MODEL: T103
24 HOUR DIAL TIME SWITCH
TYPE 1 INDOOR USE ONLY
DOUBLE POLE SINGLE THROW (DPST)
40 A RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY EACH POLE 120/208/240 VAC
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
PROGRAMMING INSTRUCTIONS
1. TO SET ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-
DIAL ON OFF, pointing to time (AM or PM) when and operations are desired,
tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL
order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction
and align the exact time-of-day on the (the time now, when CLOCK-DIAL
switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
TO OPERATE SWITCH MANUALLY: MANUAL LEVERMove
CLOCK-below
DIAL left or right as indicated by arrows. This will not effect next operation.
IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day.
See programming instructions.
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE 3 PHASE
120 V. 240 V. 208 V. 240 V.
14
12
10
8
15
20
30
40
90
90
90
90
1/2
1
2
-
2
2 1/2
3
5
N/AN/A
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON
TRIPPER
WARNING Risk of Fire or Electric Shock
Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
Installation and/or wiring must be in accordance with national and local electrical code requirements.
Use wires rated at least 90°C - COPPER conductors ONLY.
Replace plastic insulator covering terminals before powering ON.
KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE • Rotate timer dial clockwise only.
Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
AVERTISSEMENT Risque d’incendie ou de choc électrique
Utiliser des fils classés 90°C minimum - Conducteurs en CUIVRE UNIQUEMENT.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--02000
UL
HOLOGRAM
LABEL
LR3730
WIRING INSTRUCTIONS: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly
(2-18 in-lbs). Use solid or stranded COPPER only. May use two wires of the same size and type.conductors
TYPICAL
WIRING
DIAGRAM CLOCK
MOTOR
120/240
VOLT
3 WIRE
SUPPLY
TO
LOADS
GROUND
LINE 2
LINE 1
A 42
GR.
3
1
NEUT.


Produkt Specifikationer

Mærke: Intermatic
Kategori: Ikke kategoriseret
Model: T103

Har du brug for hjælp?

Hvis du har brug for hjælp til Intermatic T103 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Intermatic Manualer

Intermatic

Intermatic T101PC Manual

6 September 2024
Intermatic

Intermatic T103 Manual

6 September 2024
Intermatic

Intermatic T103PC Manual

6 September 2024
Intermatic

Intermatic T104PC Manual

6 September 2024
Intermatic

Intermatic ET1705C Manual

5 September 2024
Intermatic

Intermatic T104 Manual

29 August 2024
Intermatic

Intermatic ET8015C Manual

27 August 2024
Intermatic

Intermatic ET8215C Manual

27 August 2024
Intermatic

Intermatic WP3100C Manual

27 August 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer