Vimar 01985.120 Manual
Læs nedenfor 📖 manual på dansk for Vimar 01985.120 (1 sider) i kategorien Lysdæmper. Denne guide var nyttig for 8 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere
Side 1/1
Viale Vicenza, 14 - 36063 Marostica VI Italy
Tel. +39 0424 488 600 - Fax (Italia) +39 0424 488 188 - Fax (Export) +39 0424 488 709
www.vimar.com
MASTER dimmer 120 V~ 60 Hz for incandescent lamps 40-500 W electronic
transformers 40-300 VA, CFL lamps 10-200 W, LED lamps 3-200 W, for LED
electronic power supplies, protection fuse, installation on DIN rails (60715
TH35), occupies 4 modules size 17.5 mm. For nautical scope.
ON/OFF switch and adjustment with two built-in buttons. MOSFET+TRIAC microprocessor
technology, works in both LE (Leading Edge) and TE (Trailing Edge) modes. MASTER function,
protection fuse. The device receives commands directly from the Busbar and is able to control
the load directly. It can also control up to 3 SLAVE dimmers for DIN rails 01986.120.
IMPORTANT: Lamps controllable from a single master or slave dimmer must all be the
same. All controllable loads must be declared DIMMERABLE by the manufacturer. Check
the type of compatible dimmering on the lamp package: LE (Leading Edge) or TE (Trailing
Edge). If it is not specified, the lamp can operate in both modes (chosen at the discretion
of the installer).
CHARACTERISTICS.
• RatedsupplyvoltageTPBusbar:29V
• Ratedsupplyvoltagemains:120V~,60Hz
• AbsorptionfromTPBusbar:15mA
• Dissipatedpower:7.8W
• Terminals:N neutral, load, phase, L Ssynchronization,TPBusbar
• ProtectionfusetypeF5AH250V
• Functionsthatcanbeaccomplishedwiththedimmer:
- Switching on, off and dimmering
- Changing absolute brightness
- Actuating/saving scenarios
- Enabling "Flash Start" mode for CFL lamps
- "Ramp" operation
- Switch-off delay and warning function
-Phasecutting:LE/TE
• Localcontrols:
Pressingthe button enables using the local buttons. All messages from the busbar are
ignored.
- Briefly pressing the button :ONcontrol
- Briefly pressing the button :OFFcontrol
-Pressingandholdingdownthebutton :Increasebrightness
-Pressingandholdingdownthebutton :Decreasebrightness
In normal operation (that is when the commands are sent over the bus) pressing the buttons
for the outputs is ignored.
• Protectionagainstshort-circuitingwhenturningonwithflashingblow-outindicator.
• Thermalprotectionwithflashingblow-outindicator.
• MASTER-SLAVE function: paying attention not to exceed maximum power controllable by
each dimmer. A MASTER device can have up to 3 SLAVE dimmers (art. 01986.120) for a
maximumtotalload of2000W(VA)correspondingto500W/VAmax connectedtoeachof
the 4 devices.
• InstallationonDINrails(60715TH35),occupies4modulesof17.5mm.
CONFIGURATION.
FOR THE OPERATIONS OF INSTALLATION AND CONFIGURATION, SEE THE BY-ME
SYSTEM INSTRUCTIONS MANUAL ATTACHED TO THE CONTROL PANEL.
•Functionalunits:1;theunitcanbelongtoatmost4differentgroups.
• Selecting the functional unit (configuration): during group creation, when the control panel
requirespressingthedevicebutton:
-ItisrecommendedtoconfigurethedevicewiththeloadOFF;
-PresstheCONFbutton,theredLEDwilllightup;
- With the red LED on, the control panel will configure the functional unit; at the end of this
operation the red LED will go out.
Controllable loads LE TE
40 to 500 W 40 to 300 W
10 to 100 W 10 to 200 W(Max5lamps) (Max 10 lamps)
3 to 100 W 3 to 200 W(Max5lamps) (Max 10 lamps)
Electronic transformers
for halogen lamps
40 to 300 W
(Max 3 transformers type
L
)
40 to 300 W
(Max5transformerstype
C
)
Dimmering with Leading Edge mode Dimmering with Trailing Edge mode
INSTALLATION RULES.
Installation should be carried out in compliance with the current regulations regarding the instal-
lation of electrical systems in the country where the products are installed.
• Itshouldbeusedinplacesatatemperatureofbetween-5°Cand+45°C.
• Thelampsconnectedtothemasterorslavemustallbethesame.
