First Alert SMI105-AC Manual


Læs nedenfor 📖 manual på dansk for First Alert SMI105-AC (2 sider) i kategorien Røgdetektor. Denne guide var nyttig for 2 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
USER’S MANUAL
SMOKE ALARM
AC POWERED WITH 10-YEAR BATTERY BACKUP
Model SMI105-AC
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
The warnings/limitations card and manual contains important
information about your Smoke Alarm’s operation. If you are
installing this Alarm for use by others, you must leave this
manual—or a copy of it—with the end user.
Para el manual del usuario en español, por favor
visite rstalert.com
DANGER!
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Smoke Alarm is
installed before removing it from the mounting bracket. Failure to turn off the power
rst may result in serious electrical shock, injury or death.
! WARNING!
This unit will not alert hearing impaired residents. It is recommended that you
install special units which use devices like ashing strobe lights to alert hearing
impaired residents.
Installation of this unit must conform to the electrical codes in your area; Articles 210
and 300.3 (B) of NFPA 70 (NEC), NFPA 72, NFPA 101; ICC; SBC (SBCCI); UBC (ICBO); NBC
(BOCA); OTFDC (CABO), and any other local or building codes that may apply. Wiring and
installation must be performed by a licensed electrician. Failure to follow these guidelines
may result in injury or property damage.
This unit must be powered by a 24-hour, 120V AC pure sine wave 60 Hz circuit. Be sure
the circuit cannot be turned off by a switch, dimmer, or ground fault circuit interrupter.
Failure to connect this unit to a 24-hour circuit may prevent it from providing constant
protection. Unit may be connected to an arc fault circuit interrupter.
This Smoke Alarm must have AC or battery power to operate. If the AC power fails, battery
back-up will allow the Alarm to sound for at least 4 minutes. If AC power fails and the
battery is weak, protection should last for up to 7 days. If AC power fails and the battery is
dead or missing, the Alarm cannot operate.
Never disconnect the power from an AC powered unit to stop an unwanted Alarm. Doing
so will disable the unit and remove your protection. In the case of a true unwanted Alarm
open a window or fan the smoke away from the unit. The Alarm will reset automatically
when it returns to normal operation.
Never remove the batteries from a battery operated unit to stop an unwanted Alarm
(caused by cooking smoke, etc.). Instead open a window or fan the smoke away from the
unit. The Alarm will reset automatically.
! CAUTION!
Connect this unit ONLY to other compatible units. See “How To Install This Smoke Alarm”
for details. Do not connect it to any other type of Alarm or auxiliary device. Connecting
anything else to this unit may damage it or prevent it from operating properly.
The battery compartment resists closing unless a battery is installed. This warns you the
unit will not operate under DC power without a battery.
Do not paint over the unit. Paint may clog the openings to the sensing chamber and
prevent the unit from operating properly.
01 INTRODUCTION
Thank you for choosing First Alert
®
for your Smoke Alarm needs. You have purchased a state-of-the-
art Smoke Alarm designed to provide you with early warning of a re. Please take the time to read this
manual and make the Smoke Alarm an integral part of your family’s safety plan.
BASIC SAFETY INFORMATION
IMPORTANT!
Dangers, Warnings, and Cautions alert you to important operating instructions or to potentially
hazardous situations. Pay special attention to these items.
This Smoke Alarm is approved for use in single-family residences. It is designed for NOT
marine or RV use.
! CAUTION!
The Smoke Alarm will only indicate the presence of smoke that reaches the sensor.
The Smoke Alarm is not designed to sense gas, heat or ames.
! WARNING!
This Smoke Alarm cannot operate without working batteries. Removing the batteries for any
reason, removes your protection.
ignore any Alarm. See “If Your Smoke Alarm Sounds” for more information on how to NEVER
respond to an Alarm. Failure to respond can result in injury or death.
The Silence Features are for your convenience only and will not correct a problem. See “Using the
Silence Features” for details. Always check your home for a potential problem after any Alarm.
Failure to do so can result in injury or death.
Test this Smoke Alarm once a week. If the Alarm ever fails to test correctly, have it replaced
immediately! If the Alarm is not working properly, it cannot alert you to a problem.
02 ABOUT SMOKE ALARMS
TYPES OF ALARMS
All these Smoke Alarms are designed to provide early warning of res if located, installed and cared
for as described in the user’s manual, and if smoke reaches the Alarm. If you are unsure which type of
Smoke Alarm to install, refer the National Fire Protection Association (NFPA) Standard 72 (National Fire
Alarm and Signaling Code) and NFPA 101 (Life Safety Code). National Fire Protection Association, One
Batterymarch Park, Quincy, MA 02269-9101. Local building codes may also require specic units in
new construction or in different areas of the home.
Battery (DC) operated Smoke Alarms: Provide protection even when electricity fails, provided the
batteries are fresh and correctly installed. Units are easy to install, and do not require professional
installation. They do not, however, provide interconnected functionality.
AC powered Smoke Alarms: Can be interconnected so if one unit senses smoke, all units Alarm.
They do not operate if electricity fails.
AC with battery (DC) back-up: will operate if electricity fails, provided the batteries are fresh and
correctly installed. AC and AC/DC units must be installed by a qualied electrician.
Wireless Interconnected Alarms: Offer the same interconnected functionality as with hardwired
Alarms, without wires. Units are easy to install and do not require professional installation. They
provide protection even when electricity fails, provided the batteries are fresh and correctly installed.
Smoke Alarms for solar or wind energy users and battery backup power systems: AC powered
Smoke Alarms should only be operated with true or pure sine wave inverters. Operating this Smoke
Alarm with most batterypowered UPS (uninterruptible power supply) products or square wave or
“quasi sine wave” inverters If you are not sure about your inverter or UPS will damage the Alarm.
type, please consult with the manufacturer to verify.
Smoke Alarms for the hearing impaired: Special purpose Smoke Alarms should be installed for the
hearing impaired. They include a visual Alarm and an audible Alarm horn, and meet the requirements
of the Americans With Disabilities Act. These units can be interconnected so if one unit senses smoke,
