Installation Manual
Type
NDR DIN rail power supply
Series
NDR-75, 120, 240, 480
NDR-75-12 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 12V 6.3A
NDR-75-24 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 24V 3.2A
NDR-75-48 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 24V 1.6A
NDR-120-12 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 12V 10A
NDR-120-24 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 24V 5A
NDR-120-48 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 48V 2.5A
NDR-240-24 INPUT: 100-240VAC 2.8A 50/60Hz OUTPUT: 24V 10A
NDR-240-48 INPUT: 100-240VAC 2.8A 50/60Hz OUTPUT: 48V 5A
NDR-480-24 INPUT: 100-240VAC 5.3A 50/60Hz OUTPUT: 24V 20A
NDR-480-48 INPUT: 100-240VAC 5.3A 50/60Hz OUTPUT: 48V 10A
Introduction
NDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Well’s DIN series,
they can be mounted on a TS35 Standard DIN rail.
Installation
( )1 Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
( )2 The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
( )3 Use copper wire only, and recommended wires are shown as below.
AWG 18 16 14 12
Rated Current of
Equipment (Amp) 7A 10A 15A 20A
Cross-section of
Lead(mm2 ) 0.8 1.3 2.1 3.3
Note: Current each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
( )4 Use wires that can withstand temperatures of at least 80°C, such as UL1007.
( )5 Recommended wire strapping length is 5mm (0.197”).
( )6 Recommended screwdriver is 3mm, slotted type.


Produkt Specifikationer

Mærke: Intellinet
Kategori: Ikke kategoriseret
Model: 509091

Har du brug for hjælp?

Hvis du har brug for hjælp til Intellinet 509091 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Intellinet Manualer

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer