midnight, M tens of minutes. Accepted values go from 00.0 to 23.5. After
“23.5” the value is “---” that means “skipped defrost”. Example: DH1=8.3 means 8.30 AM .(24.0)
DLI -50...110° Defrost end temperature .(10°C)
DTO 1...120min Maximum defrost duration .(30°C)
DTY OFF;
ELE;
GAS
Defrost type .(ELE)
OFF : off cycle defrost (Compressor and Heater OFF).
ELE : electric defrost (Compressor OFF and Heater ON).
GAS : hot gas defrost (Compressor and Heater ON).
DSO OFF;
LO;
HI
Defrost start - thermostat cycle synchronization .(OFF)
OFF : none. The defrost will occur without delay.
LO : defrost start will be postponed to compressor cut-out (SOD = max delay).
HI : defrost start will be postoponed to compressor cut-in (SOD = max delay).
SOD 0...30 min Timeout for defrost start - thermostat cycle synchronization. If 0, defrost will start immediately .(5)
DPD 0...240sec Evaporator pump down. At the beginning of defrost, defrost outputs (determined by DTY) are OFF for DPD seconds .(0)
DRN 0...30min Pause after defrost (evaporator drain down time) .(3)
DDM RT;
LT;
SP;
DEF
Defrost display mode. During defrost the display will show: (DEF)
RT : the real temperature;
LT : the last temperature before defrost;
SP : the current setpoint value;
DEF : “dEF”.
DDY 0...60min Display delay. The display shows the information selected with parameter DDM during defrost and for DDY minutes after
defrost termination (10).
FID NO/YES Fans active during defrost .(NO)
FDD -50...110° Evaporator fan re-start temperature after defrost .(-5°C)
FTO 0...120min Maximum evaporator fan stop after defrost . (0)
FCM NON;
TMP;
TIM
Fan mode during thermostatic control . (NON)
NON : The fans remain ON all the time;
TMP : Temperature-based control. The fans are ON when the compressor is ON. When the compressor is turned OFF, the
fans remain ON as long as the temperature difference Te-Ta is greater than FDT. The fans are turned ON again with FDH
differential. (Te = Evaporator temperature, Ta = Air
temperature);
TIM : Timed-based control. The fans are ON when
the compressor is ON. When the compressor is
OFF, the fans switch ON and OFF according to
parameteres FT1, FT2, FT3 (See Fig.2).
FDT -12...0°
Evaporator-Air temperature difference for the fans to turn OFF after the compressor has stopped
(-2°C)
.
FDH 1...12° Temperature differential for fan re-start .(C)
Example: FDT = -1, FDH=3. In this case, after the compressor has stopped, the fans are OFF when Te > Ta - 1 (FDT),
whereas the fans are ON when Te < Ta - 4 (FDT-FDH).
FT1 0...180sec Fan stop delay after compressor/heater stop .(30)
FT2 0...30min Timed fan stop. With FT2=0 the fans remain on all the time .(3)
FT3 0...30min Timed fan run. With FT3=0, and FT2 > 0, the fans remain off all the time . (1)
ATM NON;
ABS;
REL
Alarm threshold management .(NON)
NON : all temperature alarms are inhibited (the following parameter will be ACC).
ABS : the values programmed in ALA and AHA represent the real alarm thresholds.
REL : the alarm threshold is obtained by the sum of setpoint, thermostat differential and ALR/AHR.
ALA -50... 110° Low temperature alarm threshold . (-50°C)
AHA -50... 110° High temperature alarm threshold .(120°C)
ALR -12... Low temperature alarm differential. With ALR=0 the low temperature alarm is excluded .(C)
AHR 0... 1 High temperature alarm differential. With AHR=0 the high temperature alarm is excluded .(0°C)
ATI T1; T2; T3 Probe used for temperature alarm detection .(T1)
ATD 0... 120min Delay before alarm temperature warning .(60)
ACC 0...52
weeks
Condenser periodic cleaning. When the compressor operation time, expressed in weeks, matches the ACC value
programmed, “CLashes in the display. With ACC=0 the condenser cleaning warning is disabled and CND disappears from
Info Menu .(0)
IISM NON;
MAN;
ECO;
DI;
RTC
Switchover mode to second parameter set .(NON)
NON : inhibition to use the second parameter group (the following parameter will be SB).
MAN : button switches the two parameter groups over.
ECO : automatic switchover to the second parameter group, when ECO conditions are detected.