all units Alarm.
Smoke Alarms are not to be used with detector guards unless the combination has been evaluated
and found suitable for that purpose.
All First Alert
®
Smoke Alarms conform to regulatory requirements, including UL217 and are
designed to detect particles of combustion. Smoke particles of varying number and size are
produced in all res.
Ionization technology is generally more sensitive than photoelectric technology at
detecting small particles, which tend to be produced in greater amounts by aming res,
which consume combustible materials rapidly and spread quickly. Sources of these res
may include paper burning in a wastebasket, or a grease re in the kitchen.
Photoelectric technology is generally more sensitive than ionization technology at
detecting large particles, which tend to be produced in greater amounts by smoldering
res, which may smolder for hours before bursting into ame. Sources of these res may
include cigarettes burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each level and in every
bedroom of your home.
03 INSTALLATION
BEFORE YOU INSTALL THIS SMOKE ALARM
IMPORTANT!
Read “Recommended Locations for Smoke Alarms” and “Locations to Avoid for Smoke Alarms”
before beginning. This unit monitors the air, and when smoke reaches its sensing chamber, it Alarms.
It can give you more time to escape before re spreads. This unit can ONLY give an early warning
of developing res if it is installed, maintained and located where smoke can reach it, and where all
residents can hear it, as described in this manual. This unit will not sense gas, heat, or ame. It cannot
prevent or extinguish res.
WHERE TO INSTALL THIS ALARM
The National Fire Protection Association (NFPA), recommends one Smoke Alarm on every oor, in every
sleeping area, and in every bedroom. In new construction, the Smoke Alarms must be AC powered and
interconnected. See “Agency Placement Recommendations” for details. For additional coverage, it is
recommended that you install a Smoke Alarm in all rooms, halls, storage areas, nished attics, and
basements, where temperatures normally remain between 40˚ F (4.4˚ C) and 100˚ F (37.8˚ C). Make
sure no door or other obstruction could keep smoke from reaching the Smoke Alarms.
IN GENERAL, INSTALL SMOKE ALARMS:
On every level of your home, including nished attics and basements.
Inside every bedroom, especially if people sleep with doors closed.
In the hall near every sleeping area. If your home has multiple sleeping areas, install a unit in each.
If a hall is over 40 feet (12 meters) long, install an Alarm at each end.
At the top of the rst-to-second level stairway, and at bottom of basement stairway.
IMPORTANT!
Specic requirements for Smoke Alarm installation vary from state to state and from region to region.
Check with your local Fire Department for current requirements in your area. It is recommended AC
or AC/DC units be interconnected for added protection.
RECOMMENDED PLACEMENT:
Smoke Alarm
One on every level and
in every bedroom
Carbon Monoxide Alarm
One on every level and
in every bedroom
Fire Extinguisher
One on every level, plus
kitchen and garage
When installing on the wall, the top edge of Smoke Alarms should be placed between 4 inches
(102 mm) and 12 inches (305 mm) from the wall/ceiling line.
When installing on the ceiling, place the Alarm as close to the center as possible.
In either case, install at least 4 inches (102 mm) from where the wall and ceiling meet.
NOTE: For any location, make sure no door or other obstruction could keep carbon monoxide or smoke
from reaching the Alarm.
WHERE NOT TO INSTALL THIS ALARM
FOR BEST PERFORMANCE, IT IS RECOMMENDED YOU AVOID INSTALLING SMOKE ALARMS
IN THESE AREAS:
Where combustion particles are produced. Combustion particles form when something burns.
Areas to avoid include poorly ventilated kitchens, garages, and furnace rooms. Keep units at
least 20 feet (6 meters) from the sources of combustion particles (stove, furnace, water heater,
space heater) if possible. In areas where a 20-foot (6 meter) distance is not possible – in modular,
mobile, or smaller homes, for example – it is recommended the Smoke Alarm be placed as far
from these fuel-burning sources as possible. The placement recommendations are intended
to keep these Alarms at a reasonable distance from a fuel-burning source, and thus reduce
“unwanted” Alarms. Unwanted Alarms can occur if a Smoke Alarm is placed directly next to a
fuel-burning source. Ventilate these areas as much as possible.
In air streams near kitchens. Air currents can draw cooking smoke into the sensing chamber of a
Smoke Alarm near the kitchen.
In very damp, humid or steamy areas, or directly near bathrooms with showers. Keep units at least
10 feet (3 meters) away from showers, saunas, dishwashers, etc.
Where the temperatures are regularly below 40˚ F (4.4˚ C) or above 100˚ F (37.8˚ C) including
unheated buildings, outdoor rooms, porches, or unnished attics or basements.
In very dusty, dirty, or greasy areas. Do not install a Smoke Alarm directly over the stove or range.
Clean a laundry room unit frequently to keep it free of dust or lint.
Near fresh air vents, ceiling fans, or in very drafty areas. Drafts can blow smoke away from the
unit, preventing it from reaching sensing chamber.
In insect infested areas. Insects can clog openings to the sensing chamber and cause
unwanted Alarms.
Less than 12 inches (305 mm) away from uorescent lights. Electrical “noise” can interfere
with the sensor.
In “dead air” spaces.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke Alarm. To avoid dead air spaces,
follow installation recommendations below.
On ceilings, install Smoke Alarms as close to the center of the ceiling as possible. If this is not possible,
install the Smoke Alarm at least 4 inches (102 mm) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke Alarms should be placed
between 4 inches (102 mm) and 12 inches (305 mm) from the wall/ceiling line, below typical
“dead air” spaces.
On a peaked, gabled, or cathedral ceiling, install rst Smoke Alarm within 3 feet (0.9 meters) of the
peak of the ceiling, measured horizontally. Additional Smoke Alarms may be required depending on
the length, angle, etc. of the ceiling’s slope. Refer to NFPA 72 for details on requirements for sloped or
peaked ceilings.
HOW TO INSTALL THIS ALARM
IMPORTANT!
This Smoke Alarm is designed to be mounted on any standard wiring junction box up to a 4-inch (10 cm) size,
on either the ceiling or wall (if allowed by local codes). Read “Where to Install This Alarm” and “Where This
Alarm Should Not Be Installed” before you begin installation.
Tools you will need: needle-nose pliers or utility knife, standard athead screwdriver, wire strippers
(for interconnected Alarms)
! WARNING!
