Enclosed MCCB 160/200/250A (JG***)
Instructions/Data Sheet
Hager Ltd.
Hortonwood 50
Telford
Shropshire
TF1 7FT
Sale Service Centre: 01952 675612
Technical Service Centre: 01952 675689
All product(s) must be installed by a suitably competent electrician
giving consideration to their intended use and in accordance with the
current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work
Act shall be complied with.
Only equipment and arrangements specied in Hagers technical
documentation / catalogue shall be used
Install in the vertical plane only.
Notice:
To prevent potential overheating from loose connections the installer
shall check connections are tightened to the torque levels stated in
these instructions prior to energising this board. This check should
include factory made connections which may have loosened in
transit.
Interface Characteristics
Rated & operational voltage (U n/Ue) 415V a.c. 50Hz
Rated insulation voltage (U i) 690V a.c. 50Hz
Rated impulse withstand voltage (U imp ) 6kV
Rated Current of the assembly (I nA ) and a circuit (I nc)
JG36BM 160A
JG37BM 160A
JG37BR 160A
JG38BR 200A
JG40BM 250A
JG41BM 250A
JG42BS 250A
JG43BS 250A
Rated conditional short-circuit current of
the assembly
25kA
Rated peak withstand current (Ipk) 52.5kA
Rated diversity factor (RDF) / values of
assumed loading
RDF = 1
Rated frequency (fn) 50Hz
Enclosed MCCB Assembly BS EN 61439-2
MCCB only BS EN 60947-2
Degree of protection IP3X with cover tted
Intended location Indoor use only
Mechanical impact protection IK05
Type of construction Fixed parts
Intended use Skilled persons only
Electromagnetic compatibility Environment B
Stationary assembly external design Wall mounted
Pollution degree 3
Form of separation Form 2a
Connections of functional unit:-
Incoming/Outgoing circuit connection
F (Fixed)
Suitable earthing system (When installed
in an electrical system conforming to BS
7671)
TNC-S. TN-S & TT
Height
A
Depth
B
Width
C
Weight
(kg)
JG36BM 660 120 260 10.5
JG37BM 660 120 260 10.5
JG37BR 765 120 260 11.5
JG38BR 765 120 260 11.5
JG40BM 660 120 260 10.5
JG41BM 660 120 260 10.5
JG42BS 660 120 260 10.5
JG43BS 660 120 260 10.5
Width Depth
Height
Warranty
This distribution board is offered with a 24 month warranty against
defective material or manufacture. If a warranty claim is necessary,
please call the technical support number given at the bottom of the
page and we will be pleased to help.
GB
1 ZD0754 - Issue 3 11-15
ZD0754ZD0754


Produkt Specifikationer

Mærke: Hager
Kategori: Ikke kategoriseret
Model: JG41BM

Har du brug for hjælp?

Hvis du har brug for hjælp til Hager JG41BM stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Hager Manualer

Hager

Hager JF300CF Manual

22 November 2024
Hager

Hager EC801250CT Manual

22 November 2024
Hager

Hager NCN110A Manual

11 Oktober 2024
Hager

Hager JK108BSH Manual

4 Oktober 2024
Hager

Hager VML406AH Manual

3 Oktober 2024
Hager

Hager JK116BA3 Manual

3 Oktober 2024
Hager

Hager JKD188TM Manual

27 September 2024
Hager

Hager JK104BF Manual

22 September 2024
Hager

Hager JG27BR Manual

22 September 2024
Hager

Hager TXA606B Manual

18 September 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Kramer

Kramer VP-8X8 Manual

25 November 2024
Kramer

Kramer PT-2C Manual

25 November 2024
Lazer

Lazer Bob+ Manual

25 November 2024
Dometic

Dometic DPS 80 Manual

25 November 2024
Kramer

Kramer 102MX Manual

25 November 2024
Kramer

Kramer FC-18 Manual

25 November 2024
Kramer

Kramer DSP-62-UC Manual

25 November 2024
Tiger

Tiger SKF-H101 Manual

25 November 2024