DSC PG9985 Manual
Læs nedenfor 📖 manual på dansk for DSC PG9985 (4 sider) i kategorien Detektor. Denne guide var nyttig for 5 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere
Side 1/4
PG9985/PG8985/PG4985
PowerG Wireless Flood Detector Installation
Instructions
Operation
The PG9985/PG8985/PG4985 are fully supervised two-way,
indoor PowerG flood detectors. The PG9985/PG8985/
PG4985 continuously monitor for unacceptable water levels.
If water is detected (e.g., when both probes are in contact
with the water), the PG9985/PG8985/PG4985 wirelessly
communicates an alarm condition to the alarm system.
The tamper switch is activated when the cover is removed. In
addition, the device sends a probe disconnection alert upon
the detection of a probe terminal connection failure.
An LED lights whenever alarm or tamper events are reported.
The LED does not light while a supervision message is being
transmitted.
Operating power is obtained from a 3V Lithium battery.
When the battery voltage is low, a “low battery” message is
sent to the receiver.
After every flood detection, each flood detector should be
cleaned and dried.
Device Setup
Caution! To be installed by service persons in non-hazardous
locations only. Risk of explosion if battery is replaced by an
incorrect type. Observe polarity when installing batteries.
Dispose of used batteries according to the manufacturer's
instructions and according to local rules and regulations.
Note: To ensure the continued operation of all wireless
devices after performing a system default, a global upload of
all wireless programming via DLS is recommended before
defaulting the system. After completing the system default,
download the wireless programming.
Legend
A. Transmission LED
B. Terminal block for sensor
C. Enroll button
D. Tamper switch
E. Mounting holes
F. Break-away tamper
Install the battery
1. Insert a flat-edged screw-
driver into the slot and
push upward to remove
cover.
2. Remove the screw
and separate the
cover from the base.
3. Observe polarity
and install battery.
4. Connect the sensor wire to the
terminal block.
Note: When manually programming
wireless devices, if a device has
been powered up for more than 48
hours it cannot be enrolled into the
system until the device has been
tampered and restored. When programming the panel using
the Quick Enroll procedure follow the steps detailed in Enroll
the Device into the System.
Note: After restoring a low battery trouble the system may
take up to 5 minutes to clear the trouble.
Enroll the Device into the System
To quick enroll:
1. On a keypad press [*] [8] [Installer Code] [804] [000].
2. Press and hold the device enroll button until the LED
lights steady and then release the enroll button while the
LED is still lit. A confirmation message then appears on
the keypad.
3. Press [*] key to confirm ID.
4. Enter [3 digit zone #].
5. Enter [3 digit zone type].
6. Enter [1 digit partition #] for all desired partitions and
press [#]. If using an LCD keypad you can scroll to the
desired partitions and press [*] to toggle the partition.
7. On an LCD keypad enter the label by using word library.
To pre-enroll:
1. Remotely configure the unique ID number into the sys-
tem. For more information see the HSM2HOST manual.
2. When on-site, press the device enroll button.
Note: If the wireless device has been powered for more than
48 hours without being enrolled, tamper and restore the
device to enroll it.
Perform a placement test
Before permanently mounting any wireless device, temporar-
ily mount the device and perform a Placement test with the
water sensor connected.
1. Tamper the device.
2. Restore the tamper. The device now enters Placement
test mode for 15 minutes.
3. The red LED blinks once to identify that a signal is being
sent to the receiver and then blinks three times to identify
the signal strength. The following table indicates the
received signal strength.
IMPORTANT! Only GOOD or STRONG signal strengths
are acceptable. If you receive a POOR signal from the device,
re-locate it and re-test until a GOOD or STRONG signal is
received.
Note: For UL/ULC installations, only STRONG signal levels
are acceptable. After installation verify the product function-
ality in conjunction with the compatible receivers
HSM2HOST9, HS2LCDRF(P)9, HS2ICNRF(P)9 and
PG9920.
Note: For detailed Placement instructions refer to the control
panel Reference Guide.
Mount the Device
Notes: Avoid mounting the transmitter portion of the device
behind a metal object such as a washing machine, refrigera-
tor, or freezer. RF signals can be affected by metal objects.
After every flood detection, each flood detector should be
cleaned and dried. Otherwise, the unit may not operate as
intended due to the nature of different liquids.
Note: Adhesive tape not to be used for EU Market.
1. Install the flood sensor in the lowest point in the room or
where water is expected to pool with at least 2 supplied
screws. The flood sensor must be mounted so both
probes of the device are touching water when an alarm
condition is desired.