Make sure the Alarm is not receiving excessively noisy power. Examples of noisy power could
be major appliances on the same circuit, power from a generator or solar power, light dimmer
on the same circuit or mounted near uorescent lighting. Excessively noisy power may cause
damage to your Alarm.
THE PARTS OF THIS ALARM
The Mounting Bracket: To remove the mounting bracket from the Smoke Alarm base, hold the Smoke
Alarm base rmly and twist the mounting bracket counterclockwise. The mounting bracket installs
onto the junction box. It has a variety of screw slots to t most boxes.
The Power Connector: The power connector
plugs into a power input block on the Alarm. It
supplies the unit with AC power.
The black wire is “hot.”
The white wire is neutral.
The orange wire is used for interconnect.
If you need to remove the power connector,
turn Insert a at POWER OFF rst.
screwdriver blade between the power
connector and the security tab inside the
power input block. Gently pry back the tab
and pull the connector free.
ABC
1
3
6
2
2
3
45
7
THE PARTS OF THIS SMOKE ALARM
A Smoke LED (RED)
B Power LED (GREEN)
C Test/Silence button
1 Mounting Bracket
2 Mounting Slots
3 Locking Pins
(break out of bracket)
4 Hot (Black) AC Wire
5 Neutral (White) AC Wire
6 Interconnect (Orange) Wire
7 Quick-Connect Power Connector
FOLLOW THESE SIMPLE STEPS
The basic installation of this Smoke
Alarm is similar whether you want
to install one Alarm, or interconnect
more than one Alarm. If you are
interconnecting more than one Alarm,
you read “Special Requirements MUST
for Interconnected Alarms” below before
you begin installation.
DANGER!
ELECTRICAL SHOCK HAZARD. Turn off power to the area where you will install this unit at the
circuit breaker or fuse box before beginning installation. Failure to turn off the power before
installation may result in serious electrical shock, injury or death.
! WARNING!
Improper wiring of the power connector or the wiring leading to the power connector will cause
damage to the Alarm and may lead to a non-functioning Alarm. All power connections should be done
using wire-nuts.
STAND-ALONE ALARM ONLY:
Connect the white wire on the power connector to the neutral wire in the junction box.
Connect the black wire on the power connector to the hot wire in the junction box.
Tuck the orange wire inside the junction box. It is used for interconnect only.
INTERCONNECTED UNITS ONLY:
Strip off about 1/2" (12 mm) of the plastic coating on the orange wire on the
power connector.
Connect the white wire on the power connector to the neutral wire in the junction box.
Connect the black wire on the power connector to the hot wire in the junction box.
Connect the orange wire on the power connector to the interconnect wire in the junction
box. Repeat for each unit you are interconnecting. Never connect the hot or neutral wires
in the junction box to the orange interconnect wire. Never cross hot and neutral wires
between Alarms.
1. Remove the mounting bracket from the base, and attach it to the junction box.
2. Using wire nuts, connect the power connector to the household wiring.
3. If theres a battery pull tab, activate the battery back-up by removing the “Pull to Activate Battery
Back-Up” tab. You do no need to open the battery compartment during installation. If battery is not
installed, install battery back-up. Battery back-up cannot work until you install the battery in the
correct position (Match “+” to “+” and “-” to “-”).
4. Plug the power connector into the back of the Alarm.
5. Position the base of the Alarm over the mounting bracket, and turn the Alarm clockwise (right) until
the unit is in place. If wall mounted, adjust unit so words are level.
6. Check all connections.
STAND-ALONE ALARM ONLY:
If you are only installing one Alarm, restore power to the junction box.
INTERCONNECTED UNITS ONLY:
If you are interconnecting multiple Alarms, repeat steps 1-6 for each Alarm in the series.
When you are nished, restore power to the junction box.
DANGER!
ELECTRICAL SHOCK HAZARD. Do not restore power until all Smoke Alarms are completely
installed. Restoring power before installation is complete may result in serious electrical
shock, injury or death.
7. Turn AC power back on. Under normal operation, the Green power indicator light will
shine continuously.
8. If the Green power indicator light does not light, and TURN OFF POWER TO THE JUNCTION BOX
recheck all connections. If all connections are correct and the Green power indicator still does not
light when you restore the power, the unit should be replaced immediately.
9. Single Station Alarms: Test each Alarm. Press and release the Test/Silence button. The unit will
chirp and then Alarm.
Interconnected Alarms: Press and release the Test/Silence button. The unit will chirp and
then Alarm. All interconnected Alarms should sound. The other Alarms sounding only tests the
interconnect signal between Alarms. It does not test each Alarm’s operation. You must test
each Alarm individually to check if the Alarm is functioning properly.
DANGER!
If any unit in the series does not Alarm, TURN OFF POWER and recheck connections. If it does
not Alarm when you restore power, replace it immediately.
SPECIAL REQUIREMENTS FOR INTERCONNECTED ALARMS
! WARNING!
Failure to meet any of the above requirements could damage the units and cause them to
malfunction, removing your protection.
AC and AC/DC Smoke Alarms can be interconnected. Under AC power, all units will Alarm when
one senses smoke. When power is interrupted, only the AC/DC units in the series will continue to
send and receive signals. AC powered Smoke Alarms will not operate.
Interconnected units can provide earlier warning of re than stand-alone units, especially if a re
starts in a remote area of the dwelling. If any unit in the series senses smoke, all units will Alarm. To
determine which Alarm initiated an Alarm, see table:
During an Alarm
On Initiating Alarm(s): Red LED(s) ashes (ash)
rapidly in sync with horn
On All Other Alarms: Green LED(s) Normal,
Red LED(s) Off
After an Alarm (Latching)
On Initiating Alarm(s): Red LED(s) On for 2 seconds/
Off for 2 seconds
On All Other Alarms: Green LED(s) Normal,
Red LED(s) Off
COMPATIBLE INTERCONNECTED UNITS
IMPORTANT!
Interconnect units within a single family residence only. Otherwise all households will experience
unwanted Alarms when you test any unit in the series. Interconnected units will only work if they are
wired to compatible units and all requirements are met. This unit is designed to be compatible with:
First Alert Smoke and Smoke/CO Alarms Models SMI100-AC, SMI105-AC, SMICO100-AC,
SMICO105-AC, SA520, SM100V-AC, SMCO100V-AC, SM300-AC, SM500-AC, 1039102,7030BSL,
SMI110LED-AC, SMICO110LED-AC and BRK Smoke Alarm Models 3120B, 9120, 9120B, SC9120B,
