Daikin ARXM71A5V1B Manual


Læs nedenfor 📖 manual på dansk for Daikin ARXM71A5V1B (80 sider) i kategorien Ikke kategoriseret. Denne guide var nyttig for 41 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/80
Installer reference guide
R32 split series
RXA42B5V1B8
RXA50B5V1B8
RXM50A5V1B9
RXM60A5V1B
RXM71A5V1B
ARXM50A5V1B9
ARXM60A5V1B
ARXM71A5V1B
RXP50N5V1B9
RXP60N5V1B9
RXP71N5V1B9
RXF50D6V1B
RXF60D5V1B9
RXF71D5V1B9
ARXF50A6V1B
ARXF60A5V1B9
ARXF71A5V1B9
RZAG35B5V1B
RZAG50B5V1B
RZAG60B5V1B
Table of contents
Installer reference guide
2
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
Table of contents
1 About the documentation 4
1.1 About this document...................................................................................................................................................... 4
1.1.1 Meaning of warnings and symbols................................................................................................................ 5
2 General safety precautions 7
2.1 For the installer .............................................................................................................................................................. 7
2.1.1 General........................................................................................................................................................... 7
2.1.2 Installation site............................................................................................................................................... 8
2.1.3 Refrigerant — in case of R410A or R32......................................................................................................... 11
2.1.4 Electrical......................................................................................................................................................... 12
3 Specific installer safety instructions 15
4 About the box 21
4.1 Outdoor unit................................................................................................................................................................... 21
4.1.1 To unpack the outdoor unit........................................................................................................................... 21
4.1.2 To handle the outdoor unit ........................................................................................................................... 21
4.1.3 To remove the accessories from the outdoor unit....................................................................................... 22
5 About the unit 23
5.1 Identification .................................................................................................................................................................. 23
5.1.1 Identification label: Outdoor unit.................................................................................................................. 23
6 Unit installation 24
6.1 Preparing the installation site ........................................................................................................................................ 24
6.1.1 Installation site requirements of the outdoor unit ....................................................................................... 25
6.1.2 Additional installation site requirements of the outdoor unit in cold climates ........................................... 27
6.2 Opening the unit ............................................................................................................................................................ 28
6.2.1 About opening the unit.................................................................................................................................. 28
6.2.2 To open the outdoor unit .............................................................................................................................. 28
6.3 Mounting the outdoor unit............................................................................................................................................ 28
6.3.1 About mounting the outdoor unit................................................................................................................. 28
6.3.2 Precautions when mounting the outdoor unit ............................................................................................. 29
6.3.3 To provide the installation structure............................................................................................................. 29
6.3.4 To install the outdoor unit............................................................................................................................. 30
6.3.5 To provide drainage....................................................................................................................................... 30
6.3.6 To prevent the outdoor unit from falling over.............................................................................................. 31
7 Piping installation 32
7.1 Preparing refrigerant piping........................................................................................................................................... 32
7.1.1 Refrigerant piping requirements ................................................................................................................... 32
7.1.2 Refrigerant piping insulation ......................................................................................................................... 33
7.1.3 Refrigerant piping length and height difference........................................................................................... 33
7.2 Connecting the refrigerant piping.................................................................................................................................. 34
7.2.1 About connecting the refrigerant piping ...................................................................................................... 34
7.2.2 Precautions when connecting the refrigerant piping ................................................................................... 34
7.2.3 Guidelines when connecting the refrigerant piping ..................................................................................... 35
7.2.4 Pipe bending guidelines................................................................................................................................. 36
7.2.5 To flare the pipe end ..................................................................................................................................... 36
7.2.6 Using the stop valve and service port ........................................................................................................... 37
7.2.7 To connect the refrigerant piping to the outdoor unit................................................................................. 39
7.3 Checking the refrigerant piping ..................................................................................................................................... 39
7.3.1 About checking the refrigerant piping .......................................................................................................... 39
7.3.2 Precautions when checking the refrigerant piping....................................................................................... 39
7.3.3 To check for leaks .......................................................................................................................................... 40
7.3.4 To perform vacuum drying ............................................................................................................................ 40
8 Charging refrigerant 42
8.1 About charging refrigerant............................................................................................................................................. 42
8.2 About the refrigerant ..................................................................................................................................................... 43
