3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Photoelectric Smoke Detector
2-Wire: 2WTR-B (Form C Relay), 2WTA-B (Sounder)
4-Wire: 4WTR-B (Form C Relay), 4WTA-B (Sounder)
4WTAR-B (Form C Relay, Sounder), 4WITAR-B (Isolated Thermal, Form C Relay, Sounder)
Series
BEFORE INSTALLING
Please read thoroughly System Sensor’s Applications Guide for System Smoke
Detectors (SPAG91), which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. This is available online
from System Sensor’s web site: www.systemsensor.com.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly follow-
ing National Fire Protection Association (NFPA) 72 National Fire Alarm Code
requirements. At a minimum, cleaning should be performed annually.
GENERAL DESCRIPTION
Models 2WTR-B and 2WTA-B are 2-wire photoelectric smoke detectors; models
4WTR-B, 4WTA-B, 4WTAR-B, and 4WITAR-B are 4-wire photoelectric smoke
detectors. All models incorporate a state-of-the-art optical sensing chamber
and an advanced microprocessor. The microprocessor allows the detector to
automatically adjust its sensitivity back to the factory setting when it becomes
more sensitive due to contaminants settling in its chamber. In order for this
feature to work properly, the chamber must never be opened while power is
applied to the smoke detector. This includes cleaning, maintenance or screen
replacement. All models also feature a restorable, built-in, fixed temperature
(135°F) thermal detector and are also capable of sensing a freeze condition if
the temperature is below 41°F.
Models 2WTA-B, 4WTA-B, 4WTAR-B, and 4WITAR-B contain a piezoelectric
horn which generates the ANSI S3.41 temporal pattern in an alarm condition.
All detectors on a zone will sound when the power supply to them is reversed.
The RRS-MOD can be used for the power supply reversal function. The RRS-
MOD also enables all the detectors’ sounders on a zone to be synchronized
and allows the zone to be silenced from the panel by entering the alarm si-
lence key at the keypad.
The detector that initiated the alarm condition will have its red LED and Form
C relays (if applicable) latched until reset by panel.
The model 4WITAR-B photoelectronic smoke sensor is isolated from the fixed-
temperature heat sensor, providing a self-resetting, local audible smoke alarm
that does not alarm at the panel. Only the fixed-temperature heat sensor will
cause the 4WITAR-B to initiate an alarm at the panel and the relay to change
its state.
NOTE: In order for all i3 sounder detectors on a loop to sound when the panel
alarms, the supply voltage polarity must be reversed. A reversing relay, System
Sensor model number RRS-MOD, must be used. The RRS-MOD is designed
to allow all i3 Series detectors in the same loop to sound when one of the
detectors goes into alarm. In addition, the RRS-MOD will synchronize all of
the i3 Series sounder smoke detectors on the loop. Some panels may require
the use of programmable outputs. Refer to System Sensor literature for further
information on the RRS-MOD.
All i3 Series detectors are designed to provide open area protection. Two-wire models
must be used with compatible UL Listed panels only.
ELECTRICAL SPECIFICATIONS
2-wire 4-wire
System Voltage –Nominal: 12/24 12/24 V
(Non-polarized for 2WTR-B and 4WTR-B)
Min.: 8.5 10 V
Max.: 35 35 V
Max. Ripple Voltage: 30 30 % peak to peak of applied voltage
Avg. Standby Current: 50 50 µA average
Peak Standby Current: 100 — µA
Max. Alarm Current
4WTA-B, 4WTR-B: — 35 mA
4WTAR-B, 4WITAR-B: — 50 mA
2WTR-B: 130 — mA panel must limit current
2WTA-B: 130*
Alarm Contact Ratings: — 0.5 A @ 30 V AC/DC
Form C Contact Ratings: 2 2 A @ 30 V AC/DC
Audible Signal
(temp-3 tone): 85 85 dBA min. in alarm or supply polarity reversed (Sounder units only)
Remote Annunciator Output: 7 — mA maximum
EOL Relay: — 12/24 EOLR-1
Reset Time (min): 0.3 0.3 seconds
Max. Start-up Capacitance: 0.1 — µF
Max. Initial Start-up Time: 45 15 seconds
AlarmVerification** Start-up Time: 15 15 seconds
* Direct Power (Non-reverse Polarity): 130 mA limited by panel.