2. Secure the flood sensor cable to the wall. The flood sen-
sor should be installed only in a vertical position and fac-
ing downward.
3. Attach the flood transmitter to the wall. The flood trans-
mitter should be placed as high up as possible on the wall
to improve communication and to prevent the flood
detector itself from coming into contact with water in the
event of flooding.
4. Remove the PCB board.
5. Mark and drill 2 holes
in the mounting sur-
face and fasten the
base with 2 counter-
sunk screws. If using
the break-away tam-
per, secure with an
additional screw.
6. Reattach the PCB, and
reattach the cover to
the base.
Note: External wiring shall be routed and protected in a man-
ner that prevents:
• excessive strain on wire and terminal connections
• loosening of terminal connections
• damage of conductor insulation
• developing any other type of hazard (e.g. tripping due
to loose cables.)
Configuration
To enter the wireless configuration section enter [804][Zone
Number].
Device Toggles
Specifications
Frequency Band: CE Listed PG4985: 433MHz; CE/EN
listed PG8985: 868MHz; FCC/IC/UL/ULC listed PG9985:
912-919 MHz
Communication Protocol: PowerG
Alarm Input: External flood probe
Supervision: Signaling at 4-min. intervals
Battery type: 3 V Lithium CR-123 type battery, Panasonic
or GP only.
Battery Life Expectancy: 8 years (not tested by UL/ULC)
Low Battery Threshold: 2.2 V
Battery Supervision: Automatic transmission of battery
condition data as part of periodic status report and immedi-
ately upon low battery condition detection.
Temperature Range: -10°C to +55°C (UL/ULC only veri-
fied the range 0° to 49°C)
Humidity: up to max. 93%RH, non-condensing
Dimensions:
(LxWxD)81 x 34 x 25 mm (3-3/16 x 1-1/4 x 1 in.)
Weight (including battery): 53g (1.9 oz)
Compatible Receivers
433MHz Band: HSM2HOST4; HS2LCDRF(P)4;HS2IC-
NRF(P)4; PG4920
868MHz Band: HSM2HOST8; HS2LCDRF(P)8; HS2IC-
NRF(P)8;PG8920
912-919MHz Band: HSM2HOST9; HS2LCDRF(P)9;
HS2ICNRF(P)9; PG9920
Note: Only devices operating in band 912-919MHz are UL/
ULC listed.
UL/ULC Notes
Only model PG9985 operating in the frequency band 912-919MHz are UL/ULC listed. The PG9985 has
been listed by UL//cUL under UL2017 requirements.
For UL/ULC installations use these devices only in conjunction with compatible DSC wireless receivers:
HSM2HOST9, HS2LCDRF(P)9, HS2ICNRF(P)9 and PG9920. After installation verify the product
functionality in conjunction with the compatible receiver used.
Europe: The PG8985 and PG4985 are compliant with the RTTE requirements -
Directive 1999/5/EC of the European Parliament and of the Council of 9 March 1999.
The Power G peripheral devices have two- way communication functionality,
providing additional benefits as described in the technical brochure. This
functionality has not been tested to comply with the respective technical requirements and should
therefore be considered outside the scope of the product’s certification
FCC COMPLIANCE STATEMENT
WARNING! Changes or modifications to this unit not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.
This device has been tested and found to comply with the limits for a Class B digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in residential installations. This equipment generates uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio and television reception.
However, there is no guarantee that interference will not occur in a particular installation. If this device
does cause such interference, which can be verified by turning the device off and on, the user is
encouraged to eliminate the interference by one or more of the following measures:
– Re-orient or re-locate the receiving antenna.
– Increase the distance between the device and the receiver.
– Connect the device to an outlet on a circuit different from the one that supplies power to the receiver.
– Consult the dealer or an experienced radio/TV technician.
This equipment complies with FCC and IC RF radiation exposure limits set forth for an uncontrolled
environment.
This device complies with FCC Rules Part 15 and with Industry Canada licence-exempt RSS standard(s).
Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference that may be received or that may cause undesired
operation.
Le present appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de
licence. L'exploitation est autorisee aux deux conditions suivantes :(1) l'appareil ne doit pas produire de
brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioelectrique subi, meme si le
brouillage est susceptible d'en compromettre le fonctionnement.
PG9985/PG8985/PG4985
Instructions d'installation du détecteur d'inonda-
tion au sol sans fil de la gamme PowerG
Fonctionnement
Les PG9985/PG8985/PG4985 sont des détecteurs d'inonda-
tion d'intérieur, bidirectionnels, sans fil, entièrement sur-
veillés de la gamme PowerG. Les PG9985/PG8985/PG4985
surveillent de façon continue les niveaux d'eau inacceptables.
