Emko Eco Lite Manual


Læs nedenfor 📖 manual på dansk for Emko Eco Lite (4 sider) i kategorien Temperatuurregelaar. Denne guide var nyttig for 3 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/4
3
2
1
PO1
PO2
°C
°F
/
LITE
Eco
AL1
45
6
PO1
PO2
°C
°F
/
LITE
Eco
AL1
1- Before mount ng the dev ce n your � �
panel, make sure that the cutout s of
the r ght s ze.� �
2- Check front panel gasket pos t on.� �
3- Insert the dev ce through the cutout.
If the mount ng clamps are on the un t, � �
put out them before nsert ng the un t to � �
the panel.
4- Insert the mount ng clamps to the two
of des gnated holes that located four
s des of dev ce. � �
5- Drag the mount ng clamps n � �
d rect on 5 unt l the dev ce completely � �
� �mmob le w th n the panel.
6- In order to remove dev ce push on
the mount ng clamp as shown w th � �
arrow 6 and pull back.
Introducton Brochure. ENG EcoLITE 01 V06 10/19
DISPLAY
Process D splay: 16 mm Red 3 d g t LED D splay� �
Set Value D splay: 9 mm Orange 4 d g t LED D splay� �
Led Ind cators: PO1 (Process Output-1 Status Led), PO2 (Process
Output-2 Status Led), ºC, ºF LEDs
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS
Operat ng Temperature: 0...50ºC
Hum d ty:� � 0-90%RH (none condens ng)
Protect on Class: IP65 at front, IP20 at rear
We ght: 150 gr.
D mens on: 48 x 48 mm, Depth: 86,5 mm
Panel CutOut: 46 x 46 mm
Access and Change Set Values
Eco LITE, On/Off Temperature Control Un t
- 3 d g t process (PV) and 4 d g t set (SV) d splay� � � �
- Process nput (TC,RTD)
- ON/OFF control form
- Selectable heat ng and cool ng funct on � �
- Operat ng type select on w th hysteres s � �
- Adjustment of temperature offset value
- M n mum pull ng t me adjustment for control outputs� �
- Password protect on for programm ng mode� �
Eco ser es temperature controllers are des gned for measur ng and � �
controll ng temperature. They can be used n many appl cat ons w th � �
the r TC and RTD temperature measurement � �nput, On/Off control form
and heat ng and cool ng select on. � �
They are ma nly used n glass, plast c, petro-chem stry, text le, � �
automot ve and mach ne product on � � ndustr es.
SPECIFICATIONS
Process Input: TC, RTD
Thermocouple (TC): J, K, R, S, T and L (IEC584.1)(ITS90)
Termores stance (RTD): Cu-50 and PT-100 (IEC751)(ITS90)
Measurement Range: Please refer to process nput type select on � �n
process menu parameters sect on.
Accuracy:
Thermocouple (TC):( ± 0.25% of full scale or ± 3ºC, wh ch one � �s
greater) ±1 d g t max. � �
Thermores stance (RTD):( ± 0.25% of full scale or ± C, wh ch one � �s
greater) ±1 d g t max.� �
Cold Junct on Compensat on: Automat cally ±0.1°C/1°C
L ne Compensat on: Max mum 10 Ohm
Sensor Break Protect on: Upscale
Sampl ng Cycle: 0.1 second
Input F lter: Programmable
Control Form: ON/OFF
ON/OFF Hysteres s: It can be conf gured for two control outputs
OUTPUT
Process Output - 1: Relay (5A@250V at res st ve load)V� �
Process Output - 2: Relay (5A@250VVat res st ve load)� �
ON/OFF TEMPERATURE CONTROL UNIT
LITE
Eco
SUPPLY VOLTAGE (It must be determ ned � �n order)
230V 15%) 50/60Hz - 2VAV
115V (±15%) 50/60Hz - 2VAV
100-240V 50/60Hz - 2VAV
24V (±%15) 50/60Hz - 2VAV
24V (±%15) 50/60Hz - 2VAW
10...30V - 2WZ
Electr cal W r ngs � �
The Dev ce w th One Relay:� �
The Dev ce w th Two Relays:� �
To reduce the effect of electr cal no se on dev ce, low voltage l ne (espec ally sensor � �
� � nput cable) w r ng must be separetely from h gh current and voltage l ne. If poss ble,
use sh elded cable and sh eld must be connected to ground only one s de.� �
c
LITE
Eco
1
2
3
4
5
6
7
8
9
10
11
12
13
14
C
NO
Process
Input
5A@250V
PT-100
TC
Supply
Sw tch
L
N
Supply
Voltage
1A T
Fuse
PO1
(Process Output 1)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
C
NO
NO
PO1
(Process Output 1)
PO2 / AL1
(Process Output 2 or
Alarm Output 1)
Process
Input
5A@250V
5A@250V
PT-100
TC
Supply
Sw tch
L
N
Supply
Voltage
1A T
Fuse
LITE
Eco
D mens ons� �
6 mm / 0.24 nch80,52 mm / 3.17 nch
Max mum 9 mm / 0.35 nch� �
48 mm / 1.89 nch
48 mm / 1.89 nch
PO1
PO2
°C
°F
/
LITE
Eco
AL1
Panel Mount ng
PO2
PO1
AL1
AL2
°C
°F
/
Press ncrement or decrement
button to change Set1 value.
