Occupancy Sensor OCS 100W • Setup Guide
The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a
dual-technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to
detect the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves.
The PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the
ambient room temperature.
The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy
output connections.
Front Panel Features
Ultrasonic
Sensors
Green LED
(status indicator)
Red LED
(status indicator)
Infrared/Photocell
Sensor and Lens
Removable Front Cove
r
Figure 1. OCS 100W Front Panel Features
Control
A B
1234
1234
Blue Timer Test Button
Blue Photocell Dial
Notch
Green Ultrasonic Range Dial
Red Infrar
ed Sensitivity Dial
DIP Switches (B)
DIP Switches (A)
Figure 2. OCS 100W Controls
DIP Switches (B) — (see NOTE on the next page)
B OPERATION Settings
1Timer Setting
(B1 and B2 switches
must be set together)
8 minutes:
OFF*
4 minutes:
OFF
15 minutes:
ON
30 minutes:
ON
2OFF * ON OFF ON
B OPERATION OFF ON
3Timer adjust Automatic Manual*
4Sensitivity adjust Automatic Manual*
*Default
The settings for DIP Switches B3 (timer adjust) and B4 (sensitivity adjust can be set to Automatic mode or Manual mode.
Automatic mode — The sensors automatically adjust for changes in usage and seasons, eliminating the need for
manual adjustments and improving system performance.
Manual mode — The user sets the parameters of the sensors using the DIP Switches B1 and B2 set together, and
the dials.
Ultrasonic Sensors — Detect movement in the room, based on
ultrasonic waves.
Green LED (status indicator) — Flashes when the ultrasonic
sensors detect occupancy.
Infrared/Photocell Sensor and Lens — Diffracts the incoming
light and directs the light to the infrared/photocell sensor.
Red LED (status indicator) — Flashes when the infrared sensor
detects occupancy.
Removable Front Cover — Conceals all controls and DIP
switches.
DIP Switches (A)
A OPERATION OFF ON
1Not used Not usedNot used*
2Not used Not usedNot used*
3LED indicators LEDs disabledLEDs enabled*
4Automatic adjust
reset
Toggle to reset ( )Default: OFF
*Default


Produkt Specifikationer

Mærke: Extron
Kategori: Bevægelsesdetektor
Model: OCS 100W

Har du brug for hjælp?

Hvis du har brug for hjælp til Extron OCS 100W stil et spørgsmål nedenfor, og andre brugere vil svare dig




Bevægelsesdetektor Extron Manualer

Extron

Extron OCS 100W Manual

5 September 2024
Extron

Extron OCS 100C Manual

26 Juli 2024

Bevægelsesdetektor Manualer

Nyeste Bevægelsesdetektor Manualer

DSC

DSC PG9862 Manual

13 September 2024
Maxsa

Maxsa 40234 Manual

11 September 2024
Maxsa

Maxsa 43218 Manual

11 September 2024
Hikvision

Hikvision DS-PDD12-EG2 Manual

10 September 2024
ORNO

ORNO OR-CR-233 Manual

9 September 2024
ORNO

ORNO OR-CR-219 Manual

9 September 2024