Si de l'eau est détectée (par exemple, quand les deux sondes
sont en contact avec de l'eau), les PG9985/PG8985/PG4985
communiquent par liaison sans fil un état d'alarme au sys-
tème d'alarme.
Le contact anti-sabotage est activé quand le couvercle est
retiré. En plus, il transmet une alerte de déconnexion de la
sonde à la suite de la détection d'un problème de connexion
d'une borne de la sonde.
Un voyant lumineux s'allume chaque fois que des événe-
ments de sabotage ou d'alarme sont signalés. Le voyant
lumineux ne s'allume pas alors qu'un message de surveillance
est en cours de transmission.
L'alimentation est fournie par une pile au lithium de 3 V.
Quand la tension de la pile est faible, un message de niveau
faible de pile est transmis au récepteur.
Après chaque détection d'inondation, chaque détecteur
d'inondation doit être nettoyé et séché.
Réglage du dispositif
Attention ! À faire installer par un agent de service dans des
zones non dangereuses uniquement. Risque d'explosion si la
pile n'est pas du type correct. Respecter les polarités lors de
l'installation des piles. Éliminer les piles usagées selon les
recommandations du fabricant, les lois et réglementations
locales.
Remarque : Pour garantir le fonctionnement continu de tous
les dispositifs sans fil après avoir réalisé une réinitialisation aux
valeurs par défaut, un téléchargement général de toute la pro-
grammation sans fil par DLS est recommandé avant de réini-
tialiser le système. Après avoir complété la réinitialisation aux
valeurs par défaut du système, téléchargez la programmation
sans fil.
Légende
A. Voyant lumineux de transmission
B. Bornier du capteur
C. Bouton d'attribution
D. Contact anti-sabotage
E. Trous de fixation
F. Contact anti-sabotage
Installer la pile
1. Insérez un tournevis plat
dans la fente et poussez
vers le haut pour retirer le
couvercle.
2. Retirez la vis et
détachez le
couvercle de la
base.
3. Respectez les
polarités et installez la pile.
4. Branchez les fils du détecteur
au bornier.
Remarque : Quand vous program-
mez manuellement les dispositifs
sans fil, si un dispositif a été ali-
menté pendant plus de 48 heures, il
ne peut pas être attribué dans le sys-
tème tant que le dispositif n'a pas été saboté et rétabli.
Remarque: Après la restauration d'un défaut de batterie
faible, le système peut prendre jusqu'à 5 minutes pour que la
peine.
Attribuez le dispositif dans le système
Pour une attribution rapide :
1. Sur le pavé numérique, appuyez sur [*] [8] [Code de
l'installateur] [804] [000].
2. Appuyez de façon prolongée sur le bouton d'attribution
du dispositif tant que le voyant lumineux reste allumé,
puis relâchez- le bouton d'attribution alors que le voyant
lumineux est encore allumé. Un message de
confirmation apparaît alors sur le pavé numérique.
3. Appuyez sur la touche [*] pour confirmer le ID.
4. Entrez le [n° de zone à 3 chiffres].
5. Entrez les [3 chiffres de type de zone].
6. Entrez le [n° de partition à 1 chiffre] pour toutes les
partitions souhaitées et appuyez sur [#]. Si vous utilisez
un pavé numérique à cristaux liquides LCD, vous pouvez
faire défiler les partitions souhaitées et appuyer sur [*]
pour basculer la partition.
7. Sur un pavé numérique LCD, entrez la référence en
utilisant la bibliothèque de mot.
Pour une attribution préalable :
1. Configurez à distance le numéro ID unique dans le
système. Pour plus d'informations, consultez le manuel
HSM2HOST.
2. Sur site, appuyez sur le bouton d'attribution du dispositif.
Remarque : Si le dispositif sans fil a été alimenté pendant
plus de 48 heures sans être attribué, sabotez et rétablissez le
dispositif pour l'attribuer.
Réalisation d'un test de positionnement
Avant de fixer de façon permanente un dispositif sans fil
quelconque, montez-le temporairement et effectuez un test de
positionnement avec le détecteur d'inondation connecté.
1. Sabotez le dispositif.
2. Rétablissez le système anti-sabotage. Le dispositif passe
en mode de test de positionnement pendant 15 minutes.
3. Le voyant lumineux rouge clignote une fois pour
indiquer qu'un signal est transmis au récepteur, puis
clignote trois fois pour fournir la force du signal. Le
tableau suivant décrit la force de signal reçu.