DI : switchover to the second parameter group when DIx input is on.
RTC : the second parameter group is activated at STT time and deactivated at EDT time.
IISL -50... IISH Minimum limit for IISP setting .(-25°C)
IISH IISL... 110° Maximum limit for IISP setting .(25°C)
IISP IISL... IISH Setpoint in mode 2.
IIH0 1... 10° Thermostat OFF->ON differential in mode 2 . (5°C)
IIH1 0... 10° Thermostat ON->OFF differential in mode 2 .(4°C)
IIDF 0...99 hours Time interval among defrosts in mode 2 .(6)
IIFC NON;TMP; TIM Fan control in mode 2. See FCM .(NON)
ECS 1...5 Controller sensitivity for the automatic switchover from Group I to Group II (1=minimum, 5=maximum) (3).
EPT 0...240 min Eco pull-down time. Only with IISM=ECO. Group I parameters are used in regulation for at least EPT minutes. See Fig.3
(30).
SB NO/YES Stand-by button enabling (YES).
OFF
ON
COMPR.
ON
COMPR.
ON
COMPR. OFF
FT1 FT2 FT3 FT3FT2
Fig.2 Time-optimised fan control (FCM=TIM)
DSM NON;
ALR;
STP
Door switch input mode: (NON)
NON : door switch inhibited
ALR : when DIx=DOR and the digital input is on, an alarm is generated after DAD minutes
STP : when DIx=DOR and the digital input is on, in addition to the alarm, the fans are immediately stopped and the
compressor is stopped after CSD minutes.
DAD 0...30 min Delay before door open alarm warning .(5)
CSD 0...30 min
NO
Compressor/heater stop delay after door has been opened. If CSD=NO compressor/heater never stops due to the door
opening .(1)
D1O NON;
DOR;
ALR;
IISM;
RDS
DI1 digital input operation . (NON)
NON : digital input 1 not active.
DOR : door input.
ALR: when the input is on, an alarm is generated (if AHM=STP, the compressor is stopped and the defrosts are suspended).
IISM : when the input is on, the controller will use group II parameters.
RDS : when the input is on, a defrost is started (remote control).
D1A OPN; CLS. DI1 digital input activation .(OPN)
OPN : on open
CLS : on close
D2O See D1O DI2 digital input operation. See D1O .(NON)
D2A OPN; CLS. DI2 digital input activation. See D1A .(OPN)
D3O NON;
...
RDS;
DSY.
DI3 digital input operation (NON)
NON RDS ... : See D1O.
DSY : defrost synchronization. The controllers will all start and end defrost together. The first controller in defrost will get
defrost of all the others started. The last controller ending defrost will get defrost of all the others stopped.
D3A OPN; CLS. DI3 digital input activation. See D1A .(OPN)
LSM NON;
MAN;
ECO;
DI1, DI2, DI3;
RTC.
Light control mode .(NON)
NON : light output not controlled.
MAN : light ouput controlled through button (if OAx=LGT).
ECO : lights activated/deactivated following the ECO state.
DIx : lights activated/deactivated following the DIx state.
RTC : lights change state at STT time, then they revert their state at EDT time.
LSA OPN;
CLS
Light activation (only with LSM=ECO, DIx or RTC) .(OPN)
OPN : lights on with DIx opened, ECO mode deactivated or at EDT time.
CLS : lights on with DIx closed, ECO mode activated or at STT time.
STT HH.M Start time for timed action .(23:50)
EDT HH.M End time for timed actions .(23:50)
OA1 NON;
LGT;
0-1;
2CU;
2EU;
ALO;
ALC
AUX 1 output operation .(NON)
NON : output disabled (always off).
LGT : output enabled for light control.
0-1 : the relay contacts follow the on/standby state of controller.
2CU : output programmed for the control of an auxiliary compressor.
2EU : output enabled for the control of the electrical defrost of a second evaporator.
ALO : contacts open when an alarm condition occurs.
ALC : contacts make when an alarm condition occurs.
OA2 See OA1 AUX2 output operation. See OA1 . (NON)
2CD 0...120 sec Auxiliary compressor start delay. If OAx=2CU the auxiliary output is switched on with a delay of 2CD seconds after the
main compressor has cut-in. Both compressors are turned off at the same time .(30)
OS1 -12...1 Probe T1 offset ( .0°C)
T2 NO/YES Probe T2 enabling (evaporator) .(NO)
OS2 -12...1 Probe T2 offset (C).
T3 NON;
DSP;
CND;
2EU
Auxiliary probe T3 operation .(NON)
NON : probe T3 not fitted.
DSP : temperature T3 to be displayed.
CND : condenser temperature measurement.
