Electrical Rating:
Battery Power mV to VAC, NEC Class II, Hz ..................................... 30 50/60
Input-Hardwire to VAC, NEC Class II, / Hz .................................... 20 30 50 60
Terminal Load A per terminal, A maximum all terminals combined .......................................... 1.0 1.5
Setpoint Range to F ( to ........................................ 45° 99° 37° C)
Rated Dierentials: Fast Med Slow
Heat (@ °F/ Hr) 6 .................................. 0.5°F 0.75°F 1.9°F
Cool (@ °F/ Hr) . 6 .................................. 0 9°F 1.2°F 1.7°F
Operating Ambient .................................. 32°F to +105°F (0° to +41°C)
Display Temperature Range 32°F to +99°F (0 to 37°C) .......................
Operating Humidity % non-condensing max ................................. 90
Shipping Temperature Range ................... °F to + °F-20 150 (-29° to +65°C)
Thermostat Dimensions ........................... 3-3/4” H x 6” W x 1-1/8” D
PART NO. 37-7478A-EN
1504
1F83C-11PR (Programmable)
Installation and Operating Instructions
80 Series Single Stage Thermostat
Battery Powered or Hardwired with Common
Thermostat Applications
Maximum
Stages
Heat/Cool
Conventional Gas, Oil, Electric (mV and
24V), Heat Only, Cool Only or Heat/
Cool Systems
1/1
Heat Pump (air source or geothermal)
with no Aux. Heat 1/1
Thermostat Installation 2-4
Wiring 2
Installer Menu 3-4
Using the Thermostat 5-7
Thermostat Overview 5
User Menu 6
Thermostat Operation 6
Thermostat Schedule 7
Troubleshooting 7-8
Homeowner Help Line 8
INDEX
SPECIFICATIONS
emersonthermostats.com
white-rodgers.com
MERCURY NOTICE: This product does not contain
mercury. However, this product may replace a product
that contains mercury. Mercury and products containing
mercury must not be discarded in household trash.
Refer to www.thermostat-recycle.org for information
on disposing of products containing mercury.
Optional Accessory: Wall Cover-Up Plate W x F61-2663 6 3/4, 4 1/2” H
2
Terminal Designations Terminal Function
RC* Power for Cooling
RH* Power for Heating
O/B Changeover Terminal-Energized in Heat (B) or Cool (O)
for Heat Pump or Damper Systems
Y** Cooling Relay
G Fan Relay
W** Heating Relay
C Common wire for (optional with batteries)24V
*When both RC and RH wires are present, cut RC/RH jumper (see next page).
**For heat pump systems, add a jumper wire to connect terminals Y and W
THERMOSTAT INSTALLATION
Leveling Thermostat
Leveling is for appearance only and
will not aect thermostat operation.
WIRING
Refer to equipment manufacturer’s instructions for specic system wiring information. After
wiring, see INSTALLER MENU for proper thermostat conguration. Wiring table shown are
for typical systems and describe the thermostat terminal functions.
WARNING
!
Do not use on circuits exceeding specied voltage.
Higher voltage will damage control and could
cause shock or re hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will burn
out thermostat and could cause personal injury
and/or property damage.
CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electrical power to system,
at main fuse or circuit breaker box,until
installation is complete.
Precautions
Do not exceed the specication ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handing or
distorting components could cause the control to malfunction.


Produkt Specifikationer

Mærke: Emerson
Kategori: Termostater
Model: 1F83C-11PR

Har du brug for hjælp?

Hvis du har brug for hjælp til Emerson 1F83C-11PR stil et spørgsmål nedenfor, og andre brugere vil svare dig