IMPORTANT ! Seules les forces de signal FORT ou BON
sont acceptables. Si vous recevez un signal FAIBLE du dis-
positif, déplacez-le et testez-le à nouveau jusqu'à ce qu'un
signal BON ou FORT soit reçu.
A
+
-
C
D
B
LED response Signal Strength
Green LED blinks STRONG
Orange LED blinks GOOD
Red LED blinks POOR
No blinks No communication
Floor
Avoid locating
near metal
objects
SENSOR
WIRE
TRANSMITTER
DG009365
SENSOR
Washing
Machine
[001][04] Supervision - Default [Y]
Enables supervision of the device.
E
F
Réponse du voyant Force du signal
Le voyant vert clignote FORT
Le voyant orange clignote BON
Le voyant rouge clignote FAIBLE
Aucun clignotement Aucune communication
A
+
-
C
D
B
D-304678
Produkt Specifikationer
Mærke: | DSC |
Kategori: | Detektor |
Model: | PG9985 |
Har du brug for hjælp?
Hvis du har brug for hjælp til DSC PG9985 stil et spørgsmål nedenfor, og andre brugere vil svare dig
Detektor DSC Manualer
13 September 2024
1 August 2024
28 Juli 2024
27 Juli 2024
21 Juli 2024
Detektor Manualer
- Detektor Bosch
- Detektor Denver
- Detektor Hager
- Detektor Extech
- Detektor Ei Electronics
- Detektor Silverline
- Detektor Skil
- Detektor Pioneer
- Detektor Soler & Palau
- Detektor Garmin
- Detektor Pyle
- Detektor Nedis
- Detektor Abus
- Detektor Edimax
- Detektor Optex
- Detektor Smartwares
- Detektor Kyoritsu
- Detektor Laserliner
- Detektor Black And Decker
- Detektor Dometic
- Detektor Busch-Jaeger
- Detektor Trotec
- Detektor Honeywell
- Detektor Uniden
- Detektor König
- Detektor FireAngel
- Detektor Elro
- Detektor Steinel
- Detektor Powerfix
- Detektor Maginon
- Detektor Tripp Lite
- Detektor Mercury
- Detektor Genie
- Detektor National Geographic
- Detektor Alecto
- Detektor Olympia
- Detektor Techly
- Detektor B/R/K
- Detektor Voltcraft
- Detektor GEV
- Detektor Testboy
- Detektor Cobra
- Detektor Velleman
- Detektor FLIR
- Detektor JUNG
- Detektor Byron
- Detektor Vemer
- Detektor ORNO
- Detektor Netatmo
- Detektor Amprobe
- Detektor Fluke
- Detektor Hikvision
- Detektor Sun Joe
- Detektor Gossen
- Detektor Pentatech
- Detektor Testo
- Detektor Grothe
- Detektor Siedle
- Detektor Evolveo
- Detektor Multimetrix
- Detektor Axis
- Detektor X-Sense
- Detektor Vimar
- Detektor Dahua Technology
- Detektor ZKTeco
- Detektor Joy-It
- Detektor Nexa
- Detektor HT Instruments
- Detektor AcuRite
- Detektor Homematic IP
- Detektor V-TAC
- Detektor Schwaiger
- Detektor Beha-Amprobe
- Detektor Bearware
- Detektor Ferguson
- Detektor Inovonics
- Detektor AngelEye
- Detektor Royal Sovereign
- Detektor Marquant
- Detektor Safescan
- Detektor Xavax
- Detektor X4-Tech
- Detektor FireX
- Detektor Iget
- Detektor Satel
- Detektor Garrett
- Detektor Kreator
- Detektor Gamma Scout
- Detektor Winland
- Detektor Escort
- Detektor Ebode
- Detektor System Sensor
- Detektor Guardian Avionics
- Detektor Thitronik
- Detektor Whistler
- Detektor Cavius
- Detektor PCE Instruments
- Detektor Flow Smoke Detector
- Detektor Benewake
- Detektor BeeSecure
- Detektor Fisher
- Detektor SureCall
- Detektor STI
- Detektor Schabus
- Detektor Zircon
- Detektor Sanwa
- Detektor Minelab
- Detektor Resideo
- Detektor BlendMount
- Detektor K40
- Detektor Gewiss
- Detektor Seco-Larm
- Detektor Silent Knight
- Detektor S.E. International
- Detektor Rocky Mountain
- Detektor Skyscan
- Detektor Noyafa
Nyeste Detektor Manualer
16 Oktober 2024
16 Oktober 2024
30 September 2024
21 September 2024
11 September 2024
11 September 2024
11 September 2024
11 September 2024
6 September 2024
6 September 2024