Kyoritsu KEW2117R Manual

Kyoritsu Multimeter KEW2117R

Læs nedenfor 📖 manual på dansk for Kyoritsu KEW2117R (1 sider) i kategorien Multimeter. Denne guide var nyttig for 58 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/1
INSTRUCTION MANUAL
DIGITAL CLAMP METER
KEW2117R
1. Safety Warnings
This instrument has been designed, manufactured and
tested according to IEC 61010: Safety requirements for
Electronic measuring apparatus, and delivered in the best
condition after passed the inspection. This instruction
manual contains warnings and safety rules which must be
observed by the user to ensure safe operation of the
instrument and retain it in safe condition. Therefore, read
through these operating instructions before using the
instrument.
WARNING
Read through and understand the instructions contained
in this manual before using the instrument.
Keep the manual at hand to enable quick reference
whenever necessary.
The instrument is to be used only in its intended
applications.
Understand and follow all the safety instructions
contained in the manual.
It is essential that the above instructions are adhered to.
Failure to follow the above instructions may impair the
protection provided by the instrument and test leads, and
may cause injury, instrument damage and/or damage to
equipment under test.
The symbol indicated on the instrument means that the
user must refer to the related parts in the manual for safe
operation of the instrument. It is essential to read the
instructions wherever the symbol appears in the manual.
DANGER is reserved for conditions and actions that
are likely to cause serious or fatal injury.
WARNING reserved for conditions and actions that is
can cause serious or fatal injury.
CAUTION is reserved for conditions and actions that
can cause injury or instrument damage.
Marks listed below are used on this instrument.
User must refer to the manual.
Instrument with double or reinforced insulation
Indicates that this instrument can clamp on
bare conductors when measuring a voltage
corresponding to the applicable measurement
category, which is marked next to this symbol.
AC DC Ground (Earth)
This instrument is subject to W Directive EEE
(2002/96/EC). Please contact our dealer near
you at disposal.
M urement Category eas
O Circuits which are not directly connected to the mains
power supply.
CAT II Primary electrical circuits of equipment connected
to an AC electrical outlet by a power cord.
CAT III Primary electrical circuits of the equipment
connected directly to the distribution panel, and feeders
from the distribution panel to outlets.
CAT IV The circuit from the service drop to the service
entrance, and to the power meter and primary over current
protection device(distribution panel).
This instrument is designed for CAT IV 300V / CAT III
600V. Test leads M-7066A wi the su lied cap are th pp
designed for CAT IV 600V / CAT III 1000V and wi t thou
the caps are for CAT II 1000V.
DANGER
Never make measurements under the circumstances
exceed the designed measurement category and the
rated voltage of the instrument and the test leads.
Do not attempt to m ake measurement in the presence of
flammable gasses. Otherwise, the use of the instrument
may cause sparking, which can lead to an explosion.
Never attempt to use the instrument if its surface or your
hand is wet.
Do not exceed the maximum allowable input of any
measuring range.
Never open the Battery cover during a measurement.
To avoid electrical shock by touching the equipment
under test or its surroundings, be sure to wear insulated
protective gear.
Never measure current while the test leads are inserted
into the input terminals.
Test leads to be used for voltage measurements shall be
rated as appropriate for Measurement Category III or IV
according to IEC 61010-031 and sha ll have a voltage
rating of 600V or higher.
Barriers on the instrument body and the test leads
provide protection to keep your fingers and hands from
touching an object under test. Keep your fingers and
hands behind the barriers during measurement.
WARNING
Never attempt to make measurement if any abnormal
conditions, such as broken case and exposed metal
parts are found on the instrument or test leads.
Verify proper operation on a known source before use or
take action as a result of the indication of the instrument.
Firmly attach e caps to e test leads when th th
performing measurements in CAT III or higher test
