Vemer SRG.4 Manual


Læs nedenfor 📖 manual på dansk for Vemer SRG.4 (2 sider) i kategorien Gasdetektor. Denne guide var nyttig for 50 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
ON
SRG.4
1 2 3 4
TEST
RESET
Mod. SRG.4
V3IS00460–010
86.7
159.5
50.5
12.0
58.0
86.7
50.5 50.5
C1 S1 A1 C2 S2 A2 C3 S3 A3 C4 S4 A4
1 2 3 4
SENSORS
+ –
1
2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
8A / 250V 8A / 250V
1
2
V
a
c
/
d
c
Description
 
g 
h
j 
User manual
SRG.4 - CONTROL UNIT FOR GAS DETECTOR
Read all the instructions carefully
 TheSRG.44isacontrolunitforthecreationofgasdetectionsystemsinareas
suchasboilerrooms,workshops,warehouses,laboratories,etc.Itisdesignedto
workwithprobessuchasCOSensor,CH4SensorandLPGSensor.Itoffersthe
possibilitytocontrolasolenoidvalveoranauxiliarydevice(siren,flasher,etc.)
usinganalarmrelaycontainedinside.ThealarmorfailureisdisplayedbyLED.
SAFETY WARNINGS
To ensure correct installation, you must comply with the following
indications:
1) The device must be installed by a competent person
2) The device must be installed in a panel where, after installation, the terminals
can no longer be accessed
3) In the electrical system up the line from the energy meter there must be a
device to protect against overloads
4) Connect the instrument following the diagrams shown in this sheet and in the
product marking
5) Before accessing the terminals, make sure the leads to connect to the
instrument are not electrically live
6) Do not power and connect the instrument if any part of it is damaged or
missing.
Codice Model Description
VE203600 SRG.4 Gasdetectorwith4connectingsensor
VE205100 CH4 SENSOR Methanedetectionsensor
VE206900 LPG SENSOR LPG sensor
VE207700 CO SENSOR Carbonmonoxidesensor
TECHNICAL CHARACTERISTICS
Control unit SRG.4
• Powersupply:
 −Voltage:12Vac/dc±10%
 −Powerconsumptionwith1probe:~160mA
 −Powerconsumptionwith4probes:~280mA
 −Connection:terminalsof2.5mm
2
 −Protection:fuse1A5x20mm
• Inputs:
 −4inputsforCH4Sensor(methane),LPGSensor(LPG),COSensor(CO).
 −Connectionofprobes:terminalsof2.5mm
2 per probe
 −Max.connectionlength:50mforeachprobe
 −Cross-sectionoftheleads:1.5mm2
• Output:
 −Alarm:relaywithexchangecontact8A/250VAC
 −Failure:relaywithexchangecontact8A/250VAC
 −Connection:terminalsof2.5mm
2forrelayC-NC-NO
• Luminoussignals: 1greenLED:powersupplied
 1yellowLED:generalfailure
  4yellowLED’s:failureforeachprobeline
  4redLED’s:gasalarmforeachprobeline
• Reset/testbuttonforalarmresetandprobetestfunctions
• Degreeofprotection:IP20;IP40whencorrectlyinstalledinanelectricalpanel
• Ambienttemperature:0÷+50°C
• Humidity: 90%R.H.withoutcondensation
• Productforassemblyon9-moduleDINrails
Sensors for SRG.4 control units
• Powersupply:fromthecontrolunitSRG.4
 −Currentinput(at6.5V):40mA
 −Connections:terminalsof2.5mm
2forprobeC(common),S(signal),A(power6.5Vdc)
• Modelsandcalibration:
 −Methanegas:CH4Sensor,(default)10%LIEofmethane
 −LPG:LPGSensor,(default)12%LIEofisobutene
 −Carbonmonoxide:COSensor,(default)200ppmofCO
• Container:inself-extinguishingplasticmaterial
• Fastenedtowallusingscrewsandplasticplugs
• Protection:IP30
• Ambienttemperature:0÷+50°C
• Humidity: 90%R.H.withoutcondensation
INSTRUMENT DESCRIPTION
 Ledpowersupply
Led signaling general failure
 Reset/Testbutton
Led signaling failure probes
Led signaling gas alarm
 Powersupplyterminals
g
Connection probes terminals
h
 Protectionfuse1A
 Set-upjumper
j
 Terminalsforalarmoutputrelay
 Terminalsforfailureoutputrelay
INSTALLATION
Do not use the device in excess of the limits set forth in the technical data. The installer is
responsible for correct, safe installation of the product. Use care during shipping, storage
and handling.
1) Protectionofthedevice.
 Toensuretheproperdegreeofprotectionoftheunit,itisnecessarytoinstallthecontrol
unitinanelectricalpanelconstructedinaccordancewithcurrentstandardsforthe
workplace,andinsideofwhichthepowersupplysystemcanalsobehoused.Thecontrol
unitcanbeinstalledatthebottomofthepanelorinDINmodularpanels.
 TheLPG,COandCH4Sensorsaredesignedtobewall-mounted(vertically),usingscrews
andplasticplugs.Toproceedwithinstallation,openthecontainerbyunscrewingthe
screwlocatedontheside.Makesurenottodamagethesensorandnottotouchthe
calibration devices.
2) Installationoftheproduct.
 Thecorrectinstallationoftheprobeisessentialtoproperoperationofthesystem.
Therefore,itmustbeinstalled:
 –Inareaswithcirculationofnaturalair;
 –Inareasthatarenotsubjecttodustordirtthatmayrenderthesensorinoperative;
 –Nearjetsofwater,intakegrilles,openings,etc.
 –Atanadequatedistancefromusersofgassoastopreventthesystemfromintervening
