User manual
SRG - CENTRAL UNIT FOR GAS DETECTOR
Read all the instructions carefully
 TheSRGisacontrolunitforthecreationofgasdetectionsystemsinareas
suchasboilerrooms,workshops,warehouses,laboratories,etc.Itisdesignedto
workwithprobessuchasCOSensor,CH4SensorandLPGSensor.Itoffersthe
possibilitytocontrolasolenoidvalveoranauxiliarydevice(siren,flasher,etc.)
usinganalarmrelaycontainedinside.ThealarmorfailureisdisplayedbyLED.
SAFETY WARNINGS
To ensure correct installation, you must comply with the following
indications:
1) The device must be installed by a competent person
2) The device must be installed in a panel where, after installation, the terminals
can no longer be accessed
3) In the electrical system up the line from the energy meter there must be a
device to protect against overloads.
4) Connect the instrument following the diagrams shown in this sheet and in the
product marking
5) Before accessing the terminals, make sure the leads to connect to the
instrument are not electrically live
6) Do not power and connect the instrument if any part of it is damaged or
missing.
Code Model Description
VE204400 SRG Gasdetectorwith1connectingsensor
VE205100 CH4 SENSOR Methanedetectionsensor
VE206900 LPG SENSOR LPG sensor
VE207700 CO SENSOR Carbonmonoxidesensor
TECHNICAL CHARACTERISTICS
SRG control unit
• Powersupply:
 −Voltage:12Vac/dc±10%
 −Powerconsumption:~160mA
 −Connection:terminalsof2.5mm
2
 −Protection:fuse1A5x20mm
• Input:
 −1inputforCH4Sensor(methane),LPGSensor(LPG)orCOSensor(CO)
 −Sensorconnection:terminalsof2.5mm
2C(common),S(signal),A(powersupply)
 −Max.lengthofconnection:50m
 −Cross-sectionoftheleads:1.5mm2
• Output:
 −Alarm:relaywithexchangecontact8A/250VAC
 −Failure:opencollector12Vdc/300mAmax
 −Outputconnection:terminalsof2.5mm
2
• Luminoussignals: greenLED:powersupplied
  yellowLED:failure
  redLED:gasalarm
• Reset/testbuttonforalarmresetandprobetestfunctions
• Degreeofprotection:IP20;IP40whencorrectlyinstalledinanelectricalpanel
• Degreeofpollution:II
• Ambienttemperature:0÷+50°C
• Humidity: 90%R.H.withoutcondensation
• Productforassemblyon6-moduleDINrails
Sensors for SRG control units
• Powersupply:fromthecontrolunitSRG
 −Currentinput(at6.5V):40mA
 −Connection:terminalsof2.5mm
2C(common),S(signal),A(powersupply)
• Modelsandcalibration:
 −Methanegas:CH4Sensor,(default)10%LIEofmethane
 −LPG:LPGSensor,(default)12%LIEofisobutene
 −Carbonmonoxide:COSensor,(default)200ppmofcarbonmonoxide
• Container:inself-extinguishingplasticmaterial
• Fastenedtowallusingscrewsandplasticplugs
• Protection:IP30
• Ambienttemperature:0÷+50°C
• Humidity: 90%R.H.withoutcondensation
INSTRUMENT DESCRIPTION
 Ledpowersupply
Led signaling failure
Led signaling gas alarm
 Reset/Testbutton
 Powersupplyterminals
Terminals for open collector failure
g
 Terminalsforalarmoutputrelay
h
Terminals for gas sensor connection
 Set-upjumper
j
 Protectionfuse1A
INSTALLATION
Do not use the device in excess of the limits set forth in the technical data. The installer is
responsible for correct, safe installation of the product. Use care during shipping, storage
and handling.
1) Protectionofthedevice.
 Toensuretheproperdegreeofprotectionoftheunit,itisnecessarytoinstallthecontrol
unitinanelectricalpanelconstructedinaccordancewithcurrentstandardsforthe
workplace,andinsideofwhichthepowersupplysystemcanalsobehoused.Thecontrol
unitcanbeinstalledatthebottomofthepanelorinDINmodularpanels.
 TheLPG,COandCH4Sensorsaredesignedtobewall-mounted(vertically),usingscrews
andplasticplugs.Toproceedwithinstallation,openthecontainerbyunscrewingthe
screwlocatedontheside.Makesurenottodamagethesensorandnottotouchthe
calibration devices.
2) Installationoftheproduct.
 Thecorrectinstallationoftheprobeisessentialtoproperoperationofthesystem.
Therefore,itmustbeinstalled:
 –Inareaswithcirculationofnaturalair;
 –Inareasthatarenotsubjecttodustordirtthatmayrenderthesensorinoperative;
–Nearjetsofwater,intakegrilles,openings,etc;
 –Atanadequatedistancefromusersofgassoastopreventthesystemfromintervening
improperlyduetofunctionalleakage.
 Also,positioningdependsonthetypeofgastobedetected,specifically:
– CH4 Sensor: Methane gas - at top, about 20-30 cm from the ceiling
– LPG Sensor: LPG - at bottom, about 20-30 cm from the floor
– CO Sensor: carbon monoxide – about 1.5 m from the floor
 Fornewsystems,theprobemustbeinstalledaslateaspossible,sothattypical
constructionsiteactivitiesdonotdamagethedetector.
3) Connectionsanduseoftheproduct.
 Normalelectricalcablescanbeusedforconnections.Inanycase,wheninstallationis
inplacesthatarestronglyexposedtoelectromagneticdisturbances,itisadvisableto
useshieldedcables.Thedetectionsystemmustalwaysbeinoperation.Therefore,the
electricalpowersupplyofthedetectormustnotincludeswitchesorotherdevicesthat
mayaccidentallyshutitoff.Thepowersupplyofthecontrolunitmustcomplywiththe
requiredvaluesandthecurrentinputofanydeviceconnecttotheterminalsoftherelay
mustbelessthanorequaltothemaximumcapacityofthecontacts.Theaveragelifespan
oftheprobesis5yearsfromthedateofinstallation.Therefore,attheendofthattime
theywillneedtobereplaced.
Attention: make sure you check operation at least once a year, and in any case
whenever there is an extended period of disuse or in the event of replacement.
Any tampering may compromise correct operation of the system.
OPERATION
 Oncethedevicehasbeeninstalled,youwillneedtoselecttheoperatinglogicusing
jumperE1.Itcanbeeitherpositiveornegative.Thecontrolunitsignalsitsoperating
statusbymeansofLED’s.
A
Position A
Positive logic
Position B
Negative logic
B
A
B
E1
E1
E1
A
B
 DependingonthelogicselectedusingjumperE1,inanormalsituation(noalarms),the
LED’sandtherelaywillbe:
 –positivelogic:LEDon,relayenergized
 –negativelogic:LEDoff,relayde-energized
 Ifnegativeoperatinglogicisselected,thealarmrelaymaybecontrolledinpermanentor
impulsivemode,dependingonthepositionofjumperE2:
A
Position A
Alarm relay
Permanent control
Position B
Alarm relay
Impulsive control
B
A
B
E2
E2
E2
A
B
 Oncepoweredon,thecontrolunitperformsthefollowingphasesinsequence:
• Buzzertest(durationabout5seconds)whichcausessequentiallightingoftheLED’sand
abriefringingofthebuzzer.
• Pre-heatingoftheprobe(whichlastsabout1minute),duringwhichthedetection
systemisnotoperationalbecausethisallowstheprobetoreachthecorrectoperating
temperature.
Dimensions
Connection diagram
Description
• Operationaltest(whichlastsabout3minutes)duringwhichthepowersupplyLED
flasheswithafrequencyof2Hzandalltimesettingsareresettozerotomakeiteasierto
checktheprobe.PresstheReset/Testforaboutonesecondtointerrupttheoperational
testphaseandchecktheprobe.
• Gasalarmtest,whichoccursbyplacingthetestspraycanneartheprobeandreleasing
asmallamountofgas.Donotdirectthespraydirectlyontothesensoroftheprobe,
asitmaydamageitirreparably.Thecontrolunitwillsignalthealarminthefollowing
manner:
Interface Positive logic Negative logic
Led for probe alarm(red) Off On
Alarmbuzzer Continuous sound Continuous sound
Alarmrelay De-energized Energized(permanentlyor
in impulsive mode)
 PresstheReset/Testkeyforonesecondtosilencethealarm(ifthegasisnolonger
present)andendthetestphase.Torestartthetestphase,pressthecorrespondingbutton
for about 6 seconds.
• Probefailuretest,whichistobesimulatedsimplybydisconnectingtheprobecableand
checkingthefollowingsignals:
Interface Positive logic Negative logic
Led for probe failure(yellow) Off On
Alarmbuzzer Intermittent sound Intermittent sound
Faulureoutput Off On
 Oncethetesthasbeenmade,re-connecttheprobeandpresstheReset/Testbuttonto
restorethecontrolunittonormaloperation.
Normal operation
 Duringnormaloperationofthecontrolunit,boththemonitoringforgasalarmandthe
self-diagnosisforplantanomalies(probe)andsystemsanomalies(controlunit)areactive.
Inthisphaseandwithnoalarmsorfailures,thecontrolunitstatusisasfollows:
Interface Positive logic Negative logic
Led (green)forpowersupply On On
Led for failure(yellow) On Off
Led for gas alarm(red) On Off
Alarmbuzzer Nosound Nosound
Alarmrelay De-energizedEnergized
Faulureoutput On Off
 Inpresenceofgasalarmorprobefailure,thecentralunitgoesintothesameconditions
describedintherelativestestphase.
REFERENCE STANDARDS
ConformitytotheEUdirectives
2006/95/EC(LowVoltage)
89/336/ECmodifiedby92/31/ECCand93/68/EEC(E.M.C.)
isdeclaredwithreferencetothefollowingharmonisedstandard:
EN 61779-1, EN 50270