envir ments. When KEW2117R and e test leads on th
are combined and used ether, whichever is lower tog
category & voltage to earth either of em belo to th ng
is applied.
Do not rotate the Function Switch if the instrument and
the equipment under test are connected.
Do not install substitute parts or make any modif ation to ic
the instrument. For repair or re-calibration, return the
instrument to your local ORITSU distributorKY
CAUTION
Use of this instrument is limited to domestic, commercial
and light industry applications. Strong electromagnetic
interference or strong magnetic fields, generated by
large currents, may cause malfunction of the instrument.
Connect the test leads to the terminals firmly.
This instrument isn’t water proofed. Keep away from
water.
Do not pull or tw t the test leads to prevent the risk of is
damage.
Power off the instrument after use. Remove batteries if
the instrument is to be stored and wi not be in use for a ll
long period.
Do not expose the instrument to the direct sunlight, high
temperature and humidity or dewfall.
Use a cloth dipped in water or neutral detergent for
cleaning the instrument. Do not use abras ives or solvents.
NOTE
The LCD shows some digits at the ACV and the DCV
ranges even while the test leads are open. In addition,
the LCD shows some digits instead of 0 when short-
circuiting the test leads. However, these phenomena
don’t affect measurement results.
A resistance measurement takes time to settle the
reading if there are high resistance or capacitance
components.
2 Specifi tion . ca
Temperature: 23 ± 5°C, Humidity: 45 - 75%
ACA (Auto-ra e)ng
Range Display Range A uracy (sine wave)cc
60A 0.00, 0.06-62.99A ±1.5 %rdg±4dgt (45-65Hz)
±2.0 %rdg±5dgt (40-1kHz)
600A 57.0-629.9A
1000A 570-1049A
Guaranteed accuracy : 0.10A -1000A,less than 1500A Peak
Input protective current : AC1200A
ACV (Auto-ra e)ng
Range Display Range A uracy (sine wave)cc
60V 0.00, 0.06-62.99V ±1.5 %rdg±4dgt (40-1kHz)
600V 57.0-629.9V ±1.0 %rdg±2dgt (45-65Hz)
±1.5 %rdg±4dgt (40-1kHz)
Guaranteed accuracy : 0.10V - 600.0V,less than 900V Peak
Input protective voltage : AC/DC720V 10 sec
DCV (Auto-ra e)ng
Range Display Range A uracycc
60V 0.00-±62.99V ±1.0%rdg±3dgt
600V ±57.0-±629.9V ±1.2%rdg±3dgt
Guaranteed accuracy : 0.00V - ± 600.0V
Input protective voltage : AC/DC720V 10 sec
ACV/DCV input impedance : approx. 10M
Resistan Continuity ce / (Auto-ra e)ng
Range Display Range A uracycc
600 0.0-629.9 ±1.0%rdg±5dgtΩ Ω
6k 0.570-6.299 Ω Ω
±2.0%rdg±3dgt
60k 5.70-62.99 kΩ Ω
600k 57.0-629.9 kΩ Ω
Cont. 0.0-629.9 Bz threshold value <90Ω Ω
Guaranteed accuracy : 0.0 - 600.0kΩ Ω
Open-loop voltage : 3V or less
Input protective voltage : AC/DC600V 10 sec
Measuring method : Σmodulation
Over-range indication : OL
Measurement cycle : 2.5 times per second
Crest factor : less than 3 (45-65Hz)
Add ±0.5%rdg±5dgt to above specified accuracies.
(Applicable functions : ACA, ACV)
Applicable Standards :
IEC 61010-1/ 61010-2-032/ 61010-2-033 (instrument)
Pollution degree 2, Indoor use, Altitude up to 2000m
CAT III 600V / CAT IV 300V
IEC 61010-031(Test leads Model 7066A)
w/ caps CAT IV 600V / CAT III 1000V
w/o caps CAT II 1000V
Function
Switch
Cu Sensorrrent
Hold Key
LCD
V/
Terminal
COM
Terminal
Trigger
Cap
Barrier of Tes L dst ea
Ba ierrr
Wris Strapt
Screw
EN61326 (EMC)
In the radio-frequency electromagnetic field of 3V/m,
accuracy within five times the rated accuracy.is
EN50581 (RoHS)
Withstand voltage : AC5160Vrms 5sec
between current sensor and enclosure or
circuit and enclosure
IP rating : IP40 (IEC60529)
Insulation resistance :
>100M /1000V between enclosure and electrical circuit
Operating Temperature and humidity range :
0 to 40°C 85%RH or less (no condensation)
Storage Temperature and humidity range :
-20 to 60°C 85%RH or less (no condensation)
Power source : DC3V R03 / LR03 (AAA) ×2
Current consumption : < 4mA (LED for NCV O )FF
< 8mA (LED for NCV ON)
Battery life (ACA, continuous, no load, with R03) :
approx. 70 hours (LED for NCV ON)
approx. 170 hours (LED for NCV O )FF
Dimension, Weight :
204(L)×81(W)×36(D)mm,
approx. 220g (including batteries)
A essories :cc
Test leads Model 7066A 1set
Battery R03(AAA) 2pcs
Instruction manual 1pce
Carrying case Model 9079 1pce
3. ACA Me u ment as re
DANGER
Disco ect e test leads from the instrument when nn th
performing a test.
Do not exceed e rated voltage (600V) and e th th
category ratings of e instrument. th
Keep your fingers and hands behind e barrier th