• Notsuitableforcontrollingmotors(e.g.fans,ventilators).
•Theratedpowerlevelshouldneverbeexceeded.
• Overloading, power surges and short-circuits may irreparably damage dimmers. Before
installation check the circuit carefully and eliminate any of the above causes.
• The dimmer does not have a mechanical circuit breaker in the main circuit and so is not
galvanically separated. The circuit load should be considered always powered.
For further instructions see the manual enclosed with the control panel.
CONFORMITY TO STANDARDS.
For MARINE use,thisdevicehasbeensubmittedtothefollowingtests:
IEC60068-2-52-TestKb:Saltmist,cyclic(sodium,chloridesolution),
IEC60068-2-6-TestFc:Vibration(sinusoidal)
Thisdevicecomplieswithpart15oftheFCC Rules (with the limits for a Class B digital device).
Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference
that may cause undesidered operation.
FRONT VIEW
CONNECTIONS
MaximumlengthofcablesconnectinguniversalMASTERdimmeranduniversalSLAVEdimmer:100m
Connect at least the minimum load required to the universal master dimmer.
A:IndicatorLED
B:Switchingonandincreasingbrightness
C:Switchingoffanddecreasingbrightness
D:LEDandconfigurationbutton
CHANGING FUSE
OFF
1.
01985.120
MASTER DIMMER
120V~
60Hz
40-50 0W LE
40-300W T E
CONF.
NLS
By-me
NLS
BUS
NLS
2.
01986.12001985.120 01986.120
N L S
TE Flash
Soft
LE
01986.120
SLAVE
DIMMER
40-500W LE
40-300W TE
120 V~ 60 Hz
N L S
TE Flash
Soft
LE
01986.120
SLAVE
DIMMER
40-500W LE
40-300W TE
120 V~ 60 Hz
N L S
01985.120
MASTER DIMMER
120 V~ 60 Hz
40-500W LE
40-300W TE
L
N
Bus
MASTER SLAVE SLAVE
A
B
C
D
BUS TP
LN
S
N L S
01985.120
MASTER DIMMER
120 V~ 60 Hz
40-500W LE
40-300W TE
01985.120
49400502A0011309
VIMAR - Marostica - Italy
Produkt Specifikationer
Mærke: | Vimar |
Kategori: | Lysdæmper |
Model: | 01985.120 |
Har du brug for hjælp?
Hvis du har brug for hjælp til Vimar 01985.120 stil et spørgsmål nedenfor, og andre brugere vil svare dig
Lysdæmper Vimar Manualer
15 December 2024
15 December 2024
15 December 2024
15 December 2024
15 December 2024
15 December 2024
15 December 2024
15 December 2024
15 December 2024
15 December 2024
Lysdæmper Manualer
- Lysdæmper GE
- Lysdæmper Hager
- Lysdæmper TP-Link
- Lysdæmper ABB
- Lysdæmper American DJ
- Lysdæmper Sonoro
- Lysdæmper Trust
- Lysdæmper Elro
- Lysdæmper Steinel
- Lysdæmper Grässlin
- Lysdæmper Tronic
- Lysdæmper Mercury
- Lysdæmper Velleman
- Lysdæmper JUNG
- Lysdæmper Paladin
- Lysdæmper Cotech
- Lysdæmper GAO
- Lysdæmper Eminent
- Lysdæmper Kopp
- Lysdæmper Fibaro
- Lysdæmper Eurolite
- Lysdæmper Eltako
- Lysdæmper Chauvet
- Lysdæmper Arendo
- Lysdæmper Chacon
- Lysdæmper EtiamPro
- Lysdæmper Lutron
- Lysdæmper Adastra
- Lysdæmper DiO
- Lysdæmper AMX
- Lysdæmper Homematic IP
- Lysdæmper Bearware
- Lysdæmper KlikaanKlikuit
- Lysdæmper Merten
- Lysdæmper Gira
- Lysdæmper Berker
- Lysdæmper Handson
- Lysdæmper Velbus
- Lysdæmper Ltech
- Lysdæmper InterBar
- Lysdæmper Intertechno
- Lysdæmper Schneider Electric
- Lysdæmper Tradim
- Lysdæmper Ehmann
- Lysdæmper Peha
- Lysdæmper VAMA
Nyeste Lysdæmper Manualer
9 December 2024
2 December 2024
21 September 2024
14 September 2024
12 September 2024
5 September 2024
5 September 2024
5 September 2024
5 September 2024
5 September 2024