Produkt Specifikationer

Mærke: Vemer
Kategori: Gasdetektor
Model: SRG

Har du brug for hjælp?

Hvis du har brug for hjælp til Vemer SRG stil et spørgsmål nedenfor, og andre brugere vil svare dig




Gasdetektor Vemer Manualer

Vemer

Vemer RGM Wave Manual

9 August 2024
Vemer

Vemer VALV-34NA Manual

29 Juli 2024
Vemer

Vemer RGCO Manual

22 Juli 2024
Vemer

Vemer VALV-12NC Manual

7 Oktober 2023
Vemer

Vemer SRG.4 Manual

2 April 2023
Vemer

Vemer VALV-1NA Manual

22 December 2022
Vemer

Vemer RGG Wave Manual

16 December 2022
Vemer

Vemer VALV-34NC Manual

1 November 2022
Vemer

Vemer SRG Manual

10 Oktober 2022

Gasdetektor Manualer

Nyeste Gasdetektor Manualer

Vimar

Vimar 16592 Manual

15 December 2024
Aeroqual

Aeroqual AQ-500 Manual

13 December 2024
Protector

Protector C11-L Manual

11 December 2024
Pentatech

Pentatech GA60 Manual

24 November 2024
Kidde

Kidde KN-COPF-i Manual

27 September 2024
Kidde

Kidde 900-0280CA Manual

24 September 2024
Kidde

Kidde 900-0263CO-CA Manual

24 September 2024
Elro

Elro FW3801R Manual

22 September 2024