CyberPower OR1500LCDRM1U Manual


Læs nedenfor 📖 manual på dansk for CyberPower OR1500LCDRM1U (2 sider) i kategorien Uafbrydelig strømforsyning (UPS). Denne guide var nyttig for 27 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
OR1000LCDRM1U / OR1500LCDRM1U
User’s Manual
K01-0000053-01
(SAVE THESE INSTRUCTIONS)
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please
read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to
unpack, install, or operate.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive
contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no user serviceable parts
inside, except for the battery.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into
an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the UPS.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a
computer component.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support
or medical applications. DO NOT use in any circumstance that would affect the operation or safety of any life support equipment, with any
medical applications, or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from
the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation
such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out.
INTRODUCTION
Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and
performance during the lifetime of the product.
UNPACKING
Inspect the UPS upon receipt. The box should contain the following:
(a) UPS unit (b) User’s manual (c) Rack mount brackets (d)Telephone cable (e) PowerPanel® Business Edition software CD (f) Serial interface
cable (DB-9) (g) USB A+B type cable (h) Warranty registration card
OVERVIEW
The OR1000LCDRM1U/OR1500LCDRM1U UPS provides complete power protection from utility power that isn't always consistent. The
OR1000LCDRM1U/OR1500LCDRM1U features surge protection against power surges and
maintenance free batteries for long lasting battery backup during power outages. In addition to
ensuring consistent power to your computer system and the OR1000LCDRM1U/OR1500LCDRM1U
also includes software that will automatically save your open files and shutdown your computer
system during a utility power loss.
AUTOMATIC VOLTAGE REGULATOR
The OR1000LCDRM1U/OR1500LCDRM1U stabilizes inconsistent utility power voltage to nominal
levels that are safe for equipment. Inconsistent utility power may be damaging to important data files
and hardware, but with Automatic Voltage Regulation (AVR), damaging voltage levels are corrected
to safe levels. AVR automatically increases low utility power or decreases high utility power to a
consistent and safe 110/120 volts.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Ensure that the equipment plugged into the outlets does not exceed the UPS unit’s rated capacity (1000VA/600W for OR1000LCDRM1U,
1500VA/900W for OR1500LCDRM1U). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the
UPS unit to shut down or the circuit breaker to trip.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least eight hours is recommended to ensure
that the battery's maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery,
simply leave the unit plugged into an AC outlet. The unit will charge in both the on and off position.
2. If you will use the software, connect the USB cable to the USB port on the UPS.
3. With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device (Zip drive, Jazz drive,
Tape drive, etc.) into the battery power supplied outlets. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or
other large electrical device into the UPS. The power demands of these devices will overload and
possibly damage the unit.
4. To protect a fax, telephone, modem line or network cable, connect a telephone cable or network cable from
the wall jack outlet to the IN jack of the UPS. Then connect a telephone cable or network cable from the
OUT jack on the UPS to the modem, computer, telephone, fax machine, or network device.
5. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g.
air conditioner, refrigerator, copier, etc.). Avoid using extension cords.
6. Depress the power switch to turn the unit on. The power on indicator light will illuminate and the unit will
"beep" once.
7. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at
least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker is depressed and then
turn the UPS on.
8. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically recharge.
9. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
10. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to
ensure battery life.
DESCRIPTION
1. LCD module display
LCD shows all the UPS information with icons and
messages.
2. Power On Indicator
This LED is illuminated when the utility condition is
normal and the UPS outlets are providing power,
free of surges and spikes.
3. Power Switch
Master on/off switch for equipment connected to
the battery power supplied outlets.
4. LCD function selected switch
The switch can be used to select the LCD display contents Including input/output voltage and estimated run time, etc.
5. Battery and Surge Protected Outlets
The unit has four battery powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your
equipment during a power failure. (DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum cleaner, sump pump or
other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and
damage the unit.)
6. Full-Time Surge Protection Outlets
The unit has two surge suppression outlets.
7. Communication Protection Ports RJ11/RJ45
Communication protection ports will protect any standard modem, fax, telephone line, or network cable.
8. USB Port to PC
This port allows connection and communication from the USB port on the computer to the UPS unit. The UPS communicates its status to the
PowerPanel® Business Edition software.
9. Dry contact
This port produces information for equipment that can read dry contact signals.
10. Circuit Breaker
Located on the back of the UPS, the circuit breaker serves to provide overload and fault protection. Under normal operating conditions, the circuit
breaker is depressed.
11. Electrical Wiring Fault Indicator
This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missed ground or reversed wiring. If this is
illuminated, disconnect all electrical equipment from the outlet and have an electrician check to ensure the outlet is properly wired.
12. AC Input
Connect the AC Power cord to a properly wired and grounded outlet.
13. SNMP/HTTP Network Slot
Remove the cover panel to install an optional RMCARD provides remote monitoring and management of your UPS over a network.
REPLACING THE BATTERY
CAUTION! IMPORTANT SAFETY INSTRUCTIONS Read and follow the before servicing the battery.
Service the battery under the supervision of personnel knowledgeable of batteries and their precautions.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as they may explode. Follow all local
ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the
battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. lay tools or other metal parts on top of battery or any battery terminals. DO NOT
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED
BATT ERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit).
BATT ERY REPLACEMENT PROCEDURE:
Line mode
Select SW
Press
UPS Status Display Capacity Display Digital Value Display
Load
Cap.
Battery
Cap.
Input
Voltage
Output
Voltage
Run
Time
% of
Load
% of
Batt.
Initial V X -- X V X V
1st V X -- X V X V
2nd V X -- X V X V
3rd V X -- X X V V
4th V X -- X V X V
5th(Return) V X -- X V X V
Press >3sec
(Sound Disable) V X V X -- -- -- -- -- -- --
Press >3sec
Again
(Sound Enable)
V X X X -- -- -- -- -- -- --
(Overload) V X -- V -- -- -- -- -- -- --
"V" : Illuminated, "X" : Not Illuminated, "--" : Either
Battery mode
Select SW
Press
UPS Status Display Capacity Display Digital Value Display
Load
Cap.
Battery
Cap.
Input
Voltage
Output
Voltage
Run
Time
% of
Load
% of
Batt.
Initial X V -- X X V V
1st X V -- X X V V
2nd X V -- X V X V
3rd X V -- X X V V
4th X V -- X X V V
5th(Return) X V -- X X V V
Press >3sec
(Sound Disable) X V V X -- -- -- -- -- -- --
Press >3sec
again(Sound
Enable)
X V X X -- -- -- -- -- -- --
(Overload) X V -- V -- -- -- -- -- -- --
"V" : Illuminated, "X" : Not Illuminated, "--" : Either
BASIC OPERATION
INSTALLING YOUR UPS SYSTEM
IMPORTANT SAFETY WARNINGS
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
1. Remove the right-side of the faceplate.
2.
Remove the three retaining screws on
the cable protection cover then remove
the cover.
cable.
4. Remove the retaining screw of the cable
connectors.
5. Replace the new battery pack. Assemble
the screws, cover, cable and front panel in
the reverse sequence of above steps.
Recharge the unit for 8 hours to ensure
the UPS performs expected runtime.


