CyberPower BH1500 Manual


Læs nedenfor 📖 manual på dansk for CyberPower BH1500 (2 sider) i kategorien Uafbrydelig strømforsyning (UPS). Denne guide var nyttig for 12 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
IN OUT
Automatic Voltage Regulators
increase low or decrease high voltage to computer
safe 110/120 volts. The AVR automatically provides
battery back-up power if line voltage drops below 88
volts or exceeds 140 volts.
AVR
INCONSIST ENT
UTILIT Y POWER
CONSISTENT
SAFE POWER
BH900 / BH1200 / BH1500
Users Manual
K01-BH1K500
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully during installation
and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free
of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. No user
serviceable parts inside except for battery.
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is
disconnected.
CAUTION! UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an
outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the unit.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the
battery or installing a computer component.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell
products for life support or medical applications. DO NOT use in any circumstance that would affect operation or safety
of any life support equipment or with any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near
an aquarium. Condensation from the aquarium can cause the unit to short out.
DO NOT USE WITH LASER PRINTERS! The power demands of these devices will overload and possibly
damage the unit.
1
2
3
54
UNPACKING
Inspect the UPS upon receipt. The box should contain the following:
(1) UPS unit; (1) User’s manual; (1) PowerPanel™ Personal Edition software CD; (1) USB device cable; (1) Telephone
cable; (1) Warranty registration card; (1) Coaxial Cable
WHAT IS AVR?
The BH900 / BH1200 / BH1500 provide complete power protection from utility power
that is not always consistent. The BH900 features 890 Joules and BH1200 BH1500
features 1080 Joules of surge protection, and provide long lasting battery backup with
sealed maintenance free lead acid battery for loss of utility power and voltage sags.
The BH900 / BH1200 / BH1500 ensure consistent power to your computer system and
include software that will automatically save your open files and shutdown your
computer system during a utility power loss.
AUTOMATIC VOLTAGE REGULATOR?
The BH900 / BH1200 / BH1500 stabilize utility power voltage levels that can be inconsistent. The incoming utility power
may be damaging to important data files, but with Automatic Voltage Regulation, the computer will only not experience
damaging voltage levels. An Automatic Voltage Regulator automatically increases low or decreases high voltage to a
consistent, computer safe 110v/120v. The unit’s powerful batteries will provide power only if the incoming voltage drops
below 88v or increases above 140v.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, is recharging the batteries for at least 16 hours
recommended to insure that the battery’s maximum charge capacity is achieved. A loss of charge may occur during
shipping and storage. To recharge the batteries, simply leave the unit plugged into an AC outlet. The unit will charge
in both the ON as well as the OFF position.
2. With the UPS unit off and unplugged, connect your computer, monitor, and any externally powered data storage
device (Zip drive, Jazz drive, Tape drive, etc…) into the battery power supplied outlets. Plug your peripheral
equipment (printer, scanner, speakers) into the full-time surge protection outlets. DO NOT plug a laser printer, paper
shredder, copier, space heater, vacuum or other large electrical device into the UPS. The power demands of
these devices will overload and possibly damage the unit.
3. To surge protect a network connection, connect a network cable from the wall jack outlet to the IN jack
of the UPS. Then connect a network cable from the OUT jack on the UPS to the network device.
4. Plug the UPS into a 2 pole, 3 wire grounding receptacle (wall outlet). Make sure the wall branch outlet is protected by
a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. refrigerator, copier, etc…).
The warranty prohibits the use of extension cords, outlet strips, and surge strips.
5. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will “beep” once.
6. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the
UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make
sure the circuit breaker is depressed and then turn the UPS on.
7. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
8. To store your UPS for an extended period, cover it and store with the battery fully charged. While in storage recharge
the battery every three months to insure battery life.
DESCRIPTION
1 Power Switch
Can be used as a master on/off switch for equipment connected to the battery power supplied outlets.
2 Power On Indicator
This LED is illuminated when the utility condition is normal and the UPS outlets are providing power, free of surges.
3 Using Battery Indicator
This LED is illuminated when the unit is running in the backup condition.
4 AVR Indicator
This LED is illuminated when the unit is running in the AVR mode.
5 Over Load Indicator
This LED is illuminated when the unit is overload. You will need to reduce the load.
6 Battery and Surge Protected Outlets
The unit has four battery powered/surge protected outlets for connected equipment and ensures temporary
uninterrupted operation of your equipment during a power failure.
7 Full-Time Surge Protection Outlets
The unit has four always on surge suppression outlets.
8 Electrical Wiring Fault Indicator
This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If
this is illuminated, user is advised to disconnect all electrical equipment from the outlet and have an electrician check to ensure the outlet is
