Honeywell Fire-Lite BG-12L Manual

Honeywell Skifte Fire-Lite BG-12L

Læs nedenfor 📖 manual på dansk for Honeywell Fire-Lite BG-12L (2 sider) i kategorien Skifte. Denne guide var nyttig for 29 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
BG-12L Manual Pull Station
Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending
Document 50964 I56-2263-004
Description
The BG-12L pull station is a non-coded, dual-action manual pull station with a key-lock
reset feature. It provides Fire•Lite control panels with one normally open (N/O) alarm initi-
ating input. The BG-12L meets the ADAAG controls and operating mechanisms guidelines
(section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate
the pull station. Operating instructions are molded into the pull station handle along with
Braille text. Molded Terminal numbers are also present.
Ratings
Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12L pull station can be surface mounted to an SB-10 or SB-I/O surface backbox
or semi-ush mounted on a standard single-gang, double-gang or 4 (10.16 cm) square
electrical box. The optional BG-TR trim ring can be used if the BG-12L is to be semi-ush
mounted.
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word
ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta-
tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station.
Resetting the Pull Station
1. Insert the key into the lock and rotate 1/4 turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
Note: Closing the door automatically resets the switch to the ‘Normal position. Opening
the door will not activate or deactivate the alarm switch.
STRIP GAUGE
1 2 3 4
IDC
FROM
FACP + TO NEXT
DEVICE
– IDC
+
WARNING: DO NOT LOOP WIRING
UNDER ANY TERMINALS. BREAK WIRE
RUN MAINTAIN IDC SUPERVISION.TO
P0205-00
Wiring
CAUTION! Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has already been
installed onto an electrical box.
CAUTION!
Install the FireLite BG-12L pull station in accordance with these instructions,
applicable NFPA standards, national and local Fire and Electrical codes and the requirements
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear oor space only allows forward approach to an object, the
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear oor space
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
54 inches (137.16 cm).
BG-12L
Manual Pull Station
WARNING! Do not loop wiring under any
terminals. Break wire run to
maintain IDC supervision.
Document 50964 I56-2263-004
P0194-01


Produkt Specifikationer

Mærke: Honeywell
Kategori: Skifte
Model: Fire-Lite BG-12L

Har du brug for hjælp?

Hvis du har brug for hjælp til Honeywell Fire-Lite BG-12L stil et spørgsmål nedenfor, og andre brugere vil svare dig




Skifte Honeywell Manualer

Skifte Manualer

Nyeste Skifte Manualer

Powerfix

Powerfix PSSS 2 A1 Manual

14 Januar 2025
D-Link

D-Link DES-1024D Manual

13 Januar 2025
TRENDnet

TRENDnet TEG-S5g Manual

13 Januar 2025
INOGENI

INOGENI CAM230 Manual

13 Januar 2025
Schneider

Schneider CCT15225 Manual

13 Januar 2025
Luxul

Luxul XMS-5248P Manual

13 Januar 2025
Luxul

Luxul AMS-2624P Manual

13 Januar 2025
Luxul

Luxul XGS-1005 Manual

13 Januar 2025
Luxul

Luxul AGS-1008M Manual

13 Januar 2025