TECHNICAL NOTE 7-5
Rev. E, May 1994
RS-485 CABLING GUIDELINES FOR THE COM20020 UNIVERSAL
LOCAL AREA NETWORK CONTROLLER (ULANC) AND
EXPERIMENTAL PROCEDURE FOR VERIFICATION OF RS-485
CABLING GUIDELINES
INTRODUCTION TO EIA RS-485
EIA RS-485 is a specification for the support of a multi-drop differential serial digital data network. RS-485 came about as
microprocessors and the use of distributed intelligence became popular in the design of industrial systems. The
implementation of such concepts created a demand for a standard method of communicating serially in such environments.
The actual RS-485 specification came about as a result of the shortfalls of the RS-422 standard. RS-485 is virtually
identical to RS-422 except in two respects, increased receiver sensitivity and support of longer line lengths.
The basic RS-485 specification standardizes the electrical characteristics of each transceiver and provides some basic
guidelines for establishing a network. By definition, a basic transceiver shall have a minimum input resistance of 12 Kohms
and handle a +/-7V common mode voltage regardless of whether power is applied or not. When the transceiver is
powered it must present the minimum input resistance and present less than 50pf of capacitance at its input terminals. In
addition, each driver must be capable of providing a minimum level of 1.5V in the presence of 32 transceivers and two 120
ohm terminating resistors. The 120 ohm termination results from the use of twisted pair cable, the preferred media in many
industrial applications because of its wide availability and low cost. Another critical requirement of RS-485 is that the
receiver must be capable of detecting levels down to 200mV which is of great advantage when long line lengths are
needed. RS-485 does not specify a modulation method or a maximum data rate. This gives the system designer great
flexibility in creating a low-cost high-performance network.
The combination of long line length, high node count (32 nodes), and edia has made the RS-485 support of low-cost m
specification the primary choice as a data communication standard in industrial applications.
CABLING GUIDELINES FOR RS-485 INTERFACE WITH THE COM20020
The following cabling guidelines provide a basis for establishing a low cost Local Area Network (LAN) based on the
ARCNET protocol for use with the COM20020 Universal ARCNET Controller with a differential RS-485 driver. The
guidelines presented are for unshielded twisted pair cable modulated with the COM20020's backplane encoding scheme.
All testing and experiments were performed using a 24AWG copper twisted unshielded 2 pair cable with a characteristic
impedance (Zo) of 120 Ohms. The topology used in all experiments was a daisy-chained configuration with no stubs (i.e.
no drops).
TRANSMISSION LINE EFFECTS IN LOCAL AREA NETWORKS
Transmission line effects often present an obstacle in obtaining high performance in data communication networks. Among
the problems that plague high data rate LAN's are reflections, signal attenuation, and D.C. loading. Taking into account all
three parameters when designing a network can result in a faster and more reliable network.


Produkt Specifikationer

Mærke: Microchip
Kategori: Ikke kategoriseret
Model: COM20019i

Har du brug for hjælp?

Hvis du har brug for hjælp til Microchip COM20019i stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Microchip Manualer

Microchip

Microchip PD81101 Manual

23 December 2024
Microchip

Microchip ATECC608B Manual

4 September 2024
Microchip

Microchip HV860 Manual

4 September 2024
Microchip

Microchip EVB-LAN9255 Manual

4 September 2024
Microchip

Microchip LX4580 Manual

4 September 2024
Microchip

Microchip LX7720 Manual

4 September 2024
Microchip

Microchip AT32UC3A364 Manual

2 September 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Smeg

Smeg KIT6PX Manual

23 December 2024
Smeg

Smeg KIT6CX Manual

23 December 2024
Smeg

Smeg GTA-6 Manual

23 December 2024