7010, 7010B, 7010BSL, 7020B, 7020BSL, SC7010B, SC7010BV; BRK Heat Alarm Model HD6135FB;
BRK Auxiliary Devices Models RM4 (Relay Module).
INTERCONNECTED UNITS MUST MEET ALL OF THE FOLLOWING REQUIREMENTS:
A maximum of 18 compatible units may be interconnected (Maximum of 12 Smoke Alarms).
The same fuse or circuit breaker must power all interconnected units.
The total length of wire interconnecting the units should be less than 1000 feet (300 meters). This
type of wire is commonly available at Hardware and Electrical Supply stores.
All wiring must conform to all local electrical codes and NFPA 70 (NEC). Refer to NFPA 72, NFPA
101, and/or your local building code for further connection requirements.
BA
6
7
8
11
2 2
4
53
3
45
A Unswitched 120VAC 60 Hz source B To additional units; Maximum =
18 total (Maximum 12 Smoke Alarms)
1 Alarm
2 Ceiling or Wall
3 Power Connector
4 Wire Nut
5 Junction Box
6 Neutral Wire (White)
7 Interconnect Wire
(Orange)
8 Hot Wire (Black)
Action What You Will See & Hear
Normal Operations Horn: Power LED: Silent; Steady
Green; OffSmoke LED:
AC Power to Alarm is Off Horn: Power LED: Silent; Flashes Green every
minute; OffSmoke LED:
When You Test the Alarm
Horn: Short “chirp”, then 3 beeps, pause, 3 beeps;
Power LED: Green if AC power to Alarm is On;
Smoke LED: Flashes Red in sync with horn
Alarm has reached
Low Battery/End of Life
If AC power to Alarm is on OR rst 15 minutes after AC
power is removed
Horn: Chirps 5 time every minute;
Power LED: Flashes Green 2 seconds on/2 seconds off;
Smoke LED: Off
After rst 15 minutes if AC power to Alarm is Off
Horn: Chirps 5 times every minute; Flashes Power LED:
Green 5 times every minute; OffSmoke LED:
Low Battery/End of Life
Signal is Silenced
Horn: Power Silent (for up to 2 days, 14 days total);
LED: Steady Green (AC power) or 5 Green ashes (on
battery backup); OffSmoke LED:
Alarm is Not Operating Properly
(Malfunction Signal)
Horn: Power LED: 3 chirps every minute; Flashes
Green 3 times every minute; OffSmoke LED:
Smoke is Detected
Horn: 3 beeps, pause, 3 beeps; Constant Power LED:
Green (AC power), Off (on battery backup); Smoke/
CO LED: During Alarm: Flashes Red in sync with
the horn pattern. Flashes Red On for 2 After Alarm:
seconds/Off for 2 seconds. Smoke Alarm Latch is now
engaged (See Latching Features section for details)
Smoke is Detected in Another
Interconnected Alarm
Horn: 3 beeps, pause, 3 beeps; Power LED:
Steady Green (AC power), Off (on battery
backup); OffSmoke LED:
Smoke Alarm is Silenced
(up to 15 Minutes)
Horn: Power LED: Off; Steady Green if AC power to
Alarm is On, Flash 1 time every minute if Alarm is
operating on battery backup; Flashes Smoke LED:
Red 3 times, pause, 3 times
NOTE: Without AC Power and running on battery only, Low Battery Latch or Alarm Latch are
only engaged for about 15 minutes to conserve power. Low Battery Latch and Alarm Latch do
not operation with a missing battery and no AC power.
04 ALARM FEATURES
Add protection in minutes.Easy Installation:
10 Year Battery Backup: For protection during power outages.
Identies unit that initiated Alarm.Alarm Indicator:
LATCHING FEATURES
Alarm Latch is activated after an Alarm is exposed to Alarm levels of smoke. This feature will
only work with AC power. See “Special Requirements for Interconnected Alarms” for signaling.
This feature helps emergency responders, investigators, or service technicians identify which
unit(s) in your home were exposed to Alarm levels of smoke. This can help investigators
pinpoint the source of smoke.
Interconnected Alarms. Latching Alarm Indicator shows which Alarm(s) in the series were
exposed to Alarm levels of smoke. The Latching Alarm Indicator stays ON until you clear it,
so it can alert you to an Alarm that occurred while you were away from home, even though
smoke present in the air has dropped below Alarm levels.
Latching Alarm
Unit was exposed to
Alarm levels of Smoke
Latching Not Activated
Unit was not exposed to
Alarm levels of Smoke
Low Battery Latch is activated when the Alarm is in the “low battery condition”. When this
occurs, the Green LED ashes 2 seconds on, 2 seconds off. This feature is designed to help
you identify which Alarm needs to be replaced.
OPTIONAL LOCKING FEATURE
The optional locking feature is designed to discourage unauthorized removal of the Alarm. It is
not necessary to activate the locks in single-family households where unauthorized removal
is not a concern.
Locking Pin
Tools you will need: Needle-nose pliers or
utility knife, standard athead screwdriver
The locking feature uses a locking pin,
which is molded into the mounting bracket.
Using needle nose pliers or a utility knife,
remove the pin from the mounting bracket.
TO LOCK THE MOUNTING BRACKET
1. Using needle-nose pliers
or utility knife, detach
one locking pin from
mounting bracket.
2. Insert the locking pin into the
lock located on the base as
shown in the diagram.
3. When you attach the Smoke
Alarm to the mounting
bracket, the locking pin’s
head will t into a notch
on the bracket.
TO UNLOCK THE MOUNTING BRACKET
DANGER!
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Alarm is
installed before removing it from the mounting bracket. Failure to turn off the power
rst may result in serious electrical shock, injury or death.
1. Insert a athead screwdriver
between the mounting bracket
pin and the mounting bracket.
2. Pry the Alarm away from
the bracket by turning both
the screwdriver and the
Alarm counterclockwise (left)
at the same time.
05 TESTING & MAINTENANCE
WEEKLY TESTING
! WARNING!
NEVER use an open ame of any kind to test this unit. You might accidentally damage or set re to the
unit or to your home.
! CAUTION!
DO NOT stand close to the Alarm when the horn is sounding. Exposure at close range may be
harmful to your hearing. When testing, step away when horn starts sounding.
It is important to test this unit every week to make sure it is working properly. Using the test
button is the recommended way to test this Smoke Alarm. Press and release the Test/Silence
button on the cover of the unit. The unit will “chirp” and then Alarm. If it does not Alarm, make sure
the unit is receiving power and test it again. If it still does not Alarm, replace it immediately. During
testing, you will hear a loud, repeating horn pattern: 3 beeps, pause, 3 beeps, pause.
When testing a series of interconnected units you must test each unit individually. Make sure all units
Alarm when each one is tested.
REGULAR MAINTENANCE
This unit has been designed to be as maintenance-free as possible, but there are a few simple things
you must do to keep it working properly:
Test it at least once a week.
Clean the Smoke Alarm at least once a month; gently vacuum the outside of the Smoke Alarm
using your household vacuum’s soft brush attachment. Test the Smoke Alarm. Never use water,
