User manual
TRMS ELECTRONIC DIGITAL MULTIMETERS
Read all instructions carefully
The measurement instruments in the series are electronic digital multimeters to view the EV3M TRMS
main electric measurements of 3 or 4 wire three-phase systems
The electric measurements: voltage, current, power, power factor, frequency and neutral current
are shown on three LED displays with three digits
SAFETY WARNINGS
During the installation and operation of the instrument, comply with the following instructions:
1) The product must be installed by a qualified expert.
2) Do not power or connect the instrument if it is damaged.
2) The appliance must be installed and operated in compliance with current electric systems
standards.
3) After installation, inaccessibility to the connection terminals without appropriate tools must
be guaranteed.
5) Before accessing the connection terminals, verify that the leads are not live.
6) The instrument is destined for use in environments with overvoltage category III and pollution
level 2, according to the CEI EN 61010-1 standard.
7) There must be a bipolar cut-off in the power supply network.
8) A device to protect against overloads must be installed in the electrical system upstream from
the instrument.
Code Model Description
VE333100 EV3M-D 4 DIN digital multimeter
VE334900 EV3M-R 72x72 digital multimeter
TECHNICAL CHARACTERISTICS
Power supply: 230 V AC (-15%/+10%), 50/60Hz
Input voltage: Vmax = 300V (phase-neutral)
Maximum own consumption: voltage circuits: < 2.5 VA;
current circuits: < 2.5 VA;
Input current: In = 5A; (nominal) Imax = 6A (maximum)
Accuracy: Alternating voltage: ±0.5% F.S. ±1 digit
Alternating current: ±0.5% F.S. ± 1 digit
Frequency 47-63Hz (±1Hz)
Alternating voltage: resolution 1V
minimum display: 10V
Alternating current: resolution 10mA
minimum display: 150mA with TA 5/5A
Selectable TA: x/5A type (up to 10000/5A)
Measurements taken: phase voltages (L-N); chained voltages (L-L); phase currents; phase active power;
phase apparent power; phase reactive power; power factor (cos ); frequency; φ
neutral current.
Cross-section of leads: max 6mm² pm 4DIN model;
max 2.5mm² on 72x72 model
Display: 7-segment LED display
Operating temperature: -10 ÷ +45 °C
Operating humidity: 10÷90% noncondensing
Storage temperature: -20 ÷ +60 °C
Insulation voltage: 4kV between accessible parts (front) and all terminals
Degree of Protection: IP20 / IP51 on the Front Panel
INSTALLATION
The instrument must be installed exactly as shown in the figure.
Connection for the voltage inputs is always direct, whereas an external amperometric transformer (TA) is
used for the current inputs.
Attention! The current transformer secondary circuits CANNOT be earthed.
OPERATION
Once the instrument has been installed, the pages of the various electric measurements monitored can
be viewed by pressing the key to move on to the next page, to go back to the previous page, in the d c
following order:
Page 1: PHASE VOLTAGE (L-N)
LED V(L-N) is on.
Example
field 1 230
field 2 230
field 3 230
Page 2: CHAINED VOLTAGES (L-L)
LED V(L-L) is on.
Example
field 1 300
field 2 300
field 3 300
Page 3: PHASE CURRENTS
LED (A) is on.
Example
field 1 10.8
field 2 0.53
field 3 3.00
L1
L3
L2
L1
L3
L2
L1
L3
L2
DIMENSIONS
CONNECTION DIAGRAMS
Page 4: PHASE ACTIVE POWER
LED (W) is on.
Example
field 1 100
field 2 170
field 3 120
Press the “OK” key to view the system power as follows:
Example
field 1 P
field 2 SYS
field 3 390 (calculated value)
Press OK” again to go back to the phase measurement.
Page 5: PHASE APPARENT POWER
LED (VA) is on.
Example
field 1 100
field 2 170
field 3 120
Press the “OK” key to view the system power as follows:
Example
field 1 PA
field 2 SYS
field 3 390 (calculated value)
Press OK” again to go back to the phase measurement.
Page 6: PHASE REACTIVE POWER
LED (var) is on.
Example
field 1 38.0
field 2 16.0
field 3 24.0
Press the “OK” key to view the system power as follows:
Example
field 1 Pr
field 2 SYS
field 3 78.0 (calculated value)
Press OK” again to go back to the phase measurement.
Page 7: POWER FACTOR (cosφ)
No LEDs on and the displays show the value of cos measured on each phase.φ
Example
field 1 L.86 L = inductive phase shift
field 2 C.94 C = capacity phase shift
field 3 L.82 L = inductive phase shift
If you want to display the system power factor (PF), press the key:“OK”
Example
field 1 PF
field 2 SYS
field 3 0.80 (calculated value)
Press OK” again to go back to the phase measurement.
Page 8: FREQUENCY
No LEDs on and information displayed as follows:
Example
field 1 F
field 2 50.0
field 3 (empty)
Page 9: NEUTRAL CURRENT
LED (A) is on.
Example
field 1 In
field 2 1.4
field 3 (empty)
L1
L3
L2
L1
L3
L2
L1
L3
L2
L1
L3
L2
L1
L3
L2
L1
L3
L2
L1
L3
L2
L1
L3
L2
L1
L3
L2
L1
L3
L2
Measurement unit management
The “k” and “M measurement units are associated with two LEDs which come on automatically
depending on the value of the measurement taken.
Example (with TA 5000/5A)
I1=160A; I2=1000A; I3=2500A, the information displayed will be as follows:
L1 0.16
L2 1.00
L3 2.50
LEDs “A” and “k” are on.
PARAMETER SETTING: TA AND 3 OR 4 WIRE SYSTEM
TA setting
The value of the TA secondary is 5A and cannot be modified.
To set the capacity of the primary, proceed as follows.
With the instrument turned off, hold down the key, then power the instrument. After “PRG”
approximately 3 seconds, the following information is displayed:
field 1 Pr
field 2 ct
field 3 05 (flashing)
To modify field 3 use the key (decrease). The value can be modified in steps c key (increase) or d
of 5 up to 1000A (5, 10, 15, 20, etc.) and in steps of 50 from 1000 to 10000A (1050, 1100, 1150,
etc.)
Once you have selected your chosen capacity, press to confirm.“OK”
3 or 4 wire system setting (4 wires by default)
This second setting is used by the instrument to determine the neutral current (4 wire system).
Setting page display:
field 1 Pr
field 2 SYS
field 3 04 (flashing)
To modify field 3 use the c o d keys. The selectable values are 3 or 4.
If you set the value 3 (three wire system), pages 1 (three-phase voltage) and 9 (neutral current) are
not displayed.
Press OK” again to leave the programming mode and save the settings. The instrument begins to
monitor the system. If you do not press “OK”, the instrument leaves the programming mode after 30
seconds without saving the settings made.
Subsequently, to view the TA setting, use the or arrows on page 3 (phase currents, LED “A” on) c d
and press (the parameters cannot be modified on this page). To exit press “PRG” “PRG again or
wait 30 seconds.
Note: THE TA MUST NOT BE EARTHED.
Incorrect TA connection
In case of incorrect connection of one or more TA, the display relating to the phase concerned by the
incorrect connection flashes on the active powers page [LED (W) on].
ERROR MESSAGES
Error messages
If message is shown (flashing)EEE
please contact Vemer technical support.
If message is shown (flashing)Err Par
repeat the parameter setting procedure:
cut off power, press the key and hold it down, then power the instrument again.“PRG”
Out of scale message
HHH (flashing)
Means the current and/or voltage values are beyond the full scale value.
Voltage overload V>Vmax + 6%
Current overload I>In + 20% for connection via 5/5A TA (for different TAs, multiply by the
transformation ratio).
If the page displayed is not related to the measurement in overload (out of scale), phase or chained
voltage or phase current, the message is nonetheless shown by flashing the value of the overall
measurement (if the page displayed concerns the system) or the measurements related to the
phases in overload (if the page displays the phase measurements).
Note. If at least one of the phase currents is out of scale, three dashes are displayed on the neutral
current page:
- - - (flashing)
REFERENCE STANDARDS
Compliance with Community Directives:
2006/95/EC (Low Voltage)
2004/108/EC (Electromagnetic Compatibility)
is declared with reference to the following harmonized standards:
EN 61010-1 EN 61000-6-2, and EN 61000-6-4
L1
L3
L2
L1
L3
L2
L1
L3
L2
V3IS00493-010
Mod. EV3M
DISPLAY AND KEYPAD DESCRIPTION
 









