Qubino ZMNHXD8 Manual


Læs nedenfor 📖 manual på dansk for Qubino ZMNHXD8 (1 sider) i kategorien Måleudstyr. Denne guide var nyttig for 7 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/1
3-Phase Smart Meter
ORDERING CODE
Z-WAVE FREQUENCY
ZMNHXD1
868,4 MHz
ZMNHXD2
921,4 MHz
ZMNHXD3
908,4 MHz
ZMNHXD4
869,0 MHz
ZMNHX D5
916,0 MHz
ZMNHXD8
865,2 MHz
This 3-Phase Smart Meter is used for energy
measurements in three-phase electrical power network
and can be used in residential, industrial and utility
applications. Meter measure energy directly in 4-wire
networks according to the principle of fast sampling of
voltage and current signals. A built-in microprocessor
calculates energy, power and power factor from the
measured signals.
The module can be controlled through Z-wave network
and it acts as repeater in order to improve range and
stability of Z-wave network.
It is designed to be mounted on DIN rail.
Installation
To prevent electrical shock and/or equipment
damage, disconnect electrical power: remove main
fuse or put on OFF position a main disconnection
switch (or circuit breaker if it is compliant to standard
IEC947-2), before installation or any servicing.
Make sure, that no voltage is present in the
installation.
Prevent the disconnecting device from being
switched on accidentally.
Connect the module according to electrical diagram.
Locate the antenna far from metal elements (as far
as possible).
Danger of electrocution!
Module installation requires a great degree of skill
and may be performed only by a qualied and
licensed electrician.
Even when the module is turned o, voltage may be
present on its terminals.
Note!
Do not connect the module to loads exceeding
recommended values. Connect the module only in
accordance to the below diagrams. Improper connections
may be dangerous.
Electrical installation must be protected by over current
protection fuse must be with rated current up to 80A,it
used according to wiring diagram to achieve appropriate
overload protection of the module.
Package contents
3-Phase Smart Meter
Electrical diagram 230VAC
Notes for the diagram:
L1 I, L2
I, L3I
Live input
Ni
Neutral input
L1 O, L2
O, L3O
Live output
No
Neutral output
16
Input for IR external relay/Ext. relay
15
Output for External relay (max. 3W)
S
Service button (used to add or remove
module from the Z-Wave network).
LED1
Green - Power on (solid) / no ID
(blinking slow 1s) / Inc./Exc. mode
(blinking fast 0,5s)
LED2
Yellow on output on (any) / Yellow
o outputs o (both) / Blinking IR
communication error
IR
Output for IR external relay (BICOM)
500imp/kWh
Red - lse rate (On no load Pu
indication)
Measurements
Voltage
V
Current
I
Power Active
W
Power Active total Import
kWh
Power Active total Export
kWh
Energy Reactive
var
Energy Reactive total
kvarh
Energy Apparent total
kVAh
Power Factor
PF
External relays
It is possible to connect two external relay to Smart Meter
module. One controlled by built-in optical (IR)
communication port on the side, second controlled by
output on terminal 1 5.
Module Inclusion (Adding to Z-wave
network)
Connect module to power supply
enable add/remove mode on main controller
auto-inclusion (works for about 2 minutes after
connected to power supply) or
press service button between 2 and 6 seconds S
NOTE: For auto-inclusion procedure, rst set main
controller into inclusion mode and then connect module to
power supply.
Module Exclusion/Reset (Removing
from Z-Wave network)
Connect module to power supply
enable add/remove mode on main controller and
press S button between 2 and 6 seconds
press service button between and 20 seconds . S6
The reset is only possible rst minute after the
power on
By this function all parameters of the module are set to
default values and own ID is deleted.
If service button S is pressed more than 2 and less than 6
seconds module is excluded, but conguration
parameters are not set to default values.
Technical Specications
Main terminals 1(L I, L2I, L3I, NO, L1O, L2O, L3O, NO)
Contacts capacity: 2.5 ... 16 (25) mm
2
Connection screws: M5
Max torque: 3.5 Nm (PZ2)
Optional terminals (DI, DO)
Contact capacity: 1 ... 2.5 mm
2
Screws: M3
Max torque: 1.2 Nm
Measuring input:
Type (connection): three phase ( ) 4u
Basic current (Ib 5 A ):
Maximum current (Imax): A 80
Minimum current (Imin): 0.25 A
Starting current: 20 mA
Reference voltage (Un): /400V 3X230V
Power consumption at Un: 8 VA <
Nominal frequency (fn): 50 and 60 Hz
Accuracy:
Active energy and power:
Standard 62053- : class 1 EN 21
Standard EN 50470- class B 3:
Reactive energy:
Standard EN 62053-23: class 2
LED:
Colour: red
Pulse rate: 500 imp/kWh
Led on: no load indication
Optical communication:
Type: IR - used to control
BICOM432- - 40 IR
Input ( 16):
Rated voltage: 230 V (± 20%)
Input resistance: 450 kOhm
LCD:
Display 7+1 digit (100Wh resolution)
Safety:
Indoor Meter: yes
Degree of pollution: 2
Protection class: II
AC voltage test: 4 kV
Installation Category: 300 Vrms cat. III
Standard: EN 50470
Ambient conditions and EMC:
According standards for indoor active energy Meters.
Temperature and climatic condition according to
EN - 62052 11
Ambient conditions and Safety:
According standards for indoor active energy Meters.
Temperature and climatic condition according to
EN - 62052 11
Dust/water protection: IP20
Operating temperature: -10 ... 55°C
Storage temperature: - 40 ... 70°C
Enclosure material: self extinguish
complying UL94 V
Indoor Meter: yes
Degree of pollution: 2
AC voltage test: 4 kV
Standard: EN 50470
Distance: up to 30 m indoors
(depending on building
materials)
Weight (with packaging): ( 220g 240g)
Frequency range: 868.4 MHz* -Wave , Z
Installation Din rail 35mm (EN 60715)
Dimensions (W x H x D): 53,6 x 65 x 84 mm
Package dimensions
(W x H x D): 70mm 56 x 86 x
Colour RAL 7035
* Depends on ordering code
EC Directives conformity:
EC Directive on Meas. Instruments 2004/22/EC
EC Directive on EMC 2004/108/EC
EC Directive on Low Voltage 2006/95/EC
EC Directive WEEE 2002/96/EC
Dimensional drawings:
Important disclaimer
Z-Wave wireless communication is inherently not always
100% reliable, and as such, this product should not be
used in situations in which life and/or valuables are solely
dependent on its function.
Warning!
Do not dispose of electrical appliances as unsorted
municipal waste, use separate collection facilities. Contact
your local government for information regarding the
collection systems available. If electrical appliances are
disposed of in landlls or dumps, hazardous substances
can leak into the groundwater and get into the food chain,
damaging your health and well-being. When replacing old
appliances with new once, the retailer is legally obligated
to take back your old appliance for disposal at least for
free of charge.
This user manual is subject to change and improvement
without notice.
Goap d.o.o. Nova Gorica
Ulica Klementa Juga 007
5250 Solkan
Slovenia
E-mail: info@qubino.com
Tel: +386 5 335 95 00
Web: www.qubino.com
Date: 15. .2017 04
Document: Qubino_3-Phase-Smart Meter
PLUS_v1 .0_eng
For more informatio please look at extended manual.


