APC BE850M2 Manual
APC
Uafbrydelig strømforsyning (UPS)
BE850M2
Læs nedenfor 📖 manual på dansk for APC BE850M2 (2 sider) i kategorien Uafbrydelig strømforsyning (UPS). Denne guide var nyttig for 16 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere
Side 1/2
Inventory
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and
dealer if there is any damage.
SAVE THESE INSTRUCTIONS - This section contains important
instructions that should be followed during installation and maintenance
of the UPS and batteries. Failure to follow these instructions can result
in equipment damage.
Connect the Battery
The Back-UPS is shipped with one battery cable disconnected.
Connect Equipment
Note: USB charging ports are only available on the BE850M2 and the BE850M2-LM..
Turn On the Back-UPS
Press the POWER button. It will illuminate green and a single short beep indicating that the
Back-UPS is on and providing protection for connected equipment.
The Back-UPS battery will charge regardless of whether the Back-UPS is switched on or off
as long as it is connected to AC power. The UPS will have full runtime capability after the
initial 24-hour charging period, connected to AC power.
If the red Building Wiring Fault indicator (located on the end near the power cord) is lit, your
building wiring may present a shock hazard that should be corrected by a qualified
electrician.
Turn Off the Back-UPS
Press the POWER button for at least 2 seconds. At the first beep, release the button and the
UPS will turn off. A 2 second delay has been added to mitigate unintentional contact with the
POWER button.
Quick Mute
The Back-UPS is able to temporarily mute user correctable alarms such as: On Battery,
Battery disconnected and Overload.
During such alarms, a short press (less than 2 seconds) of the POWER button will
temporarily mute the alarm until the condition has been reset. A short double beep will
confirm that Quick Mute has been activated. Pressing the POWER button for more than 2
seconds will turn off the UPS.
Other critical events such as Battery replacement and Charger notification can not be
temporarily muted. The unit in these cases must be turned off.
On Battery Indicator Modes
With the UPS turned on, configuring the On Battery Indicator modes below is done by
holding down the POWER button and waiting for the third beep. At the third beep, the
POWER button will cycle red / green. Release the POWER button and its color will indicate
the mode the UPS is in. Press the POWER button to cycle through each mode. See the table
below for the 3 mode selection colors. Once the mode has been selected, wait 5 seconds and
the setting will be committed to the UPS.
PowerChute™ Personal Edition Software
Overview
Use PowerChute Personal Edition software to configure the UPS settings. During a power
outage, PowerChute will save any open files on your computer and shut it down. When
power is restored, it will restart the computer.
Note: PowerChute is only compatible with a Windows operating system. If you are using
Mac OSX, use the native shutdown feature to protect your system. See the documentation
provided with your computer.
Installation
Use a USB cable to connect the Data port on the rear panel of the UPS to the USB port on
your computer. On the computer, go to www.apc.com/tools/download. Select “Software
Upgrades - PowerChute Personal Edition” in the “Filter by Software/Firmware” drop down
menu. Select the appropriate operating system. Follow directions to download the software.
Status Indicators
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Connect the UPS power cable directly to a wall outlet.
• The UPS is intended for indoor use only.
• Do not operate the UPS in direct sunlight, in contact with fluids, or where there is excessive dust
and humidity.
• Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
Failure to follow these instructions will result in death or serious injury.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
• Battery must be replaced when they reach end of service life.
• Batteries must be replaced when the unit indicates battery replacement is necessary.
• When replacing batteries, replace with the same number and type of batteries originally installed in
the unit.
Failure to follow these instructions could result in minor or moderate injury and
equipment damage.
Remove the
“Stop! Connect the Battery” label
that covers the outlets.
Press the battery compartment cover release
tabs located on the underside of the unit. Slide
the battery cover off.
Connect the battery cable securely to the
battery terminal. It is normal for small sparks to
be seen when the battery cable is connected to
the battery terminal.
Reinstall the battery compartment cover.
Be sure that the release tabs lock into place.
Feature Function Suggested Use
Battery Backup + Surge
Protection Outlets
• Receive power from the
battery for a limited period
of time when a power
outage, or brownout
condition occurs.