improperlyduetofunctionalleakage.
 Also,positioningdependsonthetypeofgastobedetected,specifically:
 –CH4:Methanegas-attop,about20-30cmfromtheceiling
 –LPG:LPG-atbottom,about20-30cmfromthefloor
 –CO:carbonmonoxide–about1.5mfromthefloor
 Fornewsystems,theprobemustbeinstalledaslateaspossible,sothattypical
constructionsiteactivitiesdonotdamagethedetector.
Attention: make sure you check operation at least once a year, and in any case
whenever there is an extended period of disuse or in the event of replacement.
Any tampering may compromise correct operation of the system.
3) Connectionsanduseoftheproduct.
 Normalelectricalcablescanbeusedforconnections.Inanycase,wheninstallationis
inplacesthatarestronglyexposedtoelectromagneticdisturbances,itisadvisableto
useshieldedcables.Thedetectionsystemmustalwaysbeinoperation.Therefore,the
electricalpowersupplyofthedetectormustnotincludeswitchesorotherdevicesthat
mayaccidentallyshutitoff.Thepowersupplyofthecontrolunitmustcomplywiththe
requiredvaluesandthecurrentinputofanydeviceconnecttotheterminalsoftherelay
mustbelessthanorequaltothemaximumcapacityofthecontacts.Theaveragelifespan
oftheprobesis5yearsfromthedateofinstallation.Therefore,attheendofthattime
theywillneedtobereplaced.
Attention: in the case in which in every single terminal block of the control
unit missed the probes, there must be a resistence of 18KOhm 1/4 W 5%
between C ans S furnisced in the box.
OPERATION
 Oncethedevicehasbeeninstalled,youwillneedtoselecttheoperatinglogicusing
jumperE1.Itcanbeeitherpositiveornegative.Thecontrolunitsignalsitsoperating
statusbymeansofLED’s.
A
Position A
Positive logic
Position B
Negative logic
B
A
B
E1
E1
E1
A
B
 DependingonthelogicselectedusingjumperE1,inanormalsituation(noalarms),the
LED’sandtherelaywillbe:
 –positivelogic:LEDon,relayenergized
 –negativelogic:LEDoff,relayde-energized
 Ifnegativeoperatinglogicisselected,thealarmrelaymaybecontrolledinpermanentor
impulsivemode,dependingonthepositionofjumperE2:
A
Position A
Alarm relay
Permanent control
Position B
Alarm relay
Impulsive control
B
A
B
E2
E2
E2
A
B
Dimensions
Connection diagram
 Oncepoweredon,thecontrolunitperformsthefollowingphasesinsequence:
• Buzzertest(durationabout5seconds)whichcausessequentiallightingoftheLED’sand
abriefringingofthebuzzer.
• Pre-heatingoftheprobe(whichlastsabout1minute),duringwhichthedetection
systemisnotoperationalbecausethisallowstheprobestoreachthecorrectoperating
temperature.
• Operationaltest(whichlastsabout3minutes)duringwhichthepowersupplyLED
flasheswithafrequencyof2Hzandalltimesettingsareresettozerotomakeiteasierto
checktheprobes.PresstheReset/Testforaboutonesecondtointerrupttheoperational
testphaseandchecktheprobes.
• Gasalarmtest,whichoccursbyplacingthetestspraycanneartheprobeandreleasing
asmallamountofgas.Donotdirectthespraydirectlyontothesensoroftheprobe,
asitmaydamageitirreparably.Thecontrolunitwillsignalthealarminthefollowing
manner:
Interface Positive logic Negative logic
Led for alarm (red)
of concerned probe
Off On
Alarmbuzzer Continuous sound Continuous sound
Alarmrelay De-energized Energized(permanentlyor
in impulsive mode)
 PresstheReset/Testkeyforonesecondtosilencethealarm(ifthegasisnolonger
present)andendthetestphase.Torestartthetestphase,pressthecorrespondingbutton
for about 6 seconds.
• Probeanomalytest,whichistobesimulatedsimplybydisconnectingtheconcerned
probecableandcheckingthefollowingsignals:
Interface Positive logic Negative logic
Led for failure (yellow)
of concerned probe
Off On
Alarmbuzzer Intermittent sound Intermittent sound
Failurerelay De-energized Energized
 Oncethetesthasbeenmade,re-connecttheprobeandpresstheReset/Testbuttonto
restorethecontrolunittonormaloperation.
Normal operation
 Duringnormaloperationofthecontrolunit,boththemonitoringforgasalarmand
theself-diagnosisforplantanomalies(probes)andsystemsanomalies(controlunit)are
active.Inthisphaseandwithnoalarmsorfailures,thecontrolunitstatusisasfollows:
Interface Positive logic Negative logic
Led (green)forpowersupply On On
Led for general failure(yellow) On Off
Led for probe failure (4)(yellow) On Off
Led for general alarm and (red)
line failure (4)
On Off
Alarmbuzzer No sound No sound
Alarmrelay De-energizedEnergized
Failurerelay De-energizedEnergized
 Inpresenceofgasalarmorprobefailure,thecentralunitgoesintothesameconditions
describedintherelativestestphase.
REFERENCE STANDARDS
ConformitytotheEUdirectives
2006/95/EC(LowVoltage)
89/336/ECmodifiedby92/31/ECCand93/68/EEC(E.M.C.)
isdeclaredwithreferencetothefollowingharmonisedstandard:
EN 61779-1, EN 50270


