Panduit FDCZO-24-10ULH Manual
Panduit
uklassificeret
FDCZO-24-10ULH
Læs nedenfor 📖 manual på dansk for Panduit FDCZO-24-10ULH (3 sider) i kategorien uklassificeret. Denne guide var nyttig for 5 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere
Side 1/3
FlexCore™ Front-Access Fiber Optic Cassettes
w w w.p and uit .c om
S P E C I F I C A T I O N S H E E T
c o n s t r u c t i o n
Fiber types
Multimode: OM4 50/125 m
OM5 50/125 m
OM4+ Sig Core 50/125 m
Singlemode: OS2 9/125 m
Front connectivity
MPO-LC Cassette: 2xMPO-12 to 12xDuplex LC
2xMPO-12 to 12xDuplex LC/APC
All singlemode MPOs are angled polish (APC)
All multimode MPOs are at polish (UPC)
Splice Cassette: 12 Duplex LC
12 Duplex LC/APC
8mm max cable OD
Splice Only Cassette: No front connectivity
8mm max cable OD
Tethered Cassette: 12 Duplex LC, 1 × 24-ber cable pigtail
e n v i r o n m e n t a l p r o p e r t i e s
Operating temperature: 0°C – 70°C
(32°F – 158°F)
Storage and shipping
temperature:
-40°C – 70°C
(-40°F – 158°F)
Installation temperature: 0°C – 60°C
(32°F – 140°F)
t e c h n i c a l i n f o r m a t i o n
FlexCore™ Front Access Fiber Optic Cassettes offer a wide range of deployment options for the
FlexCore™ Optical Distribution and Splice Frame. Cassettes are available with front MPO and
LC connectivity, with MPO connectors positioned on the right side or left side of the cassette
to simplify and optimize cable management within the frame. Splice cassettes with front LC
connectivity are available with bare 250 m or 12-ber ribbon pigtails. Cable entry points are
located on both sides of the cassettes to provide convenient cable routing options. Pre-terminated
tethered cassettes are available with 24-ber loose tube (non-ribbon) plenum or Euroclass B2ca/
LSZH cable pigtails of congurable lengths. A splice-only cassette with no front connectivity is
also available for direct cable-to-cable splicing within the frame.
a p p l i c a t i o n s
FlexCore™ Front Access Fiber Optic Cassettes are used within the FlexCore™ Optical Distribution and Splice Frame to provide numerous options
for breaking out high ber count cables into smaller units for distribution throughout the datacenter.
p e r f o r m a n c e p r o p e r t i e s
Insertion loss
Multimode: Optimized MPO-LC Cassette: 0.5dB max
Ultra Low MPO-LC Cassette: 0.35dB max
Optimized Splice Cassette: 0.15dB max
Ultra Splice Cassette: 0.10dB max
Optimized Tethered Cassette: 0.15dB max
Ultra Tethered Cassette: 0.10dB max
Singlemode: Standard MPO-LC Cassette: 0.75dB max
Standard Splice Cassette: 0.35dB max
Standard Tethered Cassette: 0.35dB max
Return loss (per ber)
Multimode: >26dB (LC)
Singlemode: >55dB (LC)
>65dB (LC/APC)
Connector
durability:
Connectors meeting ANSI/TIA-586C.3
Durability: 500 mating cycles
Fiber count: 24 (cassette and tethered cassette)
24 (splice cassettes)
24 discrete splice, 48 ribbon splice (splice only)
Split sleeve
material:
Zirconia ceramic
s t a n d a r d s
Meets or exceeds: ISO/IEC 11801, ANSI/TIA-568-C.3, TIA-604-5
(FOCIS-5), TIA-604-10 (FOCIS-10), RoHS 2002/95/EC compliant
supports IEEE802.3 and ANSI T11.2 (Fiber Channel) link
specications
Produkt Specifikationer
Mærke: | Panduit |
Kategori: | uklassificeret |
Model: | FDCZO-24-10ULH |
Har du brug for hjælp?
Hvis du har brug for hjælp til Panduit FDCZO-24-10ULH stil et spørgsmål nedenfor, og andre brugere vil svare dig
uklassificeret Panduit Manualer
10 August 2024
uklassificeret Manualer
Nyeste uklassificeret Manualer
21 August 2024
18 August 2024
8 August 2024
6 August 2024