Produkt Specifikationer

Mærke: Qubino
Kategori: Måleudstyr
Model: ZMNHXD8

Har du brug for hjælp?

Hvis du har brug for hjælp til Qubino ZMNHXD8 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Måleudstyr Qubino Manualer

Qubino

Qubino ZMNHXD2 Manual

27 August 2024
Qubino

Qubino ZMNHXD8 Manual

27 August 2024
Qubino

Qubino ZMNHXD3 Manual

27 August 2024
Qubino

Qubino ZMNHXD4 Manual

27 August 2024
Qubino

Qubino ZMNHXD5 Manual

27 August 2024

Måleudstyr Manualer

Nyeste Måleudstyr Manualer

Stamos

Stamos S-LS-28 Manual

15 Oktober 2024
Stamos

Stamos S-LS-86 Manual

15 Oktober 2024
Stamos

Stamos S-LS-61 Manual

15 Oktober 2024
Stamos

Stamos S-LS-81 Manual

15 Oktober 2024
Stamos

Stamos S-LS-84 Manual

15 Oktober 2024
Stamos

Stamos S-LS-74 Manual

15 Oktober 2024
Stamos

Stamos S-LS-42 Manual

15 Oktober 2024
Stamos

Stamos S-LS-75 Manual

15 Oktober 2024
Stamos

Stamos S-LS-35 Manual

15 Oktober 2024
Stamos

Stamos S-LS-38 Manual

15 Oktober 2024