Produkt Specifikationer

Mærke: Vemer
Kategori: Gasdetektor
Model: SRG.4

Har du brug for hjælp?

Hvis du har brug for hjælp til Vemer SRG.4 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Gasdetektor Vemer Manualer

Vemer

Vemer RGM Wave Manual

9 August 2024
Vemer

Vemer VALV-34NA Manual

29 Juli 2024
Vemer

Vemer RGCO Manual

22 Juli 2024
Vemer

Vemer VALV-12NC Manual

7 Oktober 2023
Vemer

Vemer SRG.4 Manual

2 April 2023
Vemer

Vemer VALV-1NA Manual

22 December 2022
Vemer

Vemer RGG Wave Manual

16 December 2022
Vemer

Vemer VALV-34NC Manual

1 November 2022
Vemer

Vemer SRG Manual

10 Oktober 2022

Gasdetektor Manualer

Nyeste Gasdetektor Manualer

Vimar

Vimar 16592 Manual

15 December 2024
Aeroqual

Aeroqual AQ-500 Manual

13 December 2024
Protector

Protector C11-L Manual

11 December 2024
Pentatech

Pentatech GA60 Manual

24 November 2024
Kidde

Kidde KN-COPF-i Manual

27 September 2024
Kidde

Kidde 900-0280CA Manual

24 September 2024
Kidde

Kidde 900-0263CO-CA Manual

24 September 2024
Elro

Elro FW3801R Manual

22 September 2024