JG79J919H01 Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
75 mm hole saw
Torque wrench
Wrench (or spanner)
4 mm hexagonal wrench
Flare tool for R32, R410A
Gauge manifold for R32, R410A
Vacuum pump for R32, R410A
Charge hose for R32, R410A
Pipe cutter with reamer
SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
ENGLISH
Model names are indicated in 1-3.
REFRIGERANT
Appropriate personal protective equipment
The installer should ensure they check the respective Work Health
and Safety (WHS) Act within their jurisdiction as the requirements
and obligations may differ.
1. BEFORE INSTALLATION
MEANINGS OF SYMBOLS DISPLAYED ON INDOOR UNIT AND/OR OUTDOOR UNIT
WARNING
5LVNRI¿UH
7KLVXQLWXVHVDÀDPPDEOHUHIULJHUDQW
,IUHIULJHUDQWOHDNVDQGFRPHVLQFRQWDFWZLWK¿UHRUKHDWLQJSDUWLWZLOOFUHDWHKDUPIXOJDVDQGWKHUHLVULVNRI¿UH
Read the OPERATING INSTRUCTIONS carefully before operation.
Service personnel are required to carefully read the OPERATING INSTRUCTIONS and INSTALLATION MANUAL before operation.
Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION MANUAL, and the like.
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
 %HVXUHWRREVHUYHWKHZDUQLQJVDQGFDXWLRQVVSHFL¿HGKHUHDVWKH\LQFOXGHLPSRUWDQWLWHPVUHODWHGWRVDIHW\
After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.
When using this product in Australia, carefully read the Australian Institute of Refrigeration and Flammable refrigerants Safety Guide in Air conditioning and Heating (AIRAH) as well.
CAUTION
WARNING
Do not install the unit by yourself (user).
,QFRPSOHWH LQVWDOODWLRQ FRXOG FDXVH ¿UH HOHFWULF VKRFN
injury due to the unit falling, or leakage of water. Consult
the dealer from whom you purchased the unit or a quali-
¿HGLQVWDOOHU
Perform the installation securely referring to the in-
stallation manual.
,QFRPSOHWH LQVWDOODWLRQ FRXOG FDXVH ¿UH HOHFWULF VKRFN
injury due to the unit falling, or leakage of water.
When installing the unit, use appropriate protective
equipment and tools for safety.
Failure to do so could cause injury.
Install the unit securely in a place which can bear the
weight of the unit.
If the installation location cannot bear the weight of the
unit, the unit could fall causing injury.
Do not alter the unit.
 ,WPD\FDXVH¿UHHOHFWULFVKRFNLQMXU\RUZDWHUOHDNDJH
(OHFWULFDOZRUNVKRXOGEHSHUIRUPHGE\DTXDOL¿HG
experienced electrician, according to the installation
manual. Be sure to use an exclusive circuit. Do not
connect other electrical appliances to the circuit.
 ,IWKHFDSDFLW\RIWKHSRZHUFLUFXLWLVLQVXI¿FLHQWRUWKHUH
LVLQFRPSOHWHHOHFWULFDOZRUNLWFRXOGUHVXOWLQD¿UHRUDQ
electric shock.
Earth the unit correctly.
Do not connect the earth to a gas pipe, water pipe, light-
ning rod, or telephone earth. Defective earthing could
cause electric shock.
Do not damage the wires by applying excessive
pressure with parts or screws.
 'DPDJHGZLUHVFRXOGFDXVH¿UHRUHOHFWULFVKRFN
Be sure to cut off the main power in case of setting
up the indoor P.C. board or wiring works.
Failure to do so could cause electric shock.
 8VH WKH VSHFL¿HG ZLUHV WR FRQQHFW WKH LQGRRU DQG
RXWGRRUXQLWVVHFXUHO\DQGDWWDFKWKHZLUHV¿UPO\WR
the terminal block connecting sections so the stress
of the wires is not applied to the sections. Do not
extend the wires, or use intermediate connection.
 ,QFRPSOHWHFRQQHFWLQJDQGVHFXULQJFRXOGFDXVH¿UH
'RQRWLQVWDOOWKHXQLWLQDSODFHZKHUHLQÀDPPDEOH
gas may leak.
If gas leaks and accumulates in the area around the unit,
it could cause an explosion.
Do not use intermediate connection of the power
cord or the extension cord and do not connect many
devices to one AC outlet.
 ,WFRXOGFDXVHD¿UHRUDQHOHFWULFVKRFNGXHWRGHIHFWLYH
contact, defective insulation, exceeding the permissible
current, etc.
%HVXUHWRXVHWKHSDUWVSURYLGHGRUVSHFL¿HGSDUWV
for the installation work.
The use of defective parts could cause an injury or leak-
DJHRIZDWHUGXHWRD¿UHDQHOHFWULFVKRFNWKHXQLWIDOO-
ing, etc.