2EU : second evaporator temperature measurement.
OS3 -12...1 Probe 3 offset .(C)
AHM NON;
ALR;
STP;
Operation in case of high condenser alarm .(NON)
NON : high condenser alarm inhibited.
ALR : in case of alarm, “HC”ashes in the display and the buzzer is switched on.
STP : in addition to the alarm symbols displayed, the compressor is stopped and defrosts are suspended.
AHT -50...110° Condensation temperature alarm (referred to T3 probe) .(60°C)
TLD 1...30 min Delay for minimum temperature (TLO) and maximum temperature (THI) logging (5).
TDS T1;
1-2;
T3
Selects the temperature probe to be displayed .(T1)
T1 : probe T1
1-2 : the AVG-weighted average between T1 and T2
T3 : probe T3
AVG 0...100% The relative weight of T2 on T1 (if TDS = 1-2) (0)
Example 1: T1 = -5°, T2 = -20°, AVG = 100%. The displayed temperature will be -20° (T1 has no effect)
Example 2: T1 = -5°, T2 = -20°, AVG = 60%. The displayed temperature will be -14.
SCL 1°C;
2°C;
°F
Readout scale (C).
1°C : measuring range -50…110°C (0.1°C resolution within -9.9 ÷ 9.9°C interval, 1°C outside)
2°C : measuring range -50 … 110°C
°F : measuring range -55 … 180°F
SIM 0...100 Display slowdown .(3)
ADR 1...255 BR1-28 address for PC communication .(1)
EPT EPT
Heavy duty Heavy dutyEco
Heavy duty
condition detection
ECO condition
detection
SP+HY0
SP
IISP
IISP+IIH0
IISP-IIH1
SP-HY1
Fig.3 - EPT parameter
5. WIRING DIAGRAMS
1 2 64 5 7 8 9 10 11 13 19
20 21 22 23 24 25 26 27 28
RS485
data I/O
remote
16(4)A16(4)A7A
7A
AUX 2 AUX 1
16(12)A
AC
DC
AUX T3
Aux
DI 1 DI 2 DI 3
L1
L2 / Neutral
L2 / Neutral
LIVE
AIR T1
EVP T2
Power Supply
100...240 Vac
FUSE 20A
Remote
unit
BR1-28
1. INSTALLATION
The BR1-28 controller, size mm (WxHxD), is to be secured to a DIN rail in such a position as to ensure that no liquid infiltrates causing serious 107x95x47
damage and compromising safety.
Make sure that electrical connections comply with the paragraph “wiring diagrams”. To reduce the effects of electromagnetic disturbance, keep the
sensor and signal cables well separate from the power wires.
Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.
Place the probe T2 on the evaporator where there is the maximum formation of frost.
The function of probe T3 is determined by the parameter T3. With =DSP the probe measures the temperature to be displayed. With =CND the probe T3 T3
measures the condenser temperature, it must therefore be placed between the fins of the condensing unit. With =2EU the probe measures the temperature T3
of the second evaporator and it must therefore be placed where there is the maximum formation of frost. With =NON, the third probe is disabled.T3
At the first power-up or after a long power failure, the display might show “TIM”: press any of the buttons to mute the buzzer, then check if the real time
clock is correct (MIN, HRS).
2. DISPLAY INFO
Alarm Room high temperature alarm
Thermostat output Room low temperature alarm
Fan output Condenser high temperature
Defrost output Generic alarm
Activation of 2nd set Condenser clean warning
Controller in stand-by Probe T1 failure
Defrost in progress Probe T2 failure
Door open alarm Probe T3 failure
Check clock time
In case of alarm, press any key to mute the buzzer sound.
Info items Navigation
Instant probe 1 temperature
* Instant probe 2 temperature
* Instant probe 3 temperature
Minutes of the RTC
Hours of the RTC
Start time for timed actions
End time for timed actions
Max probe 1 temperature
Min probe 1 temperature
** Compressor working weeks
Keypad state lock
*: only if enabled **: only if ACC > 0
Real Time Clock (RTC) modification (MIN, HRS, STT, EDT)
Keypad Lock THI / TLO / CND reset
3. OPERATION
Setpoint I and II: display and modification Standby (SB=YES)
1’’
3’’
I Set II tSe
Increase
Decrease
3.1 SELECTION OF SECOND PARAMETER GROUP
Manual (IISM=MAN) Automatic (IISM=ECO) Contact (IISM=DI) Real time clock (IISM=RTC)
ECO
(See Fig. 3)
DxA=CLS
DxA=OPN
Group II:
Start at STT
End at EDT
3.2 DEFROST START
Manual Real time clock (DFM=RTC) Timed (DFM=TIM) Optimized (DFM=FRO) Remote (DxO=RDS)
Scheduled at
DH1...DH6 time
