Schneider MTN630719 Manual


Læs nedenfor 📖 manual på dansk for Schneider MTN630719 (10 sider) i kategorien Bevægelsesdetektor. Denne guide var nyttig for 25 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/10
V6307-561-00 02/08
KNX ARGUS Presence Basic
Operating instructions
Art. no. MTN6307..
GB
Surface-mounted housing for ARGUS Presence (Art.
no. MTN550619)
¼DANGER
Risk of fatal injury from electrical current.
All work carried out on the unit may only be per-
formed by skilled electricians. Observe the regu-
lations valid in the country of use, as well as the
valid KNX guidelines.
The KNX ARGUS Presence Basic (called ARGUS in the
following) is a KNX presence detector for interior ceiling
mounting.
It detects smaller movements within a circumference of
360° and a radius of 7 m (at a mounting height of 2.5 m).
|The specified ranges refer to average conditions
for the recommended mounting height and are
therefore guide values. The range and sensitivity
can vary greatly when the temperature fluctuates.
When movement is detected, a data telegram defined by
the programming is transmitted and then evaluated to
control the lighting, blinds, or heating, for example.
The ARGUS presence function continuously adjusts for
brightness in the room. If sufficient natural light is avai-
lable, the device will switch the artificial light off even if a
person is present. The overshoot time can be adjusted
using the ETS. The integrated light sensor continually
measures the brightness level and processes this infor-
mation in the application. In addition, it is possible to
measure the brightness with an external light sensor and
have it evaluated.
The device is designed for use in offices, schools, public
buildings or at home, for example. It is intended for cei-
ling mounting in a No. 60 mounting box, and can also be
mounted on the ceiling in the surface-mounted housing
for ARGUS Presence. The ARGUS has an integrated
bus coupler and its power is supplied via KNX.
Accessories
For your safety
ARGUS introduction
|Movement/presence detectors are not suitable
for use as components of an alarm system.
|Movement/presence detectors can trigger false
alarms if the installation site has been chosen un-
favourably.
Movement/presence detectors switch on as soon as
they detect a moving heat source. This can be a person,
but also animals, trees, cars or differences in temperatu-
re in windows. In order to avoid false alarms, the chosen
installation site should be such that undesired heat sour-
ces cannot be detected (see section „Selecting the in-
stallation site“).
AProgramming button
BProgramming LED
CBus connecting terminal
When selecting a suitable installation site, you should
take a number of factors into account so that the ARGUS
operates optimally.
The shorter the distance between the detected person
and the ARGUS, the better smaller movements are
detected.
When a person is walking, a larger area of detection is
available. The reference level for the detection is the
floor.
The mounting height has a direct effect on the range
and sensitivity of the ARGUS. The optimal mounting
height is 2.5 m.
The following diagram shows the ranges of the ARGUS.
They are based on average temperature conditions at a
mounting height of 2.5 m. The range of a movement de-
tector can fluctuate considerably at variable temperatu-
res.
Using ARGUS with alarm systems
Connections, displays and operating
elements
Selecting the installation site
Mounting height Area of detection
2.0 m 11 m
2.5 m 14 m
3.0 m 17 m
A
B
C
14,0 m
2,5 m
The position of the ARGUS in regard to the direction of
movement also affects detection. If possible, install the
movement detector sideways to the direction of move-
ment.
If you wish to attach several presence detectors, install
them so that the detection areas of the individual de-
vices intersect each other.
The ARGUS is designed for permanent installation on-
ly. Mount the ARGUS on a fixed base only to avoid
faulty operation caused by the movement of the detec-
tor.
To prevent undesired load switching, do not mount the
switched luminaire directly in the detection area of the
ARGUS.
Avoid mounting the device above a luminaire (e.g.
standard lamp). The heat radiation of the luminaire
can influence the function of the ARGUS. Brightness
can no longer be measured when there is direct light
incidence. If luminaires are mounted in the ARGUS
detection area, a distance of at least 3 m must be com-
plied with when the connection load is high.
1The ARGUS is connected via a bus connecting ter-
minal and snapped onto the retaining ring.
AFlush-mounted installation
BSurface-mounted installation
For flush-mounted installation, the retaining ring inclu-
ded with supply is fixed with two screws to a size 60 in-
stallation box. For surface mounting, the retaining ring is
mounted in the surface-mounted housing which is avai-
lable as an accessory.
1Press the programming button.
The programming LED lights up.
2Load the physical address and application into the
device from the ETS.
The programming LED goes out.
The application has been loaded successfully, the de-
vice is ready for operation.
ARGUS installation
Putting ARGUS into operation
OK OK
A B
1


Produkt Specifikationer

Mærke: Schneider
Kategori: Bevægelsesdetektor
Model: MTN630719

Har du brug for hjælp?

Hvis du har brug for hjælp til Schneider MTN630719 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Bevægelsesdetektor Schneider Manualer

Bevægelsesdetektor Manualer

Nyeste Bevægelsesdetektor Manualer

DSC

DSC PG9862 Manual

13 September 2024
Maxsa

Maxsa 40234 Manual

11 September 2024
Maxsa

Maxsa 43218 Manual

11 September 2024
Hikvision

Hikvision DS-PDD12-EG2 Manual

10 September 2024
ORNO

ORNO OR-CR-233 Manual

9 September 2024
ORNO

ORNO OR-CR-219 Manual

9 September 2024
ORNO

ORNO OR-CR-232 Manual

9 September 2024
ORNO

ORNO OR-CR-231 Manual

9 September 2024