Reverse Polarity Power: 30 mA for the 2WTA-B in alarm; 12 mA for all other 2WTA-B units on the loop. Add 25 mA for the RRS-MOD reversing relay alarm current.
** Assumes the panel’s alarm verification reset time is 10 seconds or less. Should the alarm verification reset exceed 10 seconds, use the maximum initial start-up time.
PHYSICAL SPECIFICATIONS
Heat Sensor: 135°F (57.2°C)
Freeze Trouble: 41°F (5°C)
Operating Temperature Range: 32 to 100°F (0 to 37.8°C)
Operating Humidity Range: 0 to 95% RH non-condensing
Storage Temperature Range: –4 to 158°F (–20 to 70°C)
Diameter (including base): 5.3 inches
Height (including base): 2.0 inches
Weight: 7.1 oz.
I56-2170-010
1 I56-2170-010
02-20
Produkt Specifikationer
Mærke: | System Sensor |
Kategori: | Røgdetektor |
Model: | 4WTR-B |
Har du brug for hjælp?
Hvis du har brug for hjælp til System Sensor 4WTR-B stil et spørgsmål nedenfor, og andre brugere vil svare dig
Røgdetektor System Sensor Manualer
13 August 2024
12 August 2024
10 August 2024
10 August 2024
10 August 2024
8 August 2024
7 August 2024
7 August 2024
6 August 2024
Røgdetektor Manualer
- Røgdetektor Ikea
- Røgdetektor Hager
- Røgdetektor Ei Electronics
- Røgdetektor Gigaset
- Røgdetektor Emos
- Røgdetektor TFA
- Røgdetektor Nedis
- Røgdetektor Abus
- Røgdetektor Clas Ohlson
- Røgdetektor Smartwares
- Røgdetektor Trust
- Røgdetektor Blaupunkt
- Røgdetektor Bavaria
- Røgdetektor Vivanco
- Røgdetektor König
- Røgdetektor FireAngel
- Røgdetektor Elro
- Røgdetektor Mercury
- Røgdetektor Malmbergs
- Røgdetektor Alecto
- Røgdetektor Flamingo
- Røgdetektor Olympia
- Røgdetektor B/R/K
- Røgdetektor GEV
- Røgdetektor JUNG
- Røgdetektor ORNO
- Røgdetektor Netatmo
- Røgdetektor M-e
- Røgdetektor Somfy
- Røgdetektor EQ3
- Røgdetektor Brennenstuhl
- Røgdetektor Elgato
- Røgdetektor EVE
- Røgdetektor Pentatech
- Røgdetektor Eminent
- Røgdetektor GLORIA
- Røgdetektor Fibaro
- Røgdetektor X-Sense
- Røgdetektor EQ-3
- Røgdetektor Dahua Technology
- Røgdetektor Chacon
- Røgdetektor Stabo
- Røgdetektor First Alert
- Røgdetektor Nexa
- Røgdetektor Kogan
- Røgdetektor Esylux
- Røgdetektor Homematic IP
- Røgdetektor H-Tronic
- Røgdetektor Kidde
- Røgdetektor Schwaiger
- Røgdetektor Inovonics
- Røgdetektor Ajax
- Røgdetektor AngelEye
- Røgdetektor KlikaanKlikuit
- Røgdetektor Marquant
- Røgdetektor Gira
- Røgdetektor FireX
- Røgdetektor Interlogix
- Røgdetektor DSC
- Røgdetektor Fito
- Røgdetektor FirstAlert
- Røgdetektor Satel
- Røgdetektor FireHawk
- Røgdetektor Chuango
- Røgdetektor ETiger
- Røgdetektor TEF
- Røgdetektor SAVS
- Røgdetektor Jalo Helsinki
- Røgdetektor Fito Profi-line
- Røgdetektor Pristine
- Røgdetektor Cavius
- Røgdetektor Jemay
- Røgdetektor Mircom
- Røgdetektor WisuAlarm
- Røgdetektor BRK DICON
- Røgdetektor STI
- Røgdetektor Cordes
- Røgdetektor Deltronic
- Røgdetektor Insafe
- Røgdetektor Gewiss
- Røgdetektor Egardia
- Røgdetektor Qolsys
Nyeste Røgdetektor Manualer
16 December 2024
16 December 2024
16 December 2024
11 December 2024
14 Oktober 2024
8 Oktober 2024
8 Oktober 2024
3 Oktober 2024
2 Oktober 2024
2 Oktober 2024