• Provide protection from
power surges or spikes.
Connect a computer, monitor and
other critical peripheral devices
that need to remain on during
power outages or AC problems.
Surge Protection Outlets • Provide protection from
power surges or spikes.
Connect non-critical peripheral
devices (such as printer, scanner,
etc.) that do not need to remain on
during power outages or AC
problems.
USB charging ports
(BE850M2/850M2-LM only)
• Provide power when the unit
is on AC and on battery.
Charge USB devices
bu446b
bu447b
bu448b
bu449b
bu450b
USB
Charging
Ports
Battery Backup + Surge
Protection Outlets
Surge Protection
Outlets
bu451b
POWER
Button
bu452b
Building
Wiring
Fault
USB Data Port
(PowerChute)
AC Power
Inlet
Circuit
Breaker
Mode Visual
Indicator Audible Indicator Mode Selection
Color
Quiet Alarm
(default)
The POWER
button is solid
green and flashes
twice every 2
seconds until
Low Battery
notification
where it will
flash green in
rapid succession.
No alarm until Low Battery
notification where the alarm beeps
twice every 30 seconds
Flashing green
No Alarm No alarm while the UPS is On
Battery Flashing red
Full Alarm Alarm sounds 4 beeps every 30
seconds until Low Battery
notification where the alarm beeps
every half second. As the UPS shuts
down, it sounds one beep every 4
seconds
Flashing amber
Status Power Button
illumination
Audible
Indicator On
Audible Indicator
Terminates
Power On
The Back-UPS is supplying AC
power to connected equipment.
Solid green None N/A
On Battery
Back-UPS supplying battery power
to battery backup outlets.
Solid green and
flashes twice
every 2 seconds. The audible
alarm depends
on the On
Battery
Indicator mode
setting. See the
On Battery
Indicator
Modes section
for full details.
- Using Quick Mute
- Beeping stops when AC
power is restored or the
Back-UPS is turned off.
Applies only to modes
where the on battery
alarm is audible.
Low Battery notification
The Back-UPS is supplying battery
power to the battery backup outlets
and the battery is near a total
discharge state.
Flashes green in
rapid succession.
Low Battery shutdown
The battery has been completely
discharged while the Back-UPS is
on battery, the UPS will shut down.
None - AC power is restored
- AC is not restored
within 32 seconds
- The Back-UPS is turned
off.
Sleep Mode
The UPS has shut down and will
“awaken” once AC power is
restored
None None N/A
Replace Battery
• The battery is disconnected.
• The battery needs to be charged,
or replaced.
• Flashes red
only.
• Alternates
green-red
• Constant tone
• Constant tone
- Back-UPS is turned off
- If the battery is
disconnected, connect
the battery or use Quick
Mute
On Line Overload
Condition occurs when the UPS is
on AC power and the connected
load exceeds the power output of
the UPS. If overload persists for an
extended period of time, the UPS
will enter Overload Shutdown.
Solid amber Constant tone - Using Quick Mute
- Load removed from the
UPS
- Load exceeds circuit
breaker and the UPS
turns off
Overload Shutdown
An overload condition has occurred
in one or more of the battery backup
outlets while operating on battery
power. This also occurs if On Line
Overload persists for an extended
period of time.
None Constant tone Back-UPS is turned off
USB Detected Fault
A short circuit has been detected or
an error has occurred.