When plugging the power supply plug into the outlet,
make sure that there is no dust, clogging, or loose
parts in both the outlet and the plug. Make sure that
the power supply plug is pushed completely into the
outlet.
If there is dust, clogging, or loose parts on the power
supply plug or the outlet, it could cause electric shock or
¿UH ,IORRVH SDUWVDUH IRXQG RQ WKH SRZHU VXSSO\SOXJ
replace it.
Attach the electrical cover to the indoor unit and the
service panel to the outdoor unit securely.
If the electrical cover of the indoor unit and/or the service
panel of the outdoor unit are not attached securely, it
FRXOG UHVXOW LQ D ¿UH RU DQ HOHFWULF VKRFN GXH WR GXVW
water, etc.
When installing, relocating, or servicing the unit,
make sure that no substance other than the speci-
¿HGUHIULJHUDQW5HQWHUVWKHUHIULJHUDQWFLUFXLW
Any presence of foreign substance such as air can
cause abnormal pressure rise and may result in explo-
sion or injury. The use of any refrigerant other than that
VSHFL¿HG IRU WKH V\VWHP ZLOO FDXVH PHFKDQLFDO IDLOXUH
system malfunction, or unit breakdown. In the worst
case, this could lead to a serious impediment to securing
product safety.
Do not discharge the refrigerant into the atmos-
phere. If refrigerant leaks during installation, venti-
late the room. Check that the refrigerant does not
leak after installation has been completed.
 ,IUHIULJHUDQWOHDNVDQGFRPHVLQFRQWDFWZLWK¿UHRUKHDW-
ing part of such a fan heater, kerosene heater, or cooking
stove, it will create harmful gas.
Use appropriate tools and piping materials for instal-
lation.
The pressure of R32 is 1.6 times more than R22. Not
using appropriate tools or materials and incomplete in-
stallation could cause the pipes to burst or injury.
When pumping down the refrigerant, stop the com-
pressor before disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the com-
pressor is running and the stop valve is open, air could
be drawn in and the pressure in the refrigeration cycle
could become abnormally high. This could cause the
pipes to burst or injury.
When installing the unit, securely connect the refrig-
erant pipes before starting the compressor.
If the compressor is started before the refrigerant pipes
are connected and when the stop valve is open, air could
be drawn in and the pressure in the refrigeration cycle
could become abnormally high. This could cause the
pipes to burst or injury.
)DVWHQDÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HG
in this manual.
,IIDVWHQHG WRR WLJKW D ÀDUHQXW PD\ EUHDNDIWHU DORQJ
period and cause refrigerant leakage.
The unit shall be installed in accordance with na-
tional wiring regulations.
:KHQXVLQJ D JDVEXUQHU RURWKHUÀDPHSURGXFLQJ
equipment, completely remove all of the refrigerant
from the air conditioner and ensure that the area is
well-ventilated.
,I WKH UHIULJHUDQW OHDNV DQG FRPHV LQ FRQWDFW LQ ¿UH RU
heating part, it will create harmful gas and there is risk of
¿UH
Do not use means to accelerate the defrosting pro-
cess or to clean, other than those recommended by
the manufacturer.
The appliance shall be stored in a room without con-
tinuously operating ignition sources (for example:
RSHQÀDPHVDQRSHUDWLQJJDVDSSOLDQFHRUDQRSHU-
ating electric heater.
Do not pierce or burn.
Be aware that refrigerants may not contain an odour.
Pipe-work shall be protected from physical damage.
The installation of pipe-work shall be kept to a mini-
mum.
Compliance with national gas regulations shall be
observed.
Keep any required ventilation openings clear of ob-
struction.
In Australia, only technicians that possess the ap-
propriate license issued by the Australian Refrigera-
tion Council (ARC) should install this product.
Install an earth leakage breaker depending on the
installation place.
If an earth leakage breaker is not installed, it could cause
electric shock.
Perform the drainage/piping work securely according
to the installation manual.
If there is defect in the drainage/piping work, water could
drop from the unit, soaking and damaging household goods.
 'RQRWWRXFKWKHDLULQOHWRUWKHDOXPLQXP¿QVRIWKH
outdoor unit.
This could cause injury.
Do not install the outdoor unit where small animals
may live.
If small animals enter and touch the electric parts inside the
XQLWLWFRXOGFDXVHDPDOIXQFWLRQVPRNHHPLVVLRQRU¿UH
Also, advise user to keep the area around the unit clean.
Do not operate the air conditioner during interior
FRQVWUXFWLRQDQG¿QLVKLQJZRUNRUZKLOHZD[LQJ
WKHÀRRU
Before operating the air conditioner, ventilate the room
well after such work is performed. Otherwise, it may cause
volatile elements to adhere inside the air conditioner,
resulting in water leakage or scattering of dew.
(Could lead to serious injury in particular environments when operated incorrectly.)
(Could lead to death, serious injury, etc.)