Gossen Metrawatt METRALINE VT SENSE M611K Manual

Gossen Metrawatt Måling METRALINE VT SENSE M611K

Læs nedenfor 📖 manual på dansk for Gossen Metrawatt METRALINE VT SENSE M611K (4 sider) i kategorien Måling. Denne guide var nyttig for 7 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/4
Operating Instructions
3-447-258-15
1/6.24
METRALINE VT SENSE
(M611K)
Non-contact voltage tester
© Gossen Metrawatt GmbH
Prepared in Germany Subject to change, errors excepted • A
pdf version is available on the Internet
All trademarks, registered trademarks, logos, product names,
and company names are the property of their respective owners.
Gossen Metrawatt GmbH
Südwestpark 15
90449 Nürnberg
Germany
Phone: +49 911 8602-0
Fax: +49 911 8602-669
info@gossenmetrawatt.com
www.gossenmetrawatt.com
9 Repair
If your instrument requires repair, please contact our service
department.
Loss of warranty and guarantee claims
Unauthorized modication of the instrument is prohibited.
This also includes opening the instrument. If it can be
ascertained that the tester has been opened by unauthor-
ized personnel, no guarantee claims can be honored by
the manufacturer with regard to personal safety, measur-
ing accuracy, compliance with applicable safety measures
or any consequential damages.
The instrument may only be repaired or opened by author-
ized, qualied personnel who are familiar with the associated
dangers. Original replacement parts may only be installed by
authorized, qualied personnel.
10 Contact, support and service
Gossen Metrawatt GmbH can be reached directly and
simply – we have a single number for everything! Wheth-
er you require support or training, or have an individ-
ual inquiry, we can answer all of your questions here:
+49-911-8602-0
Monday to Thursday: 8 a.m. to 4 p.m.
Friday: 8 a.m. to 2 p.m.
Or contact us by e-mail at: info@gossenmetrawatt.com
Do you prefer support by e-mail?
Measuring and Test Technology:
support@gossenmetrawatt.com
Industrial Measuring Technology:
support.industrie@gossenmetrawatt.com
Please contact GMC-I Service GmbH for repairs, replacement
parts and calibration1:
+49-911-817718-0
Beuthener Str. 41, 90471 Nürnberg, Germany
service@gossenmetrawatt.com
https://www.gmci-service.com/en/
1 DAkkS calibration laboratory per DIN EN ISO/IEC 17025
accredited by the Deutsche Akkreditierungsstelle GmbH
under reference number D-K-15080-01-01.
Content
1 Safety instructions
2 Application
3 Documentation
4 The instrument
5 Conducting tests
6 Exchange of batteries
7 Storage and Transport
8 Maintenance
9 Repair
10 Contact, support and service
1 Safety instructions
Read and follow these instructions carefully and completely in
order to ensure safe and proper use.
The instructions must be made available to all persons who use
the instrument.
Keep for future reference.
The device may only be used by qualied electricians in
the commercial eld.
The respective accident prevention regulations estab-
lished by the professional associations for electrical
systems and equipment must be strictly met at all times.
The testers have been constructed and tested in
accordance with the safety regulations for voltage testers
and have left the factory in a safe and perfect condition.
To avoid an electric shock, observe the precautions when
working with voltages exceeding 120 V (60 V) DC or 50 V
(25 V) eff AC. In accordance with DIN VDE these values
represent the threshold contact voltages (values in brack-
ets refer to limited ranges, e. g. in agricultural areas).
The tester must no longer be used if one or more func-
tions fail or if no functionality is indicated.
Before using the tester, ensure that the device is in perfect
working order. Look out e. g. for broken housing or leaking
batteries.
If the safety of the user cannot be guaranteed, the tester must
be switched off and secured against unintentional use.
Safety is no longer guaranteed in the following cases, for
example:
− obvious damage
− broken housing, cracks in housing
if the tester can no longer perform the measurements/
tests
if the tester was stored for too long in unfavorable
conditions
− transport stress
− leaking batteries
It is not permitted to use the tester during rain or
precipitation.
A correct result display is guaranteed only within a tem-
perature range of +40° C and a relative humidity of
less than 80 %.
Never use the tester in explosive environments.