cleaners or solvents since they may damage the unit.
If the green power LED ashes 2 times every minute (horn is silent) it means that the Alarm needs
to be cleaned as indicated above. If green LED continues to ash, please call Consumer Support.
If the Smoke Alarm becomes contaminated by excessive dirt, dust and/or grime, and cannot be
cleaned to avoid unwanted Alarms, replace the unit immediately.
Relocate the unit if it sounds frequent unwanted Alarms. See “Locations To Avoid For Smoke
Alarms” for details.
When the battery back-up becomes weak, the Smoke Alarm will “chirp” about 5 times a minute
(the low battery warning). This warning should last 7 days, but you should replace the Alarm
immediately to continue your protection.
Protect or cover the alarm when doing any maintenance to home i.e. sanding oors, painting,
drywall patching, etc. to prevent contamination.
! WARNING!
Alarm is supplied with lithium battery (factory locked in battery drawer) that is capable of
providing backup battery function for the recommended life of the Alarm. At low battery or
end of life signal, use tool to cut/disengage the locking pin located at side of factory locked
drawer and properly dispose of lithium battery (reference drawing added) and Alarm. DO NOT
REPLACE BATTERY.
Please dispose of or recycle used batteries properly, following any local regulations. Consult your
local waste management authority or recycling organization to nd an electronics recycling facility
in your area. DO NOT DISPOSE OF BATTERIES IN FIRE. BATTERIES MAY EXPLODE OR LEAK.
! WARNING!
Keep battery out of reach of children. In the event a battery is swallowed, immediately contact
your poison control center, your physician, or the National Battery Ingestion hotline at
202-625-3333 as serious injury may occur.
IMPORTANT!
Actual battery service life depends on the Smoke Alarm
and the environment in which it is installed. At low battery
or end of life signal, use tool to cut/disengage the locking
pin located at side of factory locked drawer and properly
dispose of lithium battery and Alarm.
TROUBLESHOOTING GUIDE
DANGER!
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Alarm is installed
BEFORE removing it from the mounting bracket or checking any electrical connections!
Failure to turn off the power rst may result in electrical shock, injury or death.
IF THE ALARM... PROBLEM... YOU SHOULD...
Green Power light is off. Unit
will not Alarm when you
press the Test/Silence button
Unit may not be
receiving any power.
Check the AC
power supply. Make
sure the power
connector is securely
attached to the Alarm.
Green Power light ashes On
every minute (horn is silent).
Alarm is not
receiving AC power.
Unit is operating on
battery backup. Check the
AC power supply.
Horn “chirps” 5 times every
minute and Green Power LED
ashes on for 2 seconds ON/
2 seconds OFF (Low battery
latch is engaged)
Battery is low or missing
Replace Alarm
immediately. If unit
is under warranty,
contact Consumer
Support to process a
warranty replacement.
Horn “chirps” and Green
Power LED ashes 5
times every minute
END OF LIFE SIGNAL.
Alarm needs
to be replaced.
Replace Alarm immediately
Horn “chirps” and Green
Power LED ashes 3
times every minute
MALFUNCTION SIGNAL.
Device is not working
properly, and needs
to be replaced.
If unit is under warranty,
contact Consumer
Support to process a
warranty replacement.
Power LED ashes Green
2 times every minute Alarm requires cleaning
Clean Alarm then press and
release the test button. See
“Regular Maintenance”
section. If Green LED
continues to ash, contact
Consumer Support.
Alarm goes back into
Alarm after you press the
Test/Silence button to
silence the Alarm
Smoke levels are still
potentially dangerous
Refer to “If your Smoke
Alarm Sounds” for
details on how to
respond to an Alarm.
EVACUATE your home
immediately and call 911.
Smoke Alarm sounds when
no smoke is visible.
Unwanted Alarm may be
caused by nonemergency
source like cooking smoke.
Silence Alarm using test/
silence button. Clean the
Alarm’s cover with a soft,
clean cloth. If frequent
unwanted Alarms continue,
relocate your Alarm. Alarm
may be too close to a
kitchen, cooking appliance
or steamy bathroom.
If you have questions that cannot be answered by reading this manual, call the
Consumer Support Team at 1-800-323-9005.
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking materials properly. Never smoke
in bed. 2) Keep matches or lighters away from children; 3) Store ammable materials in proper
containers; 4) Keep electrical appliances in good condition and don’t overload electrical circuits;
5) Keep stoves, barbecue grills, replaces and chimneys grease- and debris-free; 6) Never leave
anything cooking on the stove unattended; 7) Keep portable heaters and open ames, like candles,
away from ammable materials; 8) Don’t let rubbish accumulate. Keep Alarms clean, and test them
weekly. Replace Alarms immediately if they are not working properly. Smoke Alarms that do not work
cannot alert you to a re. Keep at least one working re extinguisher on every level, and an additional
one in the kitchen. Have re escape ladders or other reliable means of escape from an upper level in
case stairs are blocked; 9) Have an escape plan and practice it regularly.
06 IF THIS SMOKE ALARM SOUNDS
RESPONDING TO AN ALARM
During an Alarm, you will hear a loud, repeating horn pattern: 3 beeps, pause, 3 beeps, pause.
! WARNING!
If the unit Alarms get everyone out of the house immediately.
If the unit Alarms and you are not testing the unit, it is warning you of a potentially dangerous
situation that requires your immediate attention. ignore any Alarm. Ignoring the Alarm may NEVER
result in injury or death.
Never disconnect the AC power to quiet an unwanted Alarm. Disconnecting the power disables the
Alarm so it cannot sense smoke. This will remove your protection. Instead open a window or fan
the smoke away from the unit. The Alarm will reset automatically.
DANGER!
ELECTRICAL SHOCK HAZARD. Attempting to disconnect the power connector from the unit when
the power is on may result in electrical shock, serious injury or death.
When an interconnected system of AC powered units is in Alarm, the Alarm indicator light on the unit(s)
that initiated the Alarm will blink rapidly. It will remain OFF on any remaining units.
If the unit Alarms and you are certain that the source of smoke is not a re—cooking smoke or an
extremely dusty furnace, for example—open a nearby window or door and fan the smoke away from
the unit. Use the Silence Feature to silence the Alarm. This will silence the Alarm, and once the smoke
clears the unit will reset itself automatically.
WHAT TO DO IN CASE OF FIRE
Don’t panic; stay calm. Follow your family escape plan.