L1
L2
L3
N
L3
L2
L1
N
P1 P2
S2 S1
I
L1
L2
L3
N
L3
L2
L1
N
P1 P2
S1 S2
I
V(L-N)
L1
L3
L2
V(L-L)
A
W
VA
var
k
M
OK
PRG
EV3M-D
EV3M-R
Prg OK
V(L-N)
L1
L3
L2
V(L-L)
A
W
VA
var
k
M
EV3M-D
EV3M-D
EV3M-D
EV3M-R
EV3M-R
EV3M-R
OK
PRG
L1
L3
L2
— Parameter programming
— Increase
— Decrease
— Display / confirm data
— Field 1
— Field 2
— Field 3


Produkt Specifikationer

Mærke: Vemer
Kategori: Ikke kategoriseret
Model: EV3M-R

Har du brug for hjælp?

Hvis du har brug for hjælp til Vemer EV3M-R stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Vemer Manualer

Vemer

Vemer TCR Manual

2 Oktober 2024
Vemer

Vemer Set PC RF8 Manual

1 Oktober 2024
Vemer

Vemer ADR-D Vision Manual

22 September 2024
Vemer

Vemer ES Manual

10 September 2024
Vemer

Vemer Thalos RF Manual

3 September 2024
Vemer

Vemer VE 502E Manual

1 September 2024
Vemer

Vemer VE LAN Manual

10 August 2024
Vemer

Vemer LCR048 Manual

10 August 2024
Vemer

Vemer PSR400 Manual

8 August 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Smeg

Smeg KIT6PX Manual

23 December 2024
Smeg

Smeg KIT6CX Manual

23 December 2024
Smeg

Smeg GTA-6 Manual

23 December 2024