properly wired. The unit will not provide surge protection without being plugged into a grounded and properly wired wall outlet.
If you are using a serial cable you must use a CyberPower
serial cable. If you need this cable please contact technical
support. tech@cyberpowersystems.com
IMPORTANT SAFETY WARNINGS
INSTALLING YOUR UPS SYSTEM
BASIC OPERATION
TROUBLE SHOOTING
TECHNICAL SPECIFICATIONS
Additional troubleshooting information can be found at www.cyberpowersystems.com/support.htm
Problem Possible Cause Solution
Full-time surge protection outlets
stop providing power to equipment.
Circuit breaker button is projecting
from the side of the unit.
Circuit breaker has tripped
due to an overload.
Turn the UPS off and unplug at least one piece of equipment.
Wait 10 seconds, reset the circuit breaker by depressing the
button, and then turn the UPS on.
The UPS does not perform
expected runtime.
Recharge the battery by leaving the UPS plugged in.
Contact CyberPower Systems about replacement batteries at
tech@cyberpowersystems.com
Battery is slightly worn out.
Battery not fully charged.
The UPS will not turn on.
The on/off switch is designed
to prevent damage by rapidly
turning it off and on.
Turn the UPS off. Wait 10 seconds and then turn the UPS on.
The unit is not connected to
an AC outlet. The unit must be connected to a 110/120v 60Hz outlet.
The battery is worn out. Contact CyberPower Systems about replacement batteries at
tech@cyberpowersystems.com
Mechanical problem. Contact CyberPower Systems at
tech@cyberpowersystems.com
PowerPanel™ Personal Edition
is inactive (all icons are gray).
The USB / serial cable is not
connected.
Connect the USB / serial cable to the UPS unit and an open
USB / serial port on the back of the computer. You must use
the cable that came with the unit.
The USB / serial cable is
connected to the wrong port.
Check the back of the computer for an additional USB / serial
port. Move the cable to this port.
The unit is not providing
battery power.
Shutdown your computer and turn the UPS off. Wait 10
seconds and turn the UPS back on. This should reset the unit.
The serial cable is not the
cable that was included with
the UPS unit.
Model iMac G4
Desktop PC Desktop PC Desktop PC Desktop PC
with LCD Monitor with 15” Monitor with 17” Monitor with 21” Monitor
BH900 105 minutes 75 minutes 60 minutes 40 minutes 35 minutes
145 minutes 90 minutes 66 minutes 50 minutes 42 minutesBH1200
170 minutes 100 minutes 75 minutes 58 minutes 48 minutesBH1500
EXPECTED RUNTIME IN MINUTES
(Due to the differences in computer components, the runtime will vary.)
9 Communication Protection Ports
Communication protection ports will protect any standard modem, fax , telephone line, broadband network or Ethernet connection.
10 Circuit Breaker
Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.
11 Serial/USB Ports to PC
The ports allow connection and communication from the USB or DB-9 serial port on the computer to the UPS unit. The UPS communicates
its status to the PowerPanel™ Personal Edition software.
Note: Only one of these two ports can be used to communicate with your computer at one time.
Note: To install PowerPanel™ Personal Edition Software the computer will need Microsoft
R Internet Explore 5.0 or higher installed.
Note: If using the Serial Port, users need to download Power PanelR
software from our website
http://www.cyberpowersystems.com
and order the standard serial cable. If you have any questions email CyberPower technical support for help.
tech@cyberpowersystems.com
12 Coax/Cable/DSS Surge Protection
The Coax/Cable/DSS surge protection ports will protect any cable modem, CATV converter, or DSS receiver.
13 Outlets Designed for AC Adapters
The unit has four outlets spaced to allow AC power adapter blocks to be plugged into the UPS without blocking
adjacent outlets.
REPLACING THE BATTERY
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the
battery under the supervision of personnel knowledgeable of batteries and their precautions.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present a risk of electrical shock. Do not dispose of battery in a fire as it may explode.
Follow all local ordinances regarding proper disposal of batteries. Almost any retailer that sells lead-acid batteries
collects used batteries for recycling, as required by most state laws.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions
before replacing the battery:
REMINDER: HAZARDOUS WASTEBatteries are consider and must be disposed of properly. Almost any retailer that
sells lead-acid batteries collects used batteries for recycling, as required by most state laws.
Model BH900 BH1200 BH1500
Capacity 900VA / 560W 1200VA / 720W 1500VA / 900W
Input Voltage on Utility 88V to 140V
Input Frequency 47 Hz to 63 Hz
On-Battery Output Voltage 120Vac ± 5%
Transfer Time 4ms Typical
Max. Load for UPS Outlets 900VA / 560W 1200VA / 720W 1500VA / 900W
Max. Load for Full-Time
Surge Protection outlets (8 Outlets) 12 Amps
On-Battery Output Wave Form Simulated Sine Wave Form
Operating Temperature + 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity 0 to 95% NON-CONDENSING
Size (L x W x H) 13 1/4” x 4” x 9 7/8” 12 3/4” x 3 1/2” x 14 1/2”
33.6 x 10.0 x 24.9cm 32.5 x 8.8 x 37.2cm
Net Weight 20.9 lbs 21.8 lbs 26.6 lbs
Typical Battery Recharge Time 8 hours typical from total discharge
Typical Battery Life 3 to 6 years, depending on number of discharge/recharge cycles
Battery Type Sealed Maintenance Free Lead Acid Battery
Safety Approvals UL1778(UPS), cUL107., FCC/DoC Class B
8
67 67
10
11
13
13
12
12 11
10
9
98


Produkt Specifikationer

Mærke: CyberPower
Kategori: Uafbrydelig strømforsyning (UPS)
Model: BH1500

Har du brug for hjælp?

Hvis du har brug for hjælp til CyberPower BH1500 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Uafbrydelig strømforsyning (UPS) CyberPower Manualer

Uafbrydelig strømforsyning (UPS) Manualer

Nyeste Uafbrydelig strømforsyning (UPS) Manualer