Produkt Specifikationer

Mærke: CyberPower
Kategori: Uafbrydelig strømforsyning (UPS)
Model: OR1500LCDRM1U
Vægt: 20683 g
Responstid: 4 ms
Relativ luftfugtighed ved drift (H-H): 0 - 95 %
Ethernet LAN-porte (RJ-45): 1
Antal USB 2.0-porte: 1
Driftstemperatur (T-T): 32 - 95 °F
Dimensioner (BxDxH): 438.15 x 235 x 44.45 mm
Udgangseffekt: 900 W
Certificering: UL1778, cUL 107.1, FCC DOC Class B
Opladningstid for batteri: 8 t
Lydalarmer: Ja
Input forbindertype: NEMA 5-15P
Antal serielle porte: 1
Vægt (efter britisk standard): 45.6 Pund
Output-forbindere: NEMA 5-15R
Dimensioner (BxDxH) (efter britisk standard): 17.25 x 19.5 x 1.75 "
Modem-porte (RJ-11): 1
Overspænding energivurdering: 1030 J
Output strømkapacitet (VA): 1.5 kVA
Typisk backup tid ved halv styrke: 11 min.
Typisk backup tid ved fuld styrke: 2 min.
Udskiftningsbatteri: BB - HR9-6

Har du brug for hjælp?

Hvis du har brug for hjælp til CyberPower OR1500LCDRM1U stil et spørgsmål nedenfor, og andre brugere vil svare dig




Uafbrydelig strømforsyning (UPS) CyberPower Manualer

Uafbrydelig strømforsyning (UPS) Manualer

Nyeste Uafbrydelig strømforsyning (UPS) Manualer