during measurement.
(1) Set the Function switch to ACA position.
(2) Press the trigger to open the Current Sensor and clamp
the one conductor (Dia. 33mm max.) under test.
4. ACV/ V Me u mentDC as re
DANGER
Before starting a measurement, ensure that e th
Fun to th opction switch is set e appr riate position.
Do not exceed e rated voltage (600V) and e th th
category ratings of e instrument. th
Keep your fingers and hands behind e barrier th
during measurement.
(1) Set the Function switch to ACV or DCV position.
(2) Firmly connect the test leads to V/ and COM terminals.
NOTE
If the connection is reversed, the LCD indicates the
“ mark (DCV measurement).
5.R istan (Continuity)Me u ment es ce as re
WARNING
Power o the circuit er test before making ff und
measurements wi is instrument.th th
(1) Set the Function switch to resistance or continuity
position.
(2) Firmly connect the test leads to V/ and COM terminals.
Beeps less than 90 .
NOTE
LCD indicates ”OL” when the test leads are open.
6 Oth Functi s . er on
NCV Function
Red LED for NCV ghts up at A functions except for OFF li ll
when an electric field exceeding AC70V detected by the is
sensor insta ed in Current Sensor.ll
It indicates a presence of voltage in an electrical circuit or
equipment without touching them.
DANGER
The LED may t light due to installation no up
co ition of electrical circuit or equipment. Never nd
t ch the circuit er test to avoid ssible ou und po
danger even if e LED for NCV doesn’t light up. th
The way you hold or place the instrument or
external voltages may affect NCV i ndication.
NCV Sensor can detect electrical field only from the
direction indicated in the below figure.
Put the fixed element (left side) closer to the conductor
under test.
Detection against in-wall outlet is impossible.
Data Hold
Press the Hold key. The LCD shows “ mark and the
reading wi be held.ll
Press the Data Hold Key again to release the display.
Low battery indication
The LCD shows “ ” mark when the batteries fall
below the normal operating voltage.
Sleep Function
Automatically powers off the instrument in about 10 min
after the last switch operation. Buzzer beeps five times
one minute before entering into the Sleep mode, and also
one time just before entering into the mode. To exit from
the Sleep mode, rotate the Fu nction switch or press any
key. To disable the Sleep function, press the HOLD key
and power on the instrument.
Confirm that the LCD shows “ about 1 sec.
7 Ba ery Repl ment . tt ace
WARNING
Replace the batteries when a Low Battery Voltage
warning " " mark is indicated on the LCD. Otherwise,
precise measurement cannot be made.
If batteries are completely exhausted, the LCD goes
blank without showing " " mark.
Do not try to replace the batteries if the surface of the
instrument is wet.
Disconnect the test leads from the object under test and
power off the instrument before opening the Battery
Compartment Cover for battery replacement.
CAUTION
Do not mix old and new batteries.
Install batteries in correct polarity as indicated in
the Battery Compartment.
(1) Set the Function Switch to "O " position.FF
(2) Unscrew and remove the Battery Compartment Cover
on the instrument.
(3) Replace the batteries observing correct polarity.
Use new two AAA 1.5V batteries.
(4) Install the Battery Compartment Cover and tighten the
screw.
1-17 92-2239A
DISTRIBUTOR
Kyoritsu reserves the rights to change specifications
or designs described in this manual without notice
and without obligations.
ACV DCV
Black(-) Red(+)
Resistance
Continuity
Co ect Inco ect rr rr
Red LED lights up in electric
field exceeding AC70V.
Replace the batteries
with new ones when
this mark appears.


Produkt Specifikationer

Mærke: Kyoritsu
Kategori: Multimeter
Model: KEW2117R

Har du brug for hjælp?

Hvis du har brug for hjælp til Kyoritsu KEW2117R stil et spørgsmål nedenfor, og andre brugere vil svare dig




Multimeter Kyoritsu Manualer

Kyoritsu

Kyoritsu KEW2046R Manual

20 September 2024
Kyoritsu

Kyoritsu KEW 2510 Manual

29 August 2024
Kyoritsu

Kyoritsu KEW 2500 Manual

29 August 2024
Kyoritsu

Kyoritsu KEW 2413R Manual

29 August 2024
Kyoritsu

Kyoritsu KT 200 Manual

29 August 2024
Kyoritsu

Kyoritsu 2431 Manual

29 August 2024
Kyoritsu

Kyoritsu 2434 Manual

28 August 2024
Kyoritsu

Kyoritsu KEW 2300R Manual

28 August 2024
Kyoritsu

Kyoritsu KEW2200 Manual

5 August 2024

Multimeter Manualer

Nyeste Multimeter Manualer