Hold the tester and accessories by the designated grip
areas only; indicators must never be covered.
The tester may be used only within the specied meas-
urement ranges and in low-voltage installations of up to
1000 V.
The tester may be used only in the measuring categories
it has been designed for.
The tester may not be used to test systems or sys-
tem components for the absence of voltage.
Testing for the absence of voltage is only permissible
with a suitable (2-pole) voltage tester / voltage meas-
uring system which fulls the requirements specied in
DIN EN 61243.
The signal of the voltage test does not indicate type and/
or strength of voltage.
The tester must not be used with an open battery
compartment.
Operational safety is no longer guaranteed if the tester is
modied or altered.
The tester may be opened by an authorized service tech-
nician only.
The tester complies with all EMC regulations. Neverthe-
less, in rare cases it may disturb electric devices with its
electrical eld or the tester may be disturbed by electrical
devices.
2 Application
Please read this important information!
2.1 Intended use / Use for intended purpose
The METRALINE VT SENSE is a contactless voltage tester for
alternating voltage testing at insulated wires without requiring
direct contact with the test object. The voltage testing detects
alternating voltages between 20 VAC and 1000 VAC (2 sensitivi-
ties). The alternating voltage is indicated through a red LED,
vibration and buzzing.
In addition, the METRALINE VT SENSE can test for the pres-
ence of magnetic elds and perform rotary eld testing.
2.2 Use for other than intended purpose
Using the instrument for any purposes other than those de-
scribed in these instrument operating instructions is contrary to
use for intended purpose. Use for purposes other than those
intended may result in unforeseeable damage!
2.3 Liability and guarantee
The warranty provided by Gossen Metrawatt GmbH, and its lia-
bility, are governed by the applicable contractual and mandatory
statutory provisions.
3 Documentation
DANGER!
DANGER! Dangerous voltage. Danger of electrical shock.
Note! Important information.
4 The instrument
4.1 Scope of delivery
1 METRALINE VT SENSE
2 batteries (1.5 V, IEC LR03)
1 Operating instructions (this document)
Please check the scope of delivery for completeness and
intactness.
4.2 Device overview
1
4
3
2
5
6
9
78
1. Test tip of voltage test 2. Torch light
3. Voltage test display Magnetic eld sensor & 4.
Magnetic eld test display
5. Grip area
6. 7. ON/OFF button Torch light button
8. Battery compartment 9. Rotary eld display
4.3 Symbols on the instrument
Warning of a potential danger. Read and follow the oper-
ating instructions.
Continuous double or reinforced insulation category II
(IEC 536 / DIN EN 61140).
Position of magnetic eld sensor.
CAT IV 1000 V Measurement category
Conformity symbol, the instrument com-
plies with the valid EU directives.
It complies with the EMC Directive
(2014/30/EU) and DIN EN IEC 61326-1.
You can nd the CE declaration on our website.
The instrument may not be disposed of with household
trash. You are required to comply with all applicable local
regulations. Further information regarding disposal can be
found on our website.
4.4 Included features
The METRALINE VT SENSE is characterized by the
following features:
Measurement category CAT IV / 1000 V
Indication of operational readiness
Torch light (test point illumination)
Self test during start-up
Low battery indication
Auto power off
Meets safety standard DIN EN 61010-1
IP65 protection (DIN EN 60529)
4.5 Specications
Indications: LEDs, buzzer, vibration
Voltage range: 20 VAC…1000 VAC (2 ranges)
Frequency range: 40 Hz… 400 Hz
Frequency range (RF): 50/60 Hz
Safety as per: DIN EN 61010-1
Duty cycle: continuous
Battery: 2 × 1.5 V LR03 (AAA)
Current consumption: approx. 80 mA
Temperature range: 0 40° C, <80 % relative humidity
Dimensions: approx. 155 × 25 × 23 mm
Weight: approx. 55 g
5 Conducting tests
5.1 Preparation of testing
Before and after use, always check that the tester is work-
ing correctly (e. g. on a known voltage source).
Switch on the tester by pressing the ON/OFF button for a
short time.
The buzzer, red LED and vibration switch on for short time
as a self test.
By default, the 50 VAC 1000 VAC testing range is activat-
ed. Press the ON/OFF button briey for switching to the
20 VAC 1000 VAC range.
If a voltage source with more than 50 V is in the vicinity of
