CDPX-X-E2-...-EX2
Operator unit
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Operating instruction| Operating conditions EX
8213962
2024-07
[8213964]
8213962
Original instructions
© 2024 all rights reserved to Festo SE & Co. KG
CODESYS, MODBUS, OPCUA, WINDOWS are registered trademarks of the respec-
tive trademark owners in certain countries.
1 About this document
1.1 Identification EX
Marking Certificates
Class I, Division 2, Groups A, B, C and D E245518
Tab. 1: Identification EX
1.2 Certified products
Type Part number
CDPX-X-E2-W-5-EX2 8155219
CDPX-X-E2-W-7-EX2 8155220
CDPX-X-E2-W-10-EX2 8155221
CDPX-X-E2-W-15-EX2 8155222
CDPX-X-E2-W-21-EX2 8155223
Tab. 2: Certified products
1.3 Applicable documents
All available documents for the product
èwww.festo.com/sp.
2 Safety
2.1 Safety instructions
The device can be used under the stated operating conditions in zone 2 of
explosive gas atmospheres.
Use the device in its original status, without any unauthorised modifications.
Clean the device with a soft cloth.
2.2 Intended use
The product is an operator unit and display unit in conjunction with PLC systems.
2.3 Cyber security measures
Accidental or improper execution of functions on the product can lead to
failure or malfunction of the product and thus the entire connected system.
In addition, unauthorised access to information stored on the product may be
possible. The system operator must therefore take appropriate measures to pre-
vent accidental or improper access to the product. Cyber security information
èwww.festo.com/psirt.
Access with Festo service tools
The following table shows the device functions and the ports used for the specific
device function.
Function [BT1] Description Port [BT2] Operation
Search The device can be found on the network with a
search protocol.
990 (UDP)
991 (UDP)
10002 (UDP/
MULTICAST)
¨
Network The device supports the display and setting of
the network parameters. On completion of setting
the device will restart.
990 (UDP)
10002 (UDP/
MULTICAST)
¨
Firmware The device supports the download of a new firm-
ware version.
10002 (UDP/
MULTICAST)
¨
Backup/restore The device supports data backup and data
recovery. This will restart the device.
10002 (UDP/
MULTICAST)
¨
Homepage The device provides an information page for
Internet browsers.
In addition, after entering the user and password,
it enables changes to parameters in the system,
firmware updates, switching services on/off.
80 (TCP)
443 (TCP)
þ
Identification The device supports the prompt for identification,
forexample, with a flashing LED display.
10002 (UDP/
MULTICAST)
þ
File transfer The device supports file transfer in the command
line mode.
10002 (UDP/
MULTICAST)
þ
FTP File transfer protocol 21 (TCP) ¨
¨ To avoid potential damage to the system do not perform the function during operation.
þ The function can be executed during operation.
Tab. 3: Functions available via the protocols used by Festo service tools
Access via the CODESYS development environment
The following table shows the functions and ports used for each function.
CODESYS is only supported with the CDPX-X-A, CDPX-X-E1 und CDPX-X-E2 var-
iants.
Function Description Port Configu-
rable
CODESYS commu-
nication
Connection from CODESYS to the controller, exe-
cution of system-critical commands (start/stop/
reset/reload/delete application, reboot, configu-
ration change, PLC Shell).
1740…1743
(UDP)
11740…
11743 (TCP)
¨
Gateway Gateway, to connect CODESYS to the gateway
(scan, wink).
1217 (TCP) ¨
Web server Web server for CODESYS web visualisation. 8080 (TCP) þ
Web server
(HTTPS)
Web server for CODESYS web visualisation
(https)
443 (TCP) þ
Network variables Read and write access to the variable interface of
the controller.
The default port can be reconfigured.
1202 (UDP) þ
ModbusTCP
server
Access to the variable interface of the controller
with read and write services.
The default port can be reconfigured.
502 (TCP) þ
Festo_EasyIP Access to the variable interface of the controller
with read and write services.
995 (UDP)
þ
OPCUA server Access to the variable interface of the controller
with read and write services.
4840 (TCP) þ
¨ The network ports are always in use.
þ The network ports are only used if they are configured in the CODESYS application.
Tab. 4: Functions available via the CODESYS development environment
Access with Festo Designer Studio
The following table shows the functions and ports used for each function.
Function Description Port Configu-
rable
FTP
FTPS
Connection from Designer Studio to the CDPX
HMIs, project download, firmware update, run-
time system update.
21 (TCP)
990 (TCP)
HTTP
HTTPS
Connection from Designer Studio to the CDPX
HMIs, search function, project download, firm-
ware update, runtime system update.
80 (TCP)
443 (TCP)
Codesys communi-
cation
Connection of CDPX HMIs via CODESYS protocol
to CODESYS controllers, access to the variable
interface of the controller by read and write serv-
ices.
1740-1743
(UDP)
11740-11743
(TCP),
1200[UDP)
þ
ModBusTCP client Access to the variable interface of the controller
with read and write services.
The default port can be reconfigured.
502 (TCP) ¨
Festo_EasyIP Access to the variable interface of the controller
with read and write services.
995 (UDP)
¨


Produkt Specifikationer

Mærke: Festo
Kategori: overvåge
Model: CDPX-X-E2-W-7-EX2

Har du brug for hjælp?

Hvis du har brug for hjælp til Festo CDPX-X-E2-W-7-EX2 stil et spørgsmål nedenfor, og andre brugere vil svare dig




overvåge Festo Manualer

overvåge Manualer

Nyeste overvåge Manualer

Philips

Philips 233V5LHAW Manual

21 December 2024
Philips

Philips 206V3LSB2 Manual

21 December 2024
HP

HP Z23i Manual

21 December 2024
HP

HP 2511x Manual

21 December 2024
Philips

Philips 86BDL4511D Manual

21 December 2024
Philips

Philips 271S9A Manual

21 December 2024