Get out of the house as quickly as possible. Don’t stop to get dressed or collect anything.
Feel doors with the back of your hand before opening them. If a door is cool, open it slowly. Don’t
open a hot door. Keep doors and windows closed, unless you must escape through them.
Cover your nose and mouth with a cloth (preferably damp). Take short, shallow breaths.
Meet at your planned meeting place outside your home, and do a head count to make sure
everybody got out safely.
Call the Fire Department as soon as possible from outside. Give your address, then your name.
Never go back inside a burning building for any reason.
Contact your Fire Department for ideas on making your home safer.
! WARNING!
Alarms have various limitations. See “General Limitations of Smoke Alarms” for details.
07 USING THE SILENCE FEATURES
The Silence Feature can temporarily quiet an unwanted Alarm for up to 15 minutes.
! WARNING!
The Silence Feature does not disable the unit—it makes it temporarily less sensitive to smoke. For
your safety, if smoke around the unit is dense enough to suggest a potentially dangerous situation,
the unit will stay in Alarm or may re-Alarm quickly. If you do not know the source of the smoke, do
not assume it is an unwanted Alarm. Not responding to an Alarm can result in property loss, injury,
or death. If the unit will not silence and no heavy smoke is present, or if it stays in silence mode
continuously, it should be replaced immediately.
TO SILENCE SMOKE ALARMS IN AN INTERCONNECTED SERIES
1. To silence multiple Alarms in an interconnected series, you must press the Test/Silence button on
the unit(s) that initiated the Alarm.
NOTE: The red LED on the initiating Alarm will ash 3 times, repeating. The red LED will be Off on
all other non-initiating Alarms. No audible sound will be heard. The unit will exit “silence mode” in
approximately 15 minutes.
2. While the unit is in “silence mode”, pressing and holding the Test/Silence button for approximately
10 seconds will test the unit. After testing, the unit will re-enter “silence mode” and the 15-minute
timer is reset.
SILENCING THE LOW BATTERY/END OF LIFE WARNING
This Silence Feature can temporarily quiet the low battery/end of life warning “chirp” for up to 48 hours.
Press the Test/Silence button on the Alarm cover until you hear the acknowledge “chirp”. Once the low
battery/end of life warning “chirp” Silence Feature is activated, the unit continues to ash the green light
5 times every minute for up to 48 hours. Then, the end of life “chirp” will resume. Replace the unit as
soon as possible, to maintain protection in event of a power outage.
IF YOU SUSPECT A PROBLEM
Smoke Alarms may not operate properly because of a dead or weak battery, a build-up of dirt, dust or
grease on the Smoke Alarm cover, or installation in an improper location. Clean the Smoke Alarm as
described in “Regular Maintenance,” and then test the Smoke Alarm again. If it fails to test properly
when you use the test button, or if the problem persists, replace the Smoke Alarm immediately.
If you hear a “chirp” 5 times a minute, replace the Alarm.
If you experience frequent non-emergency Alarms (like those caused by cooking smoke), try
relocating the Smoke Alarm.
If the Alarm sounds when no smoke is visible, try cleaning or relocating the Smoke Alarm. The
cover may be dirty.
If the Alarm does not sound during testing, make sure it is receiving AC power from the
household current.
Do not try xing the Alarm yourself — this will void your warranty!
If the Smoke Alarm is still not operating properly, and it is still under warranty, please see “How to
Obtain Warranty Service” in the Limited Warranty.
08 REGULATORY INFORMATION
FOR SMOKE ALARMS
RECOMMENDED LOCATIONS FOR SMOKE ALARMS
INSTALLING SMOKE ALARMS IN SINGLE-FAMILY RESIDENCES
The National Fire Protection Association (NFPA), recommends one Smoke Alarm on every oor, in every
sleeping area, and in every bedroom. In new construction, the Smoke Alarms must be AC powered and
interconnected. See “Agency Placement Recommendations” for details. For additional coverage, it is
recommended that you install a Smoke Alarm in all rooms, halls, storage areas, nished attics, and
basements, where temperatures normally remain between 40˚ F (4.4˚ C) and 100˚ F (37.8˚ C). Make
sure no door or other obstruction could keep smoke from reaching the Smoke Alarms.
MORE SPECIFICALLY, INSTALL SMOKE ALARMS:
On every level of your home, including nished attics and basements.
Inside every bedroom, especially if people sleep with doors closed.
In the hall near every sleeping area. If your home has multiple sleeping areas, install a unit in each.
If a hall is over 40 feet (12 meters) long, install an Alarm at each end.
At the top of the rst-to-second level stairway, and at bottom of basement stairway.
IMPORTANT!
Specic requirements for Smoke Alarm installation vary from state to state and from region to region.
Check with your local Fire Department for current requirements in your area. It is recommended AC
or AC/DC units be interconnected for added protection.
HARDWIREDBAT TERY OPERATED & WIRELESS
MULTI-STORY RESIDENCE1-STORY RESIDENCE
Wireless Alarms
Wireless Interconnected Alarms
Hardwired Interconnected
AC or AC/DC Alarms
Smoke Alarms
CO Alarms
Both OR Combination
Smoke/CO Alarms
09 AGENCY PLACEMENT RECOMMENDATIONS
Standards: Underwriters Laboratories Inc. Single and Multiple Station Smoke Alarms 217.
NFPA 72 CHAPTER 29 “FOR YOUR INFORMATION, THE NATIONAL FIRE ALARM AND SIGNALING
CODE, NFPA 72, READS AS FOLLOWS:”
29.5.1* Required Detection.
29.5.1.1* Where required by other governing laws, codes, or standards for a specic type of
occupancy, approved single and multiple-station Smoke Alarms shall be installed as follows:
1. *In all sleeping rooms and guest rooms
2. *Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any door to a
sleeping room, with the distance measured along a path of travel
3. On every level of a dwelling unit, including basements
4. On every level of a residential board and care occupancy (small facility), including basements and
excluding crawl spaces and unnished attics
5. *In the living area(s) of a guest suite
6. In the living area(s) of a residential board and care occupancy (small facility)
(Reprinted with permission from NFPA 72
®
, National Fire Alarm and Signaling Code Copyright © 2012
National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete
and ofcial position of the National Fire Protection Association, on the referenced subject which is
represented only by the standard in its entirety).
(National Fire Alarm and Signaling Code
®
and NFPA 72
®
are registered trademarks of the National Fire
Protection Association, Inc., Quincy, MA 02269).
CALIFORNIA STATE FIRE MARSHAL (CSFM)
Early warning detection is best achieved by the installation of re detection equipment in all rooms