Press Enter button to save new
Set1 value and open Set2 screen.
Ma n Screen
PO2
PO1
AL1
AL2
°C
°F
/ PO2
PO1
AL1
AL2
°C
°F
/
Ma n Screen
PO2
PO1
AL1
AL2
°C
°F
/PO2
PO1
AL1
AL2
°C
°F
/ PO2
PO1
AL1
AL2
°C
°F
/
Press ncrement or decrement
button to change Set2 value.
Press Enter button to save new
Set2 value and return ma n screen.
Note1: User can ex t from set value sect on w thout sav ng the values by press ng � �
button. If no operat on for 120 seconds, dev ce automat cally ex ts from Set Value � �
sect on.
Note2: D splayed set value at ma n screen could be changed accord ng to � �
parameter
Note3: Set values can be adjusted between Set Value Low and H gh L m ts. � �
PO2
PO1
AL1
AL2
°C
°F
/
Ma n Screen
PO2
PO1
AL1
AL2
°C
°F
/PO2
PO1
AL1
AL2
°C
°F
/
Password Screen
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
*1
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
*5
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
*4
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
*2
PO2
PO1
AL1
AL2
°C
°F
/ PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/ PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
*3
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
*3
*3
To enter program menu
press button
Enter Password w th
ncrement or decrement buttons.
Approve password
w th Enter button
*1 - M n mum pull ng t me parameter for Output-1( ) s not seen unless operat on � �
type select on for output-1 parameter( ) s set as .� �
*2 - Out-2( ) parameters are not seen on dev ces w th one relay.� �
*3 - Alarm parameters( , and ) are not seen unless operat on type
select on for output-2 parameter( ) s set as . � �
*4 - M n mum pull ng t me parameter for Output-2( ) s not seen unless operat on � �
type select on for output-2 parameter( ) s set as .� �
*5 - If s d fferent from 0 and user enters to program menu w thout enter ng the � �
password menu s not seen.
Note: User can ex t from any parameter screen w thout sav ng the values by � �
press ng button. If no operat on for 120 seconds, dev ce automat cally return to � �
the ma n screen.
Easy Access D agram For Program Parameters
: Output-1 Parameters
: Operat on Type Select on for Output-1. It can be or .� �
(Default: )
: Hysteres s Value for Output-1. It can be adjusted from %0 to %50 of
the Operat on Scale ( - ). (Default: 3)
: Set1 Value Low L m t. M n mum Set1 value s def ned w th th s � �
parameter. It can be adjusted from Operat on Scale Low L m t( ) to � �
Set1 H gh L m t( ). (Default: 0) � �
: Set1 Value H gh L m t. Max mum Set1 value s def ned w th th s � � � �
parameter. It can be adjusted from Set1 Low L m t( ) to Operat on � �
Scale H gh L m t( ). (Default: 500) � �
: M n mum Pull ng T me for Output-1. When Output-1 s nact ve th s � �
t me must be exp red for Output-1 to become act ve aga n. It can be � �
adjusted from 0 to 100 seconds. (Default: 0)
: Output-2 Parameters (Only for dev ces w th two relays)� �
: Operat on Type Select on for Output-2. It can be , or . � �
(Default: )
: Hysteres s Value for Output-2. It can be adjusted from %0 to %50 of
the Operat on Scale ( - ). (Default: 3)
: Alarm type select on. See "Alarm Types" sect on. (Default: )� �
: Set2 Value Low L m t. M n mum Set2 value s def ned w th th s � �
parameter. It can be adjusted from Operat on Scale Low L m t( ) to � �
Set1 H gh L m t( ). (Default: 0) � �
: Set2 Value H gh L m t. Max mum Set2 value s def ned w th th s � � � �
parameter. It can be adjusted from Set2 Low L m t( ) to Operat on � �
Scale H gh L m t( ). (Default: 500) � �
: M n mum Pull ng T me for Output-2. When Output-2 s nact ve th s � �
t me must be exp red for Output-2 to become act ve aga n. It can be � �
adjusted from 0 to 100 seconds. (Default: 0)
: Alarm on Delay T me. It can be adjusted from 0 to 9999 seconds.