Alternates
green-amber
None N/A
User Manual Back-UPS™ BE850M2/850M2-LM, BN900M/900M-CA
Produkt Specifikationer
Mærke: | APC |
Kategori: | Uafbrydelig strømforsyning (UPS) |
Model: | BE850M2 |
Bredde: | 327 mm |
Dybde: | 105 mm |
Højde: | 139 mm |
Vægt: | 4100 g |
Brugervejledning: | Ja |
Produktfarve: | Sort |
Pakkevægt: | 4400 g |
Pakkedybde: | 168 mm |
Pakkebredde: | 416 mm |
Pakkehøjde: | 196 mm |
USB-port: | Ja |
Formfaktor: | Kompakt |
Opbevaringstemperatur (T-T): | -15 - 45 °C |
Relativ luftfugtighed ved drift (H-H): | 10 - 90 % |
Relativ luftfugtighed ved opbevaring (H-H): | 0 - 95 % |
Antal USB 2.0-porte: | 2 |
Driftstemperatur (T-T): | 0 - 40 °C |
Kabler inkluderet: | USB kabel |
Støjniveau: | 45 dB |
Udgangseffekt: | 450 W |
LED-indikatorer: | Ja |
Kabellængde: | 1.52 m |
Batterilevetid (maks.): | 5 År |
Antal understøttede batterier: | 1 |
Opladningstid for batteri: | 8 t |
Bæredygtighedscertifikater: | ENERGY STAR |
Driftshøjde: | 0 - 3000 m |
Ikke-drift højde: | 0 - 15000 m |
Indgangsfrekvens: | 50/60 Hz |
Batteriets kapacitet: | 84 VAh |
Lydalarmer: | Ja |
Strømstik: | NEMA 5-15P |
AC udgange, antal: | 9 AC stikkontakt(er) |
AC stikkontakt typer: | NEMA 5–15R |
Overspænding energivurdering: | 354 J |
Indgående driftsspænding (maks.): | 139 V |
Output strømkapacitet (VA): | 0.85 kVA |
Indgående driftsspænding (min.): | 92 V |
Udgangs driftsspænding (min.): | 120 V |
Udgangs driftsspænding (maks.): | 120 V |
UPS topologi: | Standby (offline) |
Strøm (maks.): | 5 A |
Regulering af udgangsfrekvens: | 50 - 60 Hz |
Holdetid (maks.): | 10 ms |
Beskyttelse ved overspænding: | Ja |
Holdetid (min.): | 6 ms |
Hørbare alarmtilstande: | Alarm when on battery,Low battery alarm,Overload alarm |
Koldstart: | Ja |
EMI/RFI støjfiltrering: | Ja |
Har du brug for hjælp?
Hvis du har brug for hjælp til APC BE850M2 stil et spørgsmål nedenfor, og andre brugere vil svare dig
Uafbrydelig strømforsyning (UPS) APC Manualer
12 Oktober 2024
12 Oktober 2024
12 Oktober 2024
24 September 2024
24 September 2024
24 September 2024
17 September 2024
17 September 2024
5 Maj 2024
Uafbrydelig strømforsyning (UPS) Manualer
- Uafbrydelig strømforsyning (UPS) Ikea
- Uafbrydelig strømforsyning (UPS) Siemens
- Uafbrydelig strømforsyning (UPS) CyberPower
- Uafbrydelig strømforsyning (UPS) HP
- Uafbrydelig strømforsyning (UPS) GYS
- Uafbrydelig strømforsyning (UPS) Lenovo
- Uafbrydelig strømforsyning (UPS) Adj
- Uafbrydelig strømforsyning (UPS) Wago
- Uafbrydelig strømforsyning (UPS) Gembird
- Uafbrydelig strømforsyning (UPS) Tripp Lite
- Uafbrydelig strømforsyning (UPS) Digitus
- Uafbrydelig strømforsyning (UPS) Aiptek
- Uafbrydelig strømforsyning (UPS) EnerGenie
- Uafbrydelig strømforsyning (UPS) Voltcraft
- Uafbrydelig strømforsyning (UPS) LevelOne
- Uafbrydelig strømforsyning (UPS) Eaton
- Uafbrydelig strømforsyning (UPS) BlueWalker
- Uafbrydelig strømforsyning (UPS) V7
- Uafbrydelig strømforsyning (UPS) Steren
- Uafbrydelig strømforsyning (UPS) Salicru
- Uafbrydelig strømforsyning (UPS) Approx
Nyeste Uafbrydelig strømforsyning (UPS) Manualer
15 November 2024
8 November 2024
8 November 2024
22 Oktober 2024
22 Oktober 2024
21 Oktober 2024
2 Oktober 2024
24 September 2024
23 September 2024
23 September 2024