and areas of the household as follows: A Smoke Alarm installed in each separate sleeping area (in
the vicinity, but outside bedrooms), and Heat or Smoke Alarms in the living rooms, dining rooms,
bedrooms, kitchens, hallways, nished attics, furnace rooms, closets, utility and storage rooms,
basements, and attached garages.
10 SPECIAL COMPLIANCE CONSIDERATIONS
This Smoke Alarm is suitable for use in apartments, condominiums, townhouses, hospitals, day care
facilities, health care facilities, boarding houses, group homes and dormitories provided a primary re
detection system already exists to meet re detection requirements in common areas like lobbies,
hallways, or porches. Using this Smoke Alarm in common areas may not provide sufcient warning to
all residents or meet local re protection ordinances/regulations.
This Smoke Alarm alone is not a suitable substitute for complete re detection systems in places
housing many people—like apartment buildings, condominiums, hotels, motels, dormitories, hospitals,
health care facilities, nursing homes, day care facilities, or group homes of any kind. It is not a
suitable substitute for complete re detection systems in warehouses, industrial facilities, commercial
buildings, and special-purpose non-residential buildings which require special re detection and Alarm
systems. Depending on the building codes in your area, this Smoke Alarm may be used to provide
additional protection in these facilities.
In new construction, most building codes require the use of AC or AC/DC powered Smoke Alarms only.
In existing construction, AC, AC/DC, or DC powered Smoke Alarms can be used as specied by local
building codes. THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION’S STANDARD 72 (National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269). Refer to NFPA 101 (Life Safety Code), local building codes, or consult your Fire
Department for detailed re protection requirements in buildings not dened as “households”.
FCC COMPLIANCE
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications.
However, there is no guarantee that the interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that of the receiver.
Consult the dealer or an experienced radio or TV technician for help.
! WARNING!
Changes or modications to the product, not expressly approved by First Alert, could void the user’s
authority to operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
11 GENERAL LIMITATIONS OF SMOKE ALARMS
Smoke Alarms have played a key role in reducing deaths resulting from home res worldwide.
However, like any warning device, Smoke Alarms can only work if they are properly located, installed,
and maintained, and if smoke reaches them. They are not foolproof.
Smoke Alarms may not waken all individuals. Practice the escape plan at least twice a year,
making sure that everyone is involved – from kids to grandparents. Allow children to master re
escape planning and practice before holding a re drill at night when they are sleeping. If children
or others do not readily waken to the sound of the Smoke Alarm, or if there are infants or family
members with mobility limitations, make sure that someone is assigned to assist them in re drill and
in the event of an emergency. It is recommended that you hold a re drill while family members are
sleeping in order to determine their response to the sound of the Smoke Alarm while sleeping and to
determine whether they may need assistance in the event of an emergency.
Smoke Alarms cannot work without power. Battery operated units cannot work if the batteries
are missing, disconnected or dead, if the wrong type of batteries are used, or if the batteries are not
installed correctly. AC units cannot work if the AC power is cut off for any reason (open fuse or circuit
breaker, failure along a power line or at a power station, electrical re that burns the electrical wires,
etc.). If you are concerned about the limitations of battery or AC power, install both types of units.
Smoke Alarms cannot detect res if the smoke does not reach the Alarms. Smoke from res in
chimneys or walls, on roofs, or on the other side of closed doors may not reach the sensing chamber
and set off the Alarm. That is why one unit should be installed inside each bedroom or sleeping area—
especially if bedroom or sleeping area doors are closed at night—and in the hallway between them.
Smoke Alarms may not detect re on another level or area of the home. For example, a stand-
alone unit on the second level may not detect smoke from a basement re until the re spreads. This
may not give you enough time to escape safely. That is why recommended minimum protection is
at least one unit in every sleeping area, and every bedroom on every level of your home. Even with
a unit on every level, stand-alone units may not provide as much protection as interconnected units,
especially if the re starts in a remote area. Some safety experts recommend installing interconnected
AC powered units with battery back-up (see “About Smoke Alarms”) or professional re detection
systems, so if one unit senses smoke, all units Alarm. Interconnected units may provide earlier
warning than stand-alone units since all units Alarm when one detects smoke.
Smoke Alarms may not be heard.
Though the Alarm horn in this unit meets or exceeds current
standards, it may not be heard if: 1) the unit is located outside a closed or partially closed door, 2) residents
recently consumed alcohol or drugs, 3) the Alarm is drowned out by noise from stereo, TV, trafc, air
conditioner or other appliances, 4) residents are hearing impaired or sound sleepers. Special purpose units,
like those with visual and audible Alarms, should be installed for hearing impaired residents.
The Alarm may not have time to Alarm before the re itself causes damage, injury, or death,
since smoke from some res may not reach the unit immediately. Examples of this include
persons smoking in bed, children playing with matches, when a person’s clothing catches re
while cooking, res caused by violent explosions resulting from escaping gas, or incendiary
res where the re grows so rapidly that an occupants egress is blocked even with properly
located Smoke Alarms.
Smoke Alarms are not foolproof. Like any electronic device, Smoke Alarms are made of components
that can wear out or fail at any time. You must test the unit weekly to ensure your continued
protection. Smoke Alarms cannot prevent or extinguish res. They are not a substitute for property or
life insurance.
Smoke Alarms have a limited life. The unit should be replaced immediately if it is not operating
properly. You should always replace a Smoke Alarm after 10 years from date of purchase. Write the
purchase date on the space provided on back of unit.