(Default: 0)
: Alarm off Delay T me. It can be adjusted from 0 to 9998 seconds. If
� � t s h gher than 9998, s seen on the screen and alarm latch ng
output s selected. In alarm latch ng output mode n order to make � �
pass ve alarm outputs, press enter button at ma n screen. (Default: 0)� �
: Protec on Menu Parameters
: Password for access ng to the programm ng sect on. It can be � �
adjusted from 0 to 9999.If s 0, password screen s not seen. If � �
� � s d fferent from 0 and user enters to the menu pages w thout enter ng the
password, all menus can be seen except protect on menu . But
dev ce does not allow to do any changes n parameters. (Default: 0)� �
: User default parameters. Th s parameter s used for sav ng all � �
parameters to restore later or restore all parameters saved before. If
� �s chosen, all parameters saved before are restored. If s chosen, all
parameters saved to restore later. If s chosen, noth ng s changed. � �
(Default: )
: Th s parameter s used for restore factory defaults. If s chosen, � �
factory defaults parameters restored. If s chosen, noth ng s changed. � �
(Default: )
Remove all nput/output connect ons on term nals before � �
restor ng parameters to user/factory defaults.
c
: Process nput type select on. (Default: )� �
: J type (Fe,Cu,N ) Thermocouple , -199ºC,900ºC ; -199ºF,999ºF
: J type (Fe,Cu,N ) Thermocouple , -19.9ºC,99.9ºC ; -19.9ºF,99.9ºF
: K type (N ,Cr,N ) Thermocouple , -199ºC,999ºC ; -199ºF,999ºF� �
: K type (N ,Cr,N ) Thermocouple , -19.9ºC,99.9ºC ; -19.9ºF,99.9ºF� �
: R type (Pt13%RhPt) Thermocouple , 0ºC,999ºC ; 32ºF,999ºF
: R type (Pt13%RhPt) Thermocouple , 0.0ºC,99.9ºC ; 32.0ºF,99.9ºF
: S type (Pt10%RhPt) Thermocouple , 0ºC,999ºC ; 32ºF,999ºF
: S type (Pt10%RhPt) Thermocouple , 0.0ºC,99.9ºC ; 32.0ºF,99.9ºF
: T type (Cu,Cu,N ) Thermocouple , -199ºC,400ºC ; -199ºF,752ºF
: T type (Cu,Cu,N ) Thermocouple , -19.9ºC,99.9ºC ; -19.9ºF,99.9
: L type (N ,Cr,Co / N ,Fe,Mn,Cu) Thermocouple , -150ºC,800ºC ; � �
-199ºF,999ºF
: L type (N ,Cr,Co / N ,Fe,Mn,Cu) Thermocouple , -19.9ºC,99.9ºC ; � �
-19.9ºF,99.9ºF
: Cu-50 , -199ºC,200ºC ; -199ºF,392ºF
: Cu-50 , -19.9ºC,99.9ºC ; -19.9ºF,99.9ºF
: Pt-100 , -199ºC,650ºC ; -199ºF,999ºF
: Pt-100 , -19.9ºC,99.9ºC ; -19.9ºF,99.9ºF
: Un t Select on. or can be chosen. (Default: )� �
: Operat on Scale m n mum (Low L m t) value. It changes accord ng � �
to the process nput type and scale. (Default: -199)
: Operat on Scale max mum (H gh L m t) value. It changes accord ng � �
to the process nput type and scale. (Default: 900)
: D splay offset for process value. It can be adjusted from -10% of
scale to 10% ofscale. It s added to the process d splay value. (Default: 0)� �
: Def ne f lter t me(sec) for d splayed value. (Default: 1.0)� �
: Select on of wh ch set value d splayed at ma n screen.� �
(Default: )
: Process Menu Parameters