8.3 Precautions when charging refrigerant ......................................................................................................................... 44
8.4 To determine the additional refrigerant amount.......................................................................................................... 44
8.5 To determine the complete recharge amount.............................................................................................................. 44
8.6 To charge additional refrigerant.................................................................................................................................... 45
8.7 To check refrigerant piping joints for leaks after charging refrigerant......................................................................... 45
8.8 To fix the fluorinated greenhouse gases label............................................................................................................... 45
Table of contents
Installer reference guide
3
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
9 Electrical installation 47
9.1 About connecting the electrical wiring.......................................................................................................................... 47
9.1.1 Precautions when connecting the electrical wiring...................................................................................... 47
9.1.2 Guidelines when connecting the electrical wiring ........................................................................................ 48
9.1.3 Specifications of standard wiring components............................................................................................. 50
9.2 To connect the electrical wiring to the outdoor unit .................................................................................................... 50
10 Finishing the outdoor unit installation 52
10.1 To finish the outdoor unit installation ........................................................................................................................... 52
10.2 To close the outdoor unit............................................................................................................................................... 52
11 Configuration 54
11.1 Facility setting................................................................................................................................................................. 54
11.1.1 To set the facility mode ................................................................................................................................. 54
11.2 Standby electricity saving function................................................................................................................................ 54
11.2.1 About the standby electricity saving function .............................................................................................. 54
11.2.2 To turn ON standby electricity saving function............................................................................................. 55
12 Commissioning 56
12.1 Precautions when commissioning ................................................................................................................................. 56
12.2 Checklist before commissioning .................................................................................................................................... 57
12.3 Checklist during commissioning..................................................................................................................................... 57
12.4 To perform a test run ..................................................................................................................................................... 57
12.5 Starting up the outdoor unit.......................................................................................................................................... 58
13 Hand-over to the user 59
14 Maintenance and service 60
14.1 Overview: Maintenance and service.............................................................................................................................. 60
14.2 Maintenance safety precautions ................................................................................................................................... 61
14.3 Checklist for yearly maintenance of the outdoor unit .................................................................................................. 61
14.4 About the compressor ................................................................................................................................................... 61
15 Troubleshooting 63
15.1 Overview: Troubleshooting............................................................................................................................................ 63
15.2 Precautions when troubleshooting................................................................................................................................ 63
15.3 Solving problems based on symptoms .......................................................................................................................... 63
15.3.1 Symptom: Indoor units fall, vibrate or make noise....................................................................................... 63
15.3.2 Symptom: The unit is NOT heating or cooling as expected.......................................................................... 64
15.3.3 Symptom: Water leakage .............................................................................................................................. 64
15.3.4 Symptom: Electrical leakage.......................................................................................................................... 64
15.3.5 Symptom: Unit does NOT function or burn damage .................................................................................... 64
15.4 Fault diagnosis using LED on outdoor unit PCB............................................................................................................. 64
16 Disposal 66
16.1 Overview: Disposal......................................................................................................................................................... 66
16.2 To pump down ............................................................................................................................................................... 66
16.3 To start and stop forced cooling .................................................................................................................................... 67
16.3.1 To start and stop forced cooling using the indoor unit ON/OFF switch....................................................... 67
16.3.2 To start and stop forced cooling using the indoor unit user interface......................................................... 67
17 Technical data 68
17.1 Wiring diagram ............................................................................................................................................................... 68
17.1.1 Unified wiring diagram legend ...................................................................................................................... 68
17.2 Piping diagram................................................................................................................................................................ 71
17.2.1 Piping diagram: Outdoor unit........................................................................................................................ 71
18 Glossary 76
1 About the documentation |
Installer reference guide
4
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
1 About the documentation
1.1 About this document
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow
the instructions from Daikin (including all documents listed in “Documentation set”)
and, in addition, comply with applicable legislation and are performed by qualified
persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is
the applicable standard.