Produkt Specifikationer

Mærke: First Alert
Kategori: Røgdetektor
Model: SMI105-AC

Har du brug for hjælp?

Hvis du har brug for hjælp til First Alert SMI105-AC stil et spørgsmål nedenfor, og andre brugere vil svare dig




Røgdetektor First Alert Manualer

First Alert

First Alert SMI100 Manual

23 December 2024
First Alert

First Alert SMI105-AC Manual

23 December 2024
First Alert

First Alert SMI100-AC Manual

23 December 2024
First Alert

First Alert SM210 Manual

23 December 2024
First Alert

First Alert HD6135FB Manual

14 Oktober 2024
First Alert

First Alert SA410 Manual

1 Oktober 2024
First Alert

First Alert SA710LCE Manual

29 September 2024
First Alert

First Alert SA900 Manual

21 September 2024
First Alert

First Alert CO600 Manual

12 September 2024
First Alert

First Alert P1010 Manual

5 September 2024

Røgdetektor Manualer

Nyeste Røgdetektor Manualer

Pentatech

Pentatech RA170Q Manual

20 December 2024
EQ-3

EQ-3 HMIP-SWSD Manual

16 December 2024
EQ-3

EQ-3 HM-Sec-SD Manual

16 December 2024
EQ-3

EQ-3 HM-Sec-SD-2 Manual

16 December 2024
Kidde

Kidde CO120X Manual

11 December 2024
Elro

Elro FS151021M Manual

8 Oktober 2024
Elro

Elro 2001-023 Manual

3 Oktober 2024
FireHawk

FireHawk FHB10 Manual

2 Oktober 2024