DFT hours T2 < 0°C
for DFT hours
DxA=OPN
Synchronized (D3O=DSY)
- - -
+ + +
27 27 27
BR1-28 BR1-28 BR1-28
28 28 28
DI3 DI3 DI3 Start and end are synchronized
among connected BR1-28
3.3 DEFROST TERMINATION
Time limit Survey of 1 evaporator before time limit Survey of 2 evaporators before time limit
DTO minutes
DTO minutes
or
T2 ≥ DLI
DTO minutes
or
T2 and T3 ≥ DLI
Resuming thermostatic cycle. When defrost is over, if is greater than 0, all outputs will remain off for minutes, in order for the ice to melt DRN DRN
completely and the resulting water to drain. Moreover, if probe T2 is active (T2=YES), the fans will re-start when the evaporator gets to a temperature lower
than FDD; Vice versa, if probe T2 is not active ( =NO) or after defrost has come to an end, such condition does not occur by end of the time , after T2 FTO FTO
minutes have elapsed the fans will be switched on anyway.
Caution: if =NON or =HEA all defrost functions are inhibited; if =0, automatic defrost functions are excluded. During defrost, high temperature DFM C-H DFT
alarm is bypassed.
4. CONFIGURATION PARAMETERS
Access / Navigation / Modication
PAR RANGE DESCRIPTION
SPL -50..SPH Minimum limit for SP setting .(-25°C)
SPH SPL...110° Maximum limit for SP setting .(20°C)
Display value
Exit
Next
Previous
Visualize value
Increase or decrease value
Next or previous parameter
Exit
Thank you for having chosen an Intermatic electronic product. Before installing the instrument, please read this instruction booklet carefully in order to
ensure safe installation and optimum performance.
= Click Click and Hold =
6. TECHNICAL DATA
Power Supply
BR1-28.…W 100-240Vac ±10%, 50/60Hz, 3W
Relay Output Max Loads (240Vac)
Model
Output BR1-28..S..-. BR1-28..Q..-.
Compressor 16A resistive
12 FLA 72 LRA
12A resistive
12 FLA 72 LRA
Evap. Fan 16A resistive
3.6 FLA 21.6 LRA
12A resistive
3.6 FLA 21.6 LRA
Defrost 16A resistive
3.6 FLA 21.6 LRA
12A resistive
3.6 FLA 21.6 LRA
Auxiliary loads 1 7A resistive
1 FLA 4 LRA
7A resistive
1 FLA 4 LRA
Auxiliary loads 2 7A resistive
1 FLA 4 LRA
7A resistive
1 FLA 4 LRA
Input
NTC 10KΩ@25°C Intermatic Part No. SN4...
Measurement Range
-50…110°C, -58…180°F
-50 / -9.9 … 9.9 / 110°C
Measurement Accuracy
<0.5°C within the measurement range
Real Time Clock Battery
>150 hours; self-rechargeable
Operating Conditions
-10 … +50°C; 15%...80% r.H.
Pollution degree 2
Approvals and Reference Norms
- RoHS 2011/65/UE
- EN50082-1; EN55022 (Class B);
- EN60730-1; EN60730-2-9;
- UL60730-1, File SA32385
158--01988
Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
More than one circuit breaker or disconnect switch may be required to de-energize the equipment before servicing.
Installation and/or wiring must be in accordance with National and Local Electrical Code requirements.
The device shall be installed in compliance with the enclosure, mounting, spacing and segregation requirements of the ultimate enclosure.
WARNING Risk of Fire or Electric Shock
7777 Winn Road
Spring Grove, IL 60081
Intermatic Customer Service:
815-675-7000
www.intermatic.com
INSTRUCTIONS FOR USE
BR1-28
BR1-28
INSTRUCTIONS FOR USE EN
Increase
Decrease
BR1-28 INSTRUCTIONS FOR USE
MODE D’EMPLOI FR
0L0021R00-03


Produkt Specifikationer

Mærke: Intermatic
Kategori: Ikke kategoriseret
Model: BR1-28C1Q5WH-BI

Har du brug for hjælp?

Hvis du har brug for hjælp til Intermatic BR1-28C1Q5WH-BI stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Intermatic Manualer

Intermatic

Intermatic PF1103 Manual

17 December 2024
Intermatic

Intermatic T10004R Manual

17 December 2024
Intermatic

Intermatic PRO2002403 Manual

16 December 2024
Intermatic

Intermatic ST01A Manual

16 December 2024
Intermatic

Intermatic PF1102MT Manual

16 December 2024
Intermatic

Intermatic PF1102M Manual

16 December 2024
Intermatic

Intermatic PF1222TB1 Manual

16 December 2024
Intermatic

Intermatic PF1103T Manual

16 December 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Smeg

Smeg KIT6PX Manual

23 December 2024
Smeg

Smeg KIT6CX Manual

23 December 2024
Smeg

Smeg GTA-6 Manual

23 December 2024