INFORMATION
Make sure that the user has the printed documentation and ask him/her to keep it
for future reference.
Target audience
Authorised installers
INFORMATION
This document only describes installation instructions specific to the outdoor unit.
For installation of the indoor unit (mounting the indoor unit, connecting the
refrigerant piping to the indoor unit, connecting the electrical wiring to the indoor
unit …), see the installation manual of the indoor unit.
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
-Safety instructions that you MUST read before installing
-Format: Paper (in the box of the outdoor unit)
Outdoor unit installation manual:
-Installation instructions
-Format: Paper (in the box of the outdoor unit)
Installer reference guide:
-Preparation of the installation, reference data,
-Format: Digital files on . Use the search function tohttps://www.daikin.eu
find your model.
The latest revision of the supplied documentation is published on the regional
Daikin website and is available via your dealer.
Scan the QR code below to find the full documentation set and more information
about your product on Daikin website.
ARXF-A
ARXF-A9
ARXM-A
ARXM-A9
1 About the documentation |
Installer reference guide
5
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
RXF-D
RXF-D9
RXP-N9
RXM-A9
RXM-A
RXA-B8
RZAG-B
The original instructions are written in English. All other languages are translations
of the original instructions.
Technical engineering data
A of the latest technical data is available on the regional Daikin websitesubset
(publicly accessible).
The of the latest technical data is available on the Daikin Business Portalfull set
(authentication required).
1.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or
cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
1 About the documentation |
Installer reference guide
6
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
Symbol Explanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
For more information, see the installer and user reference
guide.
The unit contains rotating parts. Be careful when servicing or
inspecting the unit.
Symbols used in the documentation:
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
2 General safety precautions |
Installer reference guide
7
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
2 General safety precautions
2.1 For the installer
2.1.1 General
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return
to normal temperature. If you MUST touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in
electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY
use accessories, optional equipment and spare parts made or approved by Daikin
unless otherwise specified.
WARNING
Make sure installation, testing and applied materials comply with applicable
legislation (on top of the instructions described in the Daikin documentation).
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially NOT
children, can play with them. suffocation.Possible consequence:
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.
Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to
avoid water ingress.
2 General safety precautions |
Installer reference guide
9
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
WARNING
Take precautions to avoid excessive vibration or pulsation to refrigeration piping.
Protect the protection devices, piping and fittings as much as possible against
adverse environmental effects.
Provide space for expansion and contraction of long runs of piping.
Design and install piping in refrigerating systems such as to minimise the
likelihood of hydraulic shock damaging the system.
Mount the indoor equipment and pipes securely and protect them to avoid
accidental rupture of equipment or pipes in case of events such as moving
furniture or reconstruction activities.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the
minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;
air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant
leaks.
NOTICE
Do NOT re-use joints and copper gaskets which have been used already.
Joints made in the installation between parts of the refrigerant system shall be
accessible for maintenance purposes.
Installation space requirements
WARNING
If appliances contain R32 refrigerant, the floor area of the room in which the
appliances are installed, operated and stored MUST be larger than the minimum
floor area defined in table below A (m2). This applies to:
Indoor units a refrigerant leakage sensor; in case of indoor units without with
refrigerant leakage sensor, consult the installation manual
Outdoor units installed or stored indoors (e.g. winter garden, garage, machinery
room)
NOTICE
The pipework shall be securely mounted and guarded protected from physical
damage.
Keep the pipework installation to a minimum.
To determine the minimum floor area
1Determine the total refrigerant charge in the system (= factory refrigerant
charge + additional refrigerant amount charged).
2 General safety precautions |
Installer reference guide
10
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
Contains fluorinated greenhouse gases
2
11
1
2
2kg
tCO
2
eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
2Determine which graph or table to use.
For indoor units: Is the unit ceiling-mounted, wall-mounted or floor-
standing?
For outdoor units installed or stored indoors, this depends on the installation
height:
If the installation height is… Then use the graph or table for…
<1.8m Floor-standing units
1.8≤x<2.2m Wall-mounted units
≥2.2m Ceiling-mounted units
3Use the graph or table to determine the minimum floor area.
0
10
20
30
40
50 60
70 80
90100
110
120
130140
150160
170180
190200
210
220
230
240
250
260
270
280
290
300
310320
330340
350360
370380
390
400
410
420
430
440
450
460
470
480
490
500
510520
530
540
550560
570580
590600
610
620
630
640
650
660
670
680
690
700
710720
730
740
750760
770
1.843
9.55
2.21.8 2.4 2.8 3.2 3.6 4 4.4 4.8 5.2 5.6 6 6.4 6.8 7.2 7.6 8 8.4 8.8 9.22
2.6 3 3.4 3.8 4.2 4.6 5 5.4 5.8 6.2 6.6 7 7.4 7.8 8.2 8.6 9 9.4
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m [kg]
Amin [m2]
Ceiling-mounted
unit(a)
4.6 13.4 4.6 180
4.8 14.6 4.8 196
5.0 15.8 5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3 4.4 165
m (kg) Amin (m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
8 40.5
8.2 42.6
8.4 44.7
8.6 46.8
8.8 49.0
9 51.3
9.2 53.6
9.4 55.9
9.55 57.7
8 60.5
8.2 63.6
8.4 66.7
8.6 69.9
8.8 73.2
9 76.6
9.2 80.0
9.4 83.6
9.55 86.2
8 545
8.2 572
8.4 601
8.6 629
8.8 659
9 689
9.2 720
9.4 752
9.55 776
Wall-mounted
unit(b)
m (kg) Amin (m2)
Floor-standing
unit(c)
m (kg) Amin (m2)
mTotal refrigerant charge in the system
Amin Minimum floor area
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)
2 General safety precautions |
Installer reference guide
11
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
2.1.3 Refrigerant — in case of R410A or R32
If applicable. See the installation manual or installer reference guide of your
application for more information.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Self-Possible consequence:
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
During tests, NEVER pressurise the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may ONLY be charged after
performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of
oxygen going into the operating compressor.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
2 General safety precautions |
Installer reference guide
14
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
Install power cables at least 1 meter away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 meter may NOT be
sufficient.
NOTICE
ONLY applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes ON and OFF while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.


Produkt Specifikationer

Mærke: Daikin
Kategori: Ikke kategoriseret
Model: ARXM71A5V1B

Har du brug for hjælp?

Hvis du har brug for hjælp til Daikin ARXM71A5V1B stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Daikin Manualer

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer