Schneider MTN649808 Manual


Læs nedenfor 📖 manual på dansk for Schneider MTN649808 (2 sider) i kategorien niet gecategoriseerd. Denne guide var nyttig for 9 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
The blind actuator REG-K/8x/10 with manual mode
(referred to below as the actuator) can control up to
eight blind/roller shutter drives with limit switch
independently of one another.
You can switch the actuator to manual operation and
check that it works even without ETS programming, and
you can control the connected loads directly at the
actuator in the event of a bus failure.
The actuator has a bus coupler. It is installed on a DIN
rail, with the bus connection made via a bus connecting
terminal. A data rail is not required.
For your safety
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR
ARC FLASH
Safe electrical installation must be carried out only by
skilled professionals. Skilled professionals must prove
profound knowledge in the following areas:
Connecting to installation networks
Connecting several electrical devices
Laying electric cables
Connecting and establishing KNX networks
Safety standards, local wiring rules and regulations
Failure to follow these instructions will result in
death or serious injury.
RISK OF FATAL INJURY FROM ELECTRIC SHOCK
The output may carry electrical current even when the
load is switched off.
When working on the device: Always disconnect the
device from the supply by means of the fuse in the in-
coming circuit.
Even if the manual switch is in the „OFF“ position, a
KNX telegram can switch the connections to being
live at any time. Before working on the device, always
diconnect the fuse in the incoming circuit from the
supply.
Failure to follow these instructions will result in
death or serious injury.
The device may be damaged!
Always operate the product in compliance with the
specified technical data.
Only connect one motor per channel.
Only install devices with at least basic insulation next
to the device.
Failure to follow these instruction can result in
equipment damage.
Blind actuator introduction
It is supplied with power both from the bus voltage and
from the mains. This makes three different operating
modes possible:
Bus and mains supply
This is a standard operating mode. The actuator is
supplied by both the bus and mains voltages.
Bus supply only
The actuator is operated solely in bus mode. It can
continue to carry out all functions, but there may be a
slight time delay (e.g. switching of the relays, slat
adjustment). Manual operation is possible.
Mains supply only
It may only be possible to operate the actuator
manually, without bus communication. You can activate
the loads directly using the channel keys.
AMains connection: The actuator has two connecting
terminals each for the N and L cables (looping is
possible).
BUnder the cable cover: Bus connecting terminal,
programming button and programming LED (red)
COperating LED "RUN" (green)
DManual operation LED "Manual" (red)
EManual operation key "Manual"
FChannel terminals for load voltage
GChannel keys for manual control of the
corresponding channel, only respond when manual
operation is switched on
HChannel status LEDs (yellow) for the corresponding
channel
IFlap forward to open
When and how the LEDs light up
1Set the actuator onto the DIN rail.
Connections, displays and operating
elements
Mains and bus voltage
or bus voltage only
mains voltage only
RUN
(green)
On Off
Manual
(red)
during manual
operation
during manual
operation
Channel
(yellow)
during movement during movement
Mounting the actuator
1
2
1 2
1 2
1 2
1 2
Hand
L L N N
AB
C
D
E
H
I
G
F
1
2
2Connect KNX.
¼
WARNING
Risk of fatal injury from electrical current. The
device could become damaged.
Safety clearance must be guaranteed in
accordance with IEC 60664-1. There must be at
least 4 mm between the individual cores of the
230 V supply cable and the KNX line.
3Connect the mains voltage.
4Switch on bus/mains voltage.
5Wait at least 30 seconds.
After the bus/mains voltage has been switched on, all
the actuator relays are moved to a predefined position
(factory setting: "Off").
6Connect the load.
7Connect the load voltage.
The device may be damaged!
Connect the bus connection and the supply voltage
with correct polarity.
Connect the bus voltage first and only then the load
voltage.
Connections with a 10 A circuit breaker connected
upstream.
If the mains voltage is looped, protect the mains con-
nection with a 10 A circuit breaker connected up-
stream as well.
Failure to follow these instruction can result in
equipment damage.
If the toggle times are too short, the blind motor
could be damaged.!
The toggle time at the factory setting is 500 ms. A
longer toggle time may be necessary for other mo-
tors. Refer to the manufacturer's specifications in the
data sheet for the motor.
Failure to follow these instruction can result in
equipment damage.
1 2
34
5 mm
230 V
4 mm
KNX
L
L
L
L1
10A
10A
1
1
N
N
N
N
KNX
L
L
L2
2
2
10A
SpaceLogic KNX
Blind actuator REG-K/8x/10 with manual
mode
Operating instructions
Art. no. MTN649808
en
Hand


Produkt Specifikationer

Mærke: Schneider
Kategori: niet gecategoriseerd
Model: MTN649808

Har du brug for hjælp?

Hvis du har brug for hjælp til Schneider MTN649808 stil et spørgsmål nedenfor, og andre brugere vil svare dig




niet gecategoriseerd Schneider Manualer

Schneider

Schneider VW3A7740 Manual

5 September 2024
Schneider

Schneider VW3A7746 Manual

5 September 2024
Schneider

Schneider VW3A7752 Manual

5 September 2024
Schneider

Schneider VW3A7742 Manual

5 September 2024
Schneider

Schneider VW3A7737 Manual

5 September 2024
Schneider

Schneider VW3A7745 Manual

5 September 2024
Schneider

Schneider VW3A7733 Manual

5 September 2024
Schneider

Schneider VW3A7748 Manual

5 September 2024

niet gecategoriseerd Manualer

Nyeste niet gecategoriseerd Manualer