a 20 V voltage source, the tester will detect the stronger
source.
A blinking red LED indicates readiness.
The tester is switched off by pressing ON/OFF for a longer
time.
The tester automatically powers off after approx. 3 minutes.
5.2 Torch Light
Press the torch light button. As long as you hold the torch
button, the light is on.
5.3 Voltage testing
Move the device slowly along the DUT, e. g. a cable.
If the tester detects an alternating voltage in the 20 VAC
1000 VAC mode, the test tip ashes red, the tester vibrates
and the buzzer sounds.
If the tester detects an alternating voltage in the 50 VAC
1000 VAC mode, the test tip lights up in solid red, the tester
vibrates and the buzzer sounds.
The position of the earth conductor in DUT may inuence
the testing.
5.4 Magnetic eld testing
Bring the area of the tester that is marked with the magnetic
symbol near the test object. The test tip will light up yellow if
a magnetic eld is detected.
5.5 Rotary eld test (RF)
Entering the rotary eld test mode:
Press both buttons for approximately 3 seconds. Once the
yellow rotary eld LED lights up, the rotary eld test is ready
for testing.
Auto power-off:
After 3 minutes of inactivity.
Disable the rotary eld test mode: Press both buttons for a short
time.
Rotary eld test:
1. Enter the rotary eld mode.
2. Make sure that the yellow light is on and that the device
does not vibrate.
3. Touch the rst conductor under test until the tester starts
to vibrate.
4. Move the tester away from the rst conductor under test, it
stops vibrating.
5. Touch the second conductor under test until the tester starts
to vibrate and the rotary eld direction is indicated.
6. Wait until yellow LED is dark and until the tester has stopped
vibrating, before starting another test.
Rotary Field Indications:
red light: left rotary eld (L1-L3, L2-L1 or L3-L2)
green light: right rotary eld (L1-L2, L2-L3 or L3-L1)
blue light: the same phase (L1-L1, L2-L2 or L3-L3)
yellow light: ready
Red light at test tip and buzzing: Error – time between touch-
ing the two conductors under test was too long. Restart the
test.
Rotary eld test is optimized for CEE plugs.
Wiring can inuence rotary eld test.
6 Exchange of batteries
The red LED (without buzzing) indicates that the batteries need
replacing.
Open the battery compartment by pressing on the square
recess on the clip and pull of the battery compartment cover.
Replace the batteries according to the polarity indicated on
the tester.
Put the battery compartment cover back on.
Conrm that the battery compartment cover is properly
put back on prior to tests.
Do not throw used batteries into the household trash.
Observe the local regulations for disposal.
7 Storage and transport
Improper storage
Damage to the product and measuring error
due to environmental inuences .
Store the instrument in a protected location and only with-
in the limits of permissible ambient conditions.
Remove the batteries when the tester will not be in use
for a longer period in order to prevent possible hazard or
damage due to potentially leaking batteries.
Improper transport
Damage to the product and measuring error.
Transport the instrument only within the limits of per-
missible ambient conditions (temperature, humidity.
Only transport the instrument with sufcient protection.
8 Maintenance
The tester does not need any special maintenance if used
according to these operating instructions.
Cleaning
Turn off the tester and remove it from all test points before
cleaning.
Do not use abrasives or solvents.
Use a lightly damp cloth with neutral detergent for cleaning
the tester.


Produkt Specifikationer

Mærke: Gossen Metrawatt
Kategori: Måling
Model: METRALINE VT SENSE M611K

Har du brug for hjælp?

Hvis du har brug for hjælp til Gossen Metrawatt METRALINE VT SENSE M611K stil et spørgsmål nedenfor, og andre brugere vil svare dig




Måling Gossen Metrawatt Manualer

Måling Manualer

Nyeste Måling Manualer

Kern

Kern HMM-NP Manual

17 September 2024
Kern

Kern HDD 100-1 Manual

17 September 2024
Kern

Kern HBD 100-0 Manual

17 September 2024
Kern

Kern HBA 100-0 Manual

17 September 2024
Kern

Kern HO 5K Manual

11 September 2024
Kern

Kern FS 4-500 Manual

11 September 2024
Kern

Kern FH 100KUK Manual

11 September 2024
Kern

Kern HK-DB Manual

11 September 2024
Kern

Kern HN-D Manual

11 September 2024
Kern

